background image

Refer to the

NCM45x0-2 Network Control Module

Commissioning Guide (LIT-12011176)

for information

about these different types of direct and dial-up
connections to the NCM.

The RS232C B/Port 5 serial port can be used for these
applications: configured OWS, printer, modem, OT, or
local

Network Terminal (NT)

. Refer to the

NCM45x0-2

Network Control Module Commissioning Guide
(LIT-12011176)

for more information about these options.

USB Port

The USB port is not used. Do not connect any device to
this port.

Ethernet Port

The Ethernet connection (10 or 100 Mb/s) is an 8-pin
RJ-45 network port (

Figure 1

). Use the Ethernet port to

connect to IP networks. An NCM45x0-2 with a 100 Mb/s
connection communicates properly with older NCMs that
are communicating at 10 Mb/s.

Wiring the NCM

Important:

Do not connect 24 VAC supply power to the

NCM

before finishing wiring and checking

all wiring connections. Short circuits or
improperly connected wires may result in
permanent damage to the equipment.

Important:

Use copper conductors only. Make all wiring
in accordance with local, national, and
regional regulations. The NCM is a
low-voltage (<30 VAC) device. Do not
exceed the NCM electrical ratings.

Important:

Do not remove the terminal block keys. The
terminal block plugs and the terminal
sockets are keyed to fit together in the
correct configuration only.

Important:

Prevent any static electric discharge to the
NCM. Static electric discharge can damage
the NCM and void any warranties.

Important:

Make sure the building automation network
wiring meets the specifications, rules, and
guidelines in the

Power Supply, Network,

and Communication Connections

section

in this document.

Important:

For the NCM4510-2 model, do not remove
the plug that is inserted into the top

FC

Bus

terminal, or install any connector into this
port. The port is only used if the unit is
migrated to an NAE45 sometime in the
future.

Mount the NCM securely before wiring the NCM. See the

Mounting

section.

Follow these guidelines when wiring an NCM:

Route the supply power wires and communication
cables at least 50 mm (2 in.) away from the vent slots
on the sides of the NCM housing.

Provide slack in the wires and cables. Keep cables
routed neatly around the NCM to promote good
ventilation, LED visibility, and ease of service.

To wire the NCM:

1. Connect the Ethernet communication cable to the

RJ-45, 8-pin Ethernet port shown in

Figure 1

.

2. For the NCM4510-2, connect the three N2 Bus wires

to the removable 4-terminal plug as shown in

Figure

5

(labeled FC Bus). If a shield is present, follow

standard practices for terminating a shield that are
discussed in the N2 Bus literature. Refer to the

N2

Communications Bus Technical Bulletin (LIT-636018)

.

Note:

If the NCM is connected to an N2 Bus, you
must set the

End-of-Line (EOL)

switch to the

proper position. See the

Setting the

End-of-Line Switch

section in this document.

Figure 5: N2 Bus Wiring

3. For the NCM4520-2, connect the wires from the LON

network trunk to the removable 3-terminal plug as
shown in

Figure 6

.

5

NCM45x0-2 Series Network Control Module Installation Instructions

Содержание MS-NCM4510-2

Страница 1: ...ouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Canada This Class B digital apparatus meets...

Страница 2: ...connections Figure 1 Do not mount the NCM where the ambient temperature may exceed 50 C 122 F Do not mount the NCM on surfaces that are prone to vibration or in areas where electromagnetic emissions can interfere with NCM communication Do not obstruct the NCM housing ventilation holes Do not mount the power transformer below the NCM For applications where the NCM is mounted inside a panel or enclo...

Страница 3: ...losure Mount Applications Mount the enclosure per the manufacturer s instructions and mount the NCM in the enclosure following the guidelines in the Location Considerations and Mounting the NCM sections Legacy NCM Replacement Considerations Follow these important guidelines if the NCM is to replace an existing NCM350 361 controller The unit size and mounting orientation of the NCM45x0 2 are notice...

Страница 4: ...n the new NCM database configuration changes are required Refer to the NCM45x0 2 Network Control Module Commissioning Guide LIT 12011176 for details Before removing the NCM350 361 upload its database to the archive Operator Workstation OWS so that it can be edited later and eventually downloaded into the new controller Refer to the NCM45x0 2 Network Control Module Commissioning Guide LIT 12011176 ...

Страница 5: ...NCM and void any warranties Important Make sure the building automation network wiring meets the specifications rules and guidelines in the Power Supply Network and Communication Connections section in this document Important For the NCM4510 2 model do not remove the plug that is inserted into the top FC Bus terminal or install any connector into this port The port is only used if the unit is migr...

Страница 6: ...Considerations and Guidelines for Network Integrations Table 1 Guidelines for N2 Network Topology Rules Maximums Allowed Category One N2 trunk per NCM General Only daisy chained devices with maximum stub length of 3 m 10 ft to any device 100 devices per NCM 60 to 200 TC 9100s 50 devices per repeater with two repeaters cascaded Number of N2 Devices Supported 1 500 m 5 000 ft twisted pair cable with...

Страница 7: ...ent Physical Layer Repeaters 1 Each LPT10 channel segment between repeaters requires its own power supply Other factors such as power consumption of individual LPT10 devices may limit a segment to fewer devices The NCM does not have an internal network terminator Table 5 NCM Ethernet Network Rules Rules Maximums Allowed 1 Category Point to point star topology with network hubs switches General Max...

Страница 8: ...erational but the POWER LED Figure 9 remains On and the data protection battery continues to power the NCM for a few minutes while volatile data is backed up in nonvolatile memory The RUN LED flashes during this process When complete all LEDs go Off Important Do not disconnect the battery while the unit is shutting down or the data being saved may be corrupted Important The data protection battery...

Страница 9: ...ked up Connect or install battery Off Steady BATT FAULT Red On Momentarily then Off Internal fault has occurred Off Steady FAULT Red Repair Information If you replace an NCM on a site with a new NCM for any reason or add a new NCM to a site you must update the system database to ensure that the new NCM is recognized and able to communicate with the site Refer to the NCM45x0 2 Network Control Modul...

Страница 10: ...n on power failure Rechargeable NiMH battery 3 6 VDC 500 mAh with a typical life of 5 to 7 years at 21 C 70 F Product Code Number MS BAT1020 0 Data Protection Battery 192 MHz Renesas SH4 7760 RISC processor Processor 128 MB Flash nonvolatile memory 128 MB Synchronous Dynamic Random Access Memory SDRAM Note Even though the unit has 128 MB of memory it is sized to emulate the capacity of an NCM300 S...

Страница 11: ...Compliance The performance specifications are nominal and conform to acceptable industry standard For application at conditions beyond the specifications consult the local Johnson Controls office Johnson Controls Inc shall not be liable for damages resulting from misapplication or misuse of its products Building Efficiency 507 E Michigan Street Milwaukee WI 53202 Metasys and Johnson Controls are r...

Отзывы: