background image

Figure 1: Front of NCM45x0-2 Showing Dimensions (mm/in), Physical Features, and Required Mounting

Space around the NCM (mm/in)

Mounting

Location Considerations

Follow these guidelines when mounting an

NCM

:

If the NCM is to replace an existing NCM350 or
NCM361, see

Legacy NCM Replacement

Considerations

.

Ensure that the mounting surface can support the
NCM and any user-supplied enclosure.

Mount the NCM in proper orientation (

Figure 2

). A

horizontal mounting orientation is preferred, but the
unit can also be mounted vertically.

Mount the NCM on an even surface in wall mount
applications whenever possible. If you must mount
the NCM on an uneven surface, be careful not to
crack the mounting clips or NCM housing when
tightening the screws. Use shims or washers to mount
the NCM evenly on the mounting surface.

Mount the NCM in areas free of corrosive vapors, and
observe the environmental limitations listed in the

Technical Specifications

section.

Allow sufficient space for cable and wire connections
(

Figure 1

).

Do not mount the NCM where the ambient
temperature may exceed 50˚C (122˚F).

Do not mount the NCM on surfaces that are prone to
vibration or in areas where electromagnetic emissions
can interfere with NCM communication.

Do not obstruct the NCM housing ventilation holes.

Do not mount the power transformer below the NCM.

For applications where the NCM is mounted inside a
panel or enclosure, follow these additional guidelines:

Do not install the NCM in an airtight enclosure.

Do not install heat-generating devices in the enclosure
with the NCM that may cause the ambient
temperature to exceed 50°C (122°F).

Mounting the NCM

Wall Mount Applications

Use the holes in the three mounting clips for wall mount
applications.

To mount the

NCM

on a wall (or other vertical surface):

1. Ensure that all three mounting clips are inserted into

the back of the NCM housing. Pull the bottom two
clips outward and snap them firmly into the extended
position (

Figure 3

).

2. Mark the location of the three wall mount holes using

the dimensions in

Figure 2

or hold the NCM up to

the wall as a template and mark the locations.

2

NCM45x0-2 Series Network Control Module Installation Instructions

Содержание MS-NCM4510-2

Страница 1: ...ouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Canada This Class B digital apparatus meets...

Страница 2: ...connections Figure 1 Do not mount the NCM where the ambient temperature may exceed 50 C 122 F Do not mount the NCM on surfaces that are prone to vibration or in areas where electromagnetic emissions can interfere with NCM communication Do not obstruct the NCM housing ventilation holes Do not mount the power transformer below the NCM For applications where the NCM is mounted inside a panel or enclo...

Страница 3: ...losure Mount Applications Mount the enclosure per the manufacturer s instructions and mount the NCM in the enclosure following the guidelines in the Location Considerations and Mounting the NCM sections Legacy NCM Replacement Considerations Follow these important guidelines if the NCM is to replace an existing NCM350 361 controller The unit size and mounting orientation of the NCM45x0 2 are notice...

Страница 4: ...n the new NCM database configuration changes are required Refer to the NCM45x0 2 Network Control Module Commissioning Guide LIT 12011176 for details Before removing the NCM350 361 upload its database to the archive Operator Workstation OWS so that it can be edited later and eventually downloaded into the new controller Refer to the NCM45x0 2 Network Control Module Commissioning Guide LIT 12011176 ...

Страница 5: ...NCM and void any warranties Important Make sure the building automation network wiring meets the specifications rules and guidelines in the Power Supply Network and Communication Connections section in this document Important For the NCM4510 2 model do not remove the plug that is inserted into the top FC Bus terminal or install any connector into this port The port is only used if the unit is migr...

Страница 6: ...Considerations and Guidelines for Network Integrations Table 1 Guidelines for N2 Network Topology Rules Maximums Allowed Category One N2 trunk per NCM General Only daisy chained devices with maximum stub length of 3 m 10 ft to any device 100 devices per NCM 60 to 200 TC 9100s 50 devices per repeater with two repeaters cascaded Number of N2 Devices Supported 1 500 m 5 000 ft twisted pair cable with...

Страница 7: ...ent Physical Layer Repeaters 1 Each LPT10 channel segment between repeaters requires its own power supply Other factors such as power consumption of individual LPT10 devices may limit a segment to fewer devices The NCM does not have an internal network terminator Table 5 NCM Ethernet Network Rules Rules Maximums Allowed 1 Category Point to point star topology with network hubs switches General Max...

Страница 8: ...erational but the POWER LED Figure 9 remains On and the data protection battery continues to power the NCM for a few minutes while volatile data is backed up in nonvolatile memory The RUN LED flashes during this process When complete all LEDs go Off Important Do not disconnect the battery while the unit is shutting down or the data being saved may be corrupted Important The data protection battery...

Страница 9: ...ked up Connect or install battery Off Steady BATT FAULT Red On Momentarily then Off Internal fault has occurred Off Steady FAULT Red Repair Information If you replace an NCM on a site with a new NCM for any reason or add a new NCM to a site you must update the system database to ensure that the new NCM is recognized and able to communicate with the site Refer to the NCM45x0 2 Network Control Modul...

Страница 10: ...n on power failure Rechargeable NiMH battery 3 6 VDC 500 mAh with a typical life of 5 to 7 years at 21 C 70 F Product Code Number MS BAT1020 0 Data Protection Battery 192 MHz Renesas SH4 7760 RISC processor Processor 128 MB Flash nonvolatile memory 128 MB Synchronous Dynamic Random Access Memory SDRAM Note Even though the unit has 128 MB of memory it is sized to emulate the capacity of an NCM300 S...

Страница 11: ...Compliance The performance specifications are nominal and conform to acceptable industry standard For application at conditions beyond the specifications consult the local Johnson Controls office Johnson Controls Inc shall not be liable for damages resulting from misapplication or misuse of its products Building Efficiency 507 E Michigan Street Milwaukee WI 53202 Metasys and Johnson Controls are r...