—MR2 Refrigeration Temperature/Defrost Control Installation Bulletin 

Table 4: Error Codes and Status 

Error Code (Codes will flash on the display) 

System Status 

F1

  Open or shorted temperature sensor 

Alarm output On. Compressor runs according to 

SF

. Cycle 

power to reset. 

A1

  Binary input open for longer than 

id

 and 

iF

 = 1 

Compressor output Off. Alarm output On. Correct problem to 
reset. 

A2

  Binary input open for longer than 

id

 and 

iF

 = 2 

Alarm output On. Correct problem to reset. 

A3

  Binary input open for longer than 

id

 and 

iF

 = 3 

Alarm output On, 

AH

 and 

AL

 disabled. Correct problem to reset. 

HI

  Temperature has reached or exceeded 

(se 

AH

Alarm output On. Correct problem to reset. 

LO

  Temperature has reached or  fallen below 

(setpoint 

– 

AL

Alarm output On. Correct problem to reset. 

EE

  Program failure 

Alarm output On. Other outputs Off. Replace control. 

O

rdering Information 

Table 5: Specifications 

Power Requirements 

3.7 VA @ 24 VAC 50/60 Hz, Class 2 (20-30 VAC) 

Ambient Conditions 

Operating 

14 to 140

o

F (-10 to 60

o

C); 0 to 95% RH (non-condensing) 

Storage   

-22 to 176

o

F (-30 to 80

o

C); 0 to 95% RH (non-condensing) 

Accuracy 

+1.8 F

o

 (+1C

o

Agency Listings 

UL Recognized: File E194024, CCN XAPX2 
Canadian UL Recognized: File E194024, CCN XAPX8 
FCC Compliant per Class A Digital Device, Part 15 
Canadian DOC Compliant per Class A, Radio Interference Regulations 

Table 6: Ordering Information 

Product Code Number 

Description 

MR2PM24-11C 

MR2 Panel Mount Control; A99BB-200C sensor included 

MR2DR24-11C 

MR2 DIN Rail Mount Control; A99BB-200C sensor included 

A99BB-200C 

Replacement Sensor, cable length: 6-1/2 ft (2 m) 

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these 
specifications, consult Johnson Controls/Penn Refrigeration Application Engineering at (414) 274-5535. Johnson Controls, Inc. shall not be 
liable for damages resulting from misapplication or misuse of its products. 
 

Controls Group 

 

507 E. Michigan Street 

 

P.O. Box 423 

Printed in U.S.A. 

Milwaukee, WI  53201 

www.johnsoncontrols.com 

 

Содержание MR2

Страница 1: ...ust for tightness To mount the DIN Rail Mount version install the DIN rail where appropriate Snap the control onto the rail in position Wiring WARNING Shock Hazard To avoid possible electrical shock or equipment damage disconnect power supply before wiring any connections Follow these wiring guidelines All wiring must conform to the National Electric Code and local regulations Make all wiring conn...

Страница 2: ...r 15 seconds of inactivity the display shows the process temperature Programming the Control To lock and unlock the unit for programming Press the Enter Up and Down buttons simultaneously and hold until is displayed Hold for about 10 seconds until the current temperature is displayed To change the setpoint 1 Hold the Enter button for approximately 3 seconds The display will change to show the setp...

Страница 3: ...um Defrost Duration Defrost ends after this time 0 disables defrost 0 to 99 minutes 45 dC Dripping Time Time compressor stopped after defrost so evaporator can drip 0 to 99 minutes 5 dU First Defrost After Power Up Time first defrost cycle is delayed after power up OF 0 to 99 minutes OF Off dP Display During Defrost Temperature displayed during defrost cycle 0 last reading 1 setpoint 0 dr Display ...

Страница 4: ...VA 24 VAC 50 60 Hz Class 2 20 30 VAC Ambient Conditions Operating 14 to 140o F 10 to 60o C 0 to 95 RH non condensing Storage 22 to 176o F 30 to 80o C 0 to 95 RH non condensing Accuracy 1 8 Fo 1Co Agency Listings UL Recognized File E194024 CCN XAPX2 Canadian UL Recognized File E194024 CCN XAPX8 FCC Compliant per Class A Digital Device Part 15 Canadian DOC Compliant per Class A Radio Interference Re...

Отзывы: