—MS2 Two Stage Electronic Temperature Control Installation Bulletin 

Table 3: Functions and Settings 

Mode 

2d

 = Direct 

2r

 = Reverse 

2b

 = Deadband 

2i

 = Independent Setpoint 

Setting 

Description 

Setting Range 

Default 

SI

 

Setpoint 

Modes d, r, b:  relay cut-off point 
Mode i: 

heating independent setpoint 

-40 to 99°F  
(-40 to 70°C) 

— 

HI

 

Differential (Hysteresis) 

Temperature difference relative to setpoint or offset at 
which the load is switched On or Off 

1 to 9F° (1 to 9C°) 

S2

 

Setpoint 2 (Offset) 

Modes d, r: 

difference between setpoint and Stage 2 

Mode b: 

deadband (centered on setpoint) 

Mode I: 

cooling independent setpoint 

d, r:  1 to 40F°  
 

(1 to 40C°) 

b: 

2 to 40F°  

 

(2 to 40C°) 

I: 

LL

 to 

HL

H2

 

Differential (Hysteresis) 2 

See Differential (hysteresis) 

1 to 9F° (1 to 9C°) 

LL

 

Low Setpoint Stop 

Lower limit of end-user setpoint adjustment 

-40F° (-40C°) to 

HL

 

32 

HL

 

High Setpoint Stop 

Upper limit of end-user setpoint adjustment 

LL

 to 99°F (70°C) 

90 

Cc

 

Anti-short Cycle Timer, 

 

Cool 

Time delay between equipment On cycles for cooling 
stages 

0 to 9 minutes 

CH

  Anti-short Cycle Timer, 

 

Heat 

Time delay between equipment On cycles for heating 
stages 

0 to 9 minutes 

rt

  Soft Start 

Rate at which process temperature approaches setpoint 

0 to 99 
minutes/degrees 

10 

AH

  High Temperature Alarm 

High temperature alarm setpoint relative to main setpoint  0 to 50F° (0 to 50C°) 

above setpoint  

15 

AL 

Low Temperature Alarm 

Low temperature alarm setpoint relative to main setpoint 

-50 to 0F° (-50 to 0C°) 
below setpoint 

-15 

Ad

 

Alarm Differential 

Temperature difference relative to high and low alarms at 
which alarm output is switched Off  

1 to 9F° (1 to 9C°) 

At

 

Alarm Time Delay 

Delay between alarm detection and activation 

0 to 99 minutes 

15 

So

 

Sensor Offset 

Compensates for long sensor leads or sensor location 

-20 to +20F° 
(-20 to +20C°) 

Un

 

Units Used 

Temperature units used  

0 = °C  1 = °F 

PU

 

Display Refresh Rate 

Time delay between display refreshes 

1 to 99 seconds 

IF

 

Binary Input Function 

Configuration for normally closed binary input 

0 = No binary input 
1 = Shutoff/alarm  
 

 signaling  

2 = Setback 
3 = Remote shutoff 

Sb

 

Setback 

Value of setpoint shift when binary input is open and 

IF

=2  0 to 20F° (0 to 20C°) 

10 

Id

  Binary Input Time Delay 

Time between binary input detection and enabling of 

IF

 

0 to 99 minutes 

iS

  Interstage Time Delay 

Minimum amount of time between two successive stages  3 to 90 seconds 

R

epair and Replacement 

Field repair must not be made. In case of defective or 
improperly functioning control, contact your nearest 
authorized Johnson Controls/PENN distributor. 

When requesting a replacement, reference the model 
number found on the data plate of the control. 

Содержание MS2

Страница 1: ... version ensure that there is sufficient space behind the panel At least 2 3 4 inches 70 mm are needed Make a cutout 1 3 16 by 2 13 16 inches 29 by 71 mm Remove retaining clip from control Insert the control into the hole Install retaining clip and adjust for tightness Wiring WARNING Risk of Electrical Shock Disconnect power supply before making electrical connections to avoid possible electrical ...

Страница 2: ...input status On or OF After 15 seconds of inactivity the display shows the process temperature Setting Up the Stage Control To lock unlock the unit for programming Press the Enter Up and Down buttons simultaneously and hold until is displayed Hold for about 10 seconds until the current temperature is displayed This toggles the keypad between locked and unlocked To run the self test procedure IMPOR...

Страница 3: ...A MS2 Two Stage Electronic Temperature Control Installation Bulletin 3 value it is not saved The control reverts to the old value ...

Страница 4: ... degrees 10 AH High Temperature Alarm High temperature alarm setpoint relative to main setpoint 0 to 50F 0 to 50C above setpoint 15 AL Low Temperature Alarm Low temperature alarm setpoint relative to main setpoint 50 to 0F 50 to 0C below setpoint 15 Ad Alarm Differential Temperature difference relative to high and low alarms at which alarm output is switched Off 1 to 9F 1 to 9C 5 At Alarm Time Del...

Страница 5: ...set Ordering Information Table 6 Specifications Power Requirements 3 7 VA 24 VAC 50 60 Hz Class 2 20 30 VAC Ambient Conditions Operating 14 to 140 F 10 to 60 C 0 to 95 RH non condensing Storage 22 to 176 F 30 to 80 C 0 to 95 RH non condensing Accuracy 1 8 F 1C Agency Listings UL Recognized File E194024 CCN XAPX2 Canadian UL Recognized File E194024 CCN XAPX8 FCC Compliant per Class A Digital Device...

Отзывы: