—MR2 Refrigeration Temperature/Defrost Control Installation Bulletin 

Use Table 1 with function 

So

 to compensate for long 

sensor leads. 

Table 1: Sensor Wire Size and Length 

18 AWG 

20 AWG 

22 AWG 

Offset 

300-599 ft 
91-183 m 

190-374 ft 
58-114 m 

120 -239 ft 
36-73 m 

1F° 

1C° 

600-899 ft 
183-274 m 

375-564 ft 
114-172 m 

240-349 ft 
73-107 m 

2F° 

2C° 

900+ ft 
274+ m 

565+ ft 
172+ m 

350+ ft 
107+ m 

3F° 

3C° 

Table 2: Rating Table 

Rating Category 

120 

VAC 

240 

VAC 

24 

VDC 

Horsepower 

1/4 

1/2 

--- 

Full Load Amperes 

5.8 

4.9 

--- 

Locked Rotor Amperes 

34.8 

29.4 

--- 

Inductive (non-motor) 
Amperes  

Pilot Duty VA 

275 

450 

--- 

Power source is 24 VAC. Alarms require external 
power source. 

F

CC Compliance 

This equipment has been tested and found to comply 
with the limits for a Class A digital device pursuant to 
Part 15 of the FCC Rules. These limits are designed to 
provide reasonable protection against harmful 
interference when the equipment is operated in a 
commercial environment. This equipment generates, 
uses, and can radiate radio frequency energy and, if 
not installed and used in accordance with the 
instruction manual, may cause harmful interference to 
radio communications. Operation of this equipment in 
a residential area is likely to cause harmful 
interference, in which case the user will be required to 
correct the interference at his/her own expense. 

D

isplay 

Press Up and Down buttons to scroll through process 
temperature, binary input status (

On

 or 

OF

), and 

auxiliary temperature sensor reading (

F2

 if none). After 

15 seconds of inactivity, the display shows the process 
temperature. 

P

rogramming the Control 

To lock and unlock the unit for programming: 

 

Press the Enter, Up, and Down buttons 
simultaneously 

and hold until “- - -” is 

displayed. Hold for about 10 seconds until the 
current temperature is displayed. 

To change the setpoint: 

 

1.  Hold the Enter button for approximately 

3 seconds. The display will change to 
show the setpoint. Release the Enter 
button. 

 

2.  Press the Up or Down button until you 

reach the new setpoint. 

 

3.  Press the Enter button to save the new 

setpoint. 

Note: 

If the Enter button is not pressed after selecting the new 

setpoint, the new setpoint is not saved. The control reverts 

to the original setpoint. 

To run the self-test procedure: 

IMPORTANT: 

Disconnect loads before self-test 
procedure. Cycle power to resume 
normal operation. 

 

Press the Up and Down buttons in sequence, 
and hold for 5 seconds. 

To begin a manual defrost cycle: 

 

Hold the Defrost button for 3 seconds. 

To begin a deep freeze cycle: 

 

Press the Enter and Up buttons in sequence 
and hold both for 5 seconds. The compressor 
status LED will light. 

To program values other than setpoint: 

 

1.  Hold the Enter button for about 10 

seconds. The display changes to 

HY

 

2.  Press the Up or Down button until the 

desired parameter is displayed. 

 

3.  Press the E

nter button. The parameter’s 

current value is displayed. 

 

4.  Press the Up or Down button until the 

desired value is shown. 

 

5.  Press the Enter button to save the new 

value. After 10 seconds of inactivity, the 
display will return to its normal function. 

Note: 

If the Enter button is not pressed after selecting the new 

value, the new value is not saved. The control reverts to 

the previous value. 

Содержание MR2

Страница 1: ...ust for tightness To mount the DIN Rail Mount version install the DIN rail where appropriate Snap the control onto the rail in position Wiring WARNING Shock Hazard To avoid possible electrical shock or equipment damage disconnect power supply before wiring any connections Follow these wiring guidelines All wiring must conform to the National Electric Code and local regulations Make all wiring conn...

Страница 2: ...r 15 seconds of inactivity the display shows the process temperature Programming the Control To lock and unlock the unit for programming Press the Enter Up and Down buttons simultaneously and hold until is displayed Hold for about 10 seconds until the current temperature is displayed To change the setpoint 1 Hold the Enter button for approximately 3 seconds The display will change to show the setp...

Страница 3: ...um Defrost Duration Defrost ends after this time 0 disables defrost 0 to 99 minutes 45 dC Dripping Time Time compressor stopped after defrost so evaporator can drip 0 to 99 minutes 5 dU First Defrost After Power Up Time first defrost cycle is delayed after power up OF 0 to 99 minutes OF Off dP Display During Defrost Temperature displayed during defrost cycle 0 last reading 1 setpoint 0 dr Display ...

Страница 4: ...VA 24 VAC 50 60 Hz Class 2 20 30 VAC Ambient Conditions Operating 14 to 140o F 10 to 60o C 0 to 95 RH non condensing Storage 22 to 176o F 30 to 80o C 0 to 95 RH non condensing Accuracy 1 8 Fo 1Co Agency Listings UL Recognized File E194024 CCN XAPX2 Canadian UL Recognized File E194024 CCN XAPX8 FCC Compliant per Class A Digital Device Part 15 Canadian DOC Compliant per Class A Radio Interference Re...

Отзывы: