The data protection battery slowly loses charge when 24
VAC power is removed from the NCM. If the battery
completely loses charge, the NCM real-time clock stops.
The database and code, however, are still retained. (This
is different from the NCM300 Series model, in which only
72 hours of backup was provided, after which the unit
required a download.)

Whenever an NCM is disconnected from 24 VAC power
for over 30 days, ensure that the unit has the correct date
and time. Also, keep the NCM powered long enough to
recharge the data protection battery.

Setting the End-of-Line Switch

Network and field devices at either end of the N2 Bus
must be set as network terminated devices. The

NCM

has an

EOL

switch that allows you to set the NAE as a

network terminated device. The NCM is shipped with the
EOL switch in the factory default, ON (up) position (

Figure

8

). Set the EOL switch to the appropriate position for each

NCM in your network. For more details, refer to the
Setting Terminations section of the

N2 Communications

Bus Technical Bulletin (LIT-636018)

.

Figure 8: FC Bus EOL Switch in the Factory Default

ON (Up) Position

Turning On the NCM

Apply 24 VAC power to the

NCM

and verify that the RUN

LED begins to flash. This indicates normal operation. If
this is a new NCM from the factory, the RUN LED
continues to flash, indicating that the unit needs to be
commissioned with WNCSETUP. Refer to the

NCM45x0-2

Network Control Module Commissioning Guide
(LIT-12011176)

for additional information on

commissioning an NCM.

Disconnecting Power from the NCM

When 24 VAC supply power to an

NCM

is disconnected

or lost, the NCM is non-operational, but the POWER LED
(

Figure 9

remains On and the data protection battery

continues to power the NCM for a few minutes while
volatile data is backed up in nonvolatile memory. The
RUN LED flashes during this process. When complete,
all LEDs go Off.

Important:

Do not disconnect the battery while the unit
is shutting down, or the data being saved
may be corrupted.

Important:

The data protection battery must be installed
and charged before disconnecting the 24
VAC supply power.

Troubleshooting

LED Status Indicators

The

NCM

has nine LEDs to indicate power and network

communication status.

Figure 9

shows the LEDs and

describes the LED indications. For the NCM4510-2 model,
the

FC

Bus LED indicates network traffic over the N2

Bus. For the NCM4520-2 model, the LON LED indicates
network traffic over the LON Network. All the other LEDs
are the same on both models.

Figure 9: NCM LED Designations

LED Test Sequence at Startup

When you connect power to the

NCM

, it initiates a

2-second LED test to verify the operational status of its
LEDs. After this test, the operating system is loaded, the
NCM application starts, the NCM database is loaded from
flash memory (or, if not present, downloaded from the

OWS

), and NCM initialization occurs. A steady On RUN

LED indicates a fully initialized NCM. If the RUN LED
continues to blink for several minutes, verify whether the
NCM database was successfully downloaded from the
archive Operator Workstation. You can also examine the

Network Controller (NC)

Task Error Log, which may

provide useful information for diagnosing startup
problems. For details, refer to the

NCM45x0-2 Network

Control Module Commissioning Guide (LIT-12011176)

.

For more information about the other possible behaviors
of the NCM LEDs, see

Table 6

.

8

NCM45x0-2 Series Network Control Module Installation Instructions

Содержание MS-NCM4510-2

Страница 1: ...ouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Canada This Class B digital apparatus meets...

Страница 2: ...connections Figure 1 Do not mount the NCM where the ambient temperature may exceed 50 C 122 F Do not mount the NCM on surfaces that are prone to vibration or in areas where electromagnetic emissions can interfere with NCM communication Do not obstruct the NCM housing ventilation holes Do not mount the power transformer below the NCM For applications where the NCM is mounted inside a panel or enclo...

Страница 3: ...losure Mount Applications Mount the enclosure per the manufacturer s instructions and mount the NCM in the enclosure following the guidelines in the Location Considerations and Mounting the NCM sections Legacy NCM Replacement Considerations Follow these important guidelines if the NCM is to replace an existing NCM350 361 controller The unit size and mounting orientation of the NCM45x0 2 are notice...

Страница 4: ...n the new NCM database configuration changes are required Refer to the NCM45x0 2 Network Control Module Commissioning Guide LIT 12011176 for details Before removing the NCM350 361 upload its database to the archive Operator Workstation OWS so that it can be edited later and eventually downloaded into the new controller Refer to the NCM45x0 2 Network Control Module Commissioning Guide LIT 12011176 ...

Страница 5: ...NCM and void any warranties Important Make sure the building automation network wiring meets the specifications rules and guidelines in the Power Supply Network and Communication Connections section in this document Important For the NCM4510 2 model do not remove the plug that is inserted into the top FC Bus terminal or install any connector into this port The port is only used if the unit is migr...

Страница 6: ...Considerations and Guidelines for Network Integrations Table 1 Guidelines for N2 Network Topology Rules Maximums Allowed Category One N2 trunk per NCM General Only daisy chained devices with maximum stub length of 3 m 10 ft to any device 100 devices per NCM 60 to 200 TC 9100s 50 devices per repeater with two repeaters cascaded Number of N2 Devices Supported 1 500 m 5 000 ft twisted pair cable with...

Страница 7: ...ent Physical Layer Repeaters 1 Each LPT10 channel segment between repeaters requires its own power supply Other factors such as power consumption of individual LPT10 devices may limit a segment to fewer devices The NCM does not have an internal network terminator Table 5 NCM Ethernet Network Rules Rules Maximums Allowed 1 Category Point to point star topology with network hubs switches General Max...

Страница 8: ...erational but the POWER LED Figure 9 remains On and the data protection battery continues to power the NCM for a few minutes while volatile data is backed up in nonvolatile memory The RUN LED flashes during this process When complete all LEDs go Off Important Do not disconnect the battery while the unit is shutting down or the data being saved may be corrupted Important The data protection battery...

Страница 9: ...ked up Connect or install battery Off Steady BATT FAULT Red On Momentarily then Off Internal fault has occurred Off Steady FAULT Red Repair Information If you replace an NCM on a site with a new NCM for any reason or add a new NCM to a site you must update the system database to ensure that the new NCM is recognized and able to communicate with the site Refer to the NCM45x0 2 Network Control Modul...

Страница 10: ...n on power failure Rechargeable NiMH battery 3 6 VDC 500 mAh with a typical life of 5 to 7 years at 21 C 70 F Product Code Number MS BAT1020 0 Data Protection Battery 192 MHz Renesas SH4 7760 RISC processor Processor 128 MB Flash nonvolatile memory 128 MB Synchronous Dynamic Random Access Memory SDRAM Note Even though the unit has 128 MB of memory it is sized to emulate the capacity of an NCM300 S...

Страница 11: ...Compliance The performance specifications are nominal and conform to acceptable industry standard For application at conditions beyond the specifications consult the local Johnson Controls office Johnson Controls Inc shall not be liable for damages resulting from misapplication or misuse of its products Building Efficiency 507 E Michigan Street Milwaukee WI 53202 Metasys and Johnson Controls are r...

Отзывы: