Johnson Controls JRE Series Скачать руководство пользователя страница 31

JRE-Series

R e v. :   A u g u s t   1 9 ,   2 0 2 0

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

I n s t a l l a t i o n ,   O p e r a t i o n ,   M a i n t e n a n c e

31

Condenser Hot Water Reheat – Sequence of Operation, Cont’d.

•  1st Stage Heating:

 A simultaneous call from (G) and 

(Y1) to the (G) and (Y1) terminals of the DXM2 control 

board will bring the unit on in 1st Stage Heating. 

•  2nd Stage Heating:

 A simultaneous call from (G), 

(Y1), and (Y2) to the (G), (Y1), and (Y2) terminals of the 

DXM2 control board will bring the unit on in 2nd Stage 

Heating. When the call is satisfied at the thermostat 

the unit will continue to run in 1st Stage Heating until 

the call is removed or satisfied, shutting down the 

unit. 

NOTE: Not all units have two-stage heating 

functionality (e.g. JRE036-072 units). 

•  Reheat Mode:

 A call from the Humidistat/Dehumidistat 

to the (H) terminal of the DXM2 control board will 

bring the unit on in Reheat Mode if there is no call 

for cooling at the thermostat. When the Humidistat/

Dehumidification call is removed or satisfied the unit 

will shut down. 

NOTE: Cooling always overrides 

Reheat Mode. In the Cooling mode, the unit cools 

and dehumidifies. If the cooling thermostat is 

satisfied but there is still a call for dehumidification, 

the unit will continue to operate in Reheat Mode.

NOTE: Care must be taken when using a humidistat 

to operate condenser water reheat. When the DIP 

switch on the DXM2 controller is set for ‘humidistat’ 

it reverses the control logic so that an “open” control 

circuit initiates a reheat run cycle. If a humidistat is not 

connected, or if a manual switch on the humidistat is 

set to “off”, reheat will see the open circuit and call for 

dehumidification.

JRE Component Functions

•  Motorized Valve/Proportional Controller

•  Supply Air Sensor

•  Loop Pump

•  Hydronic Coil

•  Low Pressure Switch

The Proportional Controller operates on 24 VAC power 

supply and automatically adjusts the water valve based 

upon the Supply Air Sensor. The Supply Air Sensor 

senses supply air temperature at the blower inlet 

providing the input signal necessary for the proportional 

control to drive the motorized valve during the reheat 

mode of operation. 

The Motorized Valve is a proportional actuator/three-way 

valve combination used to divert the condenser water 

from the coax to the hydronic reheat coil during the reheat 

mode of operation. The proportional controller signals the 

motorized valve based on the supply air temperature of 

the supply air sensor.

The Loop Pump circulates condenser water through the 

hydronic reheat coil during the reheat mode of operation. 

In this application, the loop pump is only energized during 

the reheat mode of operation. The Hydronic Coil is utilized 

during the reheat mode of operation to reheat the air to 

the setpoint of the proportional controller. Condenser 

water is diverted by the motorized valve and pumped 

through the hydronic coil by the loop pump in proportion 

to the control setpoint. The amount of reheating is 

dependent on the setpoint and how far from setpoint the 

supply air temperature is. The factory setpoint is 72°F 

[22°C], generally considered “neutral” air.

Application Considerations

The reheat coil adds a small amount of resistance to the 

air stream. In some cases the high static option may be 

required for applications with higher static ductwork. 

Consult the submittal data or the Installation/Operation/

Maintenance (I.O.M.) manual for the specific heat pump to 

review blower tables.

Unlike most hot gas reheat options, the condenser hot 

water reheat option will operate over a wide range of 

EWTs. Special flow regulation (water regulating valve) is 

not required for low EWT conditions.

JRE units with the condenser hot water reheat option 

shall have an antifreeze solution to protect the coil in low 

ambient conditions. ASHRAE minimums for the region 

shall be considered during the calculation of the antifreeze 

solution.

In applications where antifreeze is not specified, a 

secondary heat exchanger can be used to isolate the 

JRE from the water loop, thus requiring less antifreeze 

to be used with the JRE Secondary brazed plate heat 

exchanger. 

Water-source heat pumps with condenser hot water 

reheat should not be used as make-up air units. 

These applications should use equipment specifically 

designed for make-up air.

Содержание JRE Series

Страница 1: ...Water Source Heat Pumps Installation Operation Maintenance Supersedes Form 14808 NOM1 0820 97B0081N06 Issue Date August 19 2020 JRE Series Water Source Heat Pump MODELS JRE 3 20 Tons...

Страница 2: ...orized Water Valve 18 Electrical Data 20 Electrical Data Reheat or Internal Secondary Pump 21 TWD Units with MPC DDC Auxiliary Diagram 22 TWD Units with LON DDC Auxiliary Diagram 23 TWD Units with Eco...

Страница 3: ...EXTENDED RANGE STANDARD RANGE YES NO NO NO YES NO NO NO YES YES NO NO NO YES NO NO NO YES F MODULATING ENTHALPY ECONOMIZER F HOT GAS BYPASS REHEAT COIL 3 WAY MOTORIZED VALVE PROPORTIONAL CONTROL CIRCU...

Страница 4: ...uipment from pallets until equipment is required for installation Unit Protection Cover rooftop units on the job site Cap the open ends of pipes In areas where painting plastering roofing or the spray...

Страница 5: ...JRE036 072 Dimensional Data Optional Rain Hood Optional Rain Hood Pipe Chase Top View of Base S e r v i c e A c c e s s 3 5 1 1 m e t e r s Service Access 3 5 1 1 m eters Size Outdoor Air Opening Wate...

Страница 6: ...96 144 Dimensional Data Top View of Base Optional Rain Hood Optional Rain Hood S e r v i c e A c c e s s 3 5 1 1 m e t e r s Service Access 3 5 1 1 m eters Size Outdoor Air Opening Water In Out IPT JR...

Страница 7: ...tion Maintenance 7 JRE168 240 Dimensional Data Pipe Chase Optional Rain Hood Optional Rain Hood S e r v i c e A c c e s s 3 5 1 1 m e t e r s S e r v i c e A c c e s s 3 5 1 1 m e t e r s Top View of...

Страница 8: ...0 Installation Operation Maintenance 8 Standard Roof Curb Model A B C D E F JRE036 48 60 72 72 25 18 35 25 72 25 35 25 14 or 24 JRE096 120 144 82 25 21 41 25 82 25 41 25 14 or 24 JRE168 240 82 25 21 7...

Страница 9: ...ntenance 9 Standard Curb with Vibration Isolation Model A B C D E F JRE036 48 60 72 72 25 18 35 25 72 25 35 25 14 or 24 JRE096 120 144 82 25 21 41 25 82 25 41 25 14 or 24 JRE168 240 82 25 21 78 88 82...

Страница 10: ...T PUMPS JRE Series Rev Au gu st 19 2020 Installation Operation Maintenance 10 Side Discharge Supply Return Roof Curb Model A B C JRE036 48 60 72 72 25 18 35 25 JRE096 120 144 82 25 21 41 25 JRE168 240...

Страница 11: ...RGY EFFI C I E NC Y Installation Operation Maintenance 11 Side Discharge Supply Roof Isolation Curb Model A B C JRE036 48 60 72 72 25 18 35 25 JRE096 120 144 82 25 21 41 25 JRE168 240 82 25 21 78 88 N...

Страница 12: ...ss to the unit side panels and all electrical connections Follow these guidelines when installing the curb 1 Set unit on curb 2 Align unit so that return air and supply air in the unit match return an...

Страница 13: ...osed geothermal loop GLHP GWHP Pipe joint compound is not necessary when Teflon threaded tape is pre applied to hose assemblies or when flared end connections are used If pipe joint compound is prefer...

Страница 14: ...de Levels 10 C 24 C 38 C Copper Cupronickel 20ppm NR NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Titanium 1000 ppm 550 ppm 375 ppm Erosion and Clogging Particulate...

Страница 15: ...accept other types of conductors Figure 2 illustrates a typical trap used with JRE Heat Pumps Multiple units within the same zone should be operated from a common temperature control Thermostat Wirin...

Страница 16: ...eratures below 60 F 15 6 C must include the optional water refrigerant circuit insulation package to prevent internal condensation Figure 3 LT1 Limit Setting Alarm Relay Comp Relay O Y2 W G C R AL1 24...

Страница 17: ...ing OFF OFF ON Humidifier ON ON OFF Outside air damper All other DIP combinations are invalid A slow closing valve may be required to help reduce water hammer Figure 4 shows typical wiring for a 24VAC...

Страница 18: ...5 Valve Wiring Figure 6 Typical Valve Wiring From Water Source IN OUT NOTE Shut off valves strainers and other required components not shown Solenoid Valve Flow Regulator To Discharge Stage 1 Stage 2...

Страница 19: ...Thermostat wire must be 18 AWG wire Representative thermostat wiring is shown in Figure 8 however actual wiring connections should be determined from the thermostat IOM and or unit wiring diagram Pra...

Страница 20: ...D E 2 13 7 83 1 1 9 2 3 0 36 6 N A N A 40 0 50 F 460 3 60 414 506 A B C 2 6 2 41 0 1 3 1 2 0 15 5 N A N A 17 0 20 F 460 3 60 414 506 D E 2 6 2 41 0 1 4 3 3 0 16 7 N A N A 18 3 20 N 575 3 60 518 633 A...

Страница 21: ...N 575 3 60 518 633 A B C 2 4 8 33 0 1 2 3 2 0 1 0 44 12 3 N A N A 13 5 15 N 575 3 60 518 633 D E 2 4 8 33 0 1 3 4 3 0 1 0 44 13 4 N A N A 14 6 15 JRE120 H 208 3 60 197 254 A B C 2 15 6 110 0 1 9 2 3...

Страница 22: ...WATER SOURCE HEAT PUMPS JRE Series Rev Au gu st 19 2020 Installation Operation Maintenance 22 Typical Wiring Diagram Units with MPC DDC Option Auxillary Diagram...

Страница 23: ...JRE Series Rev Au g u st 19 2020 THE SMART SOLUTION FOR ENERGY EFFI C I E NC Y Installation Operation Maintenance 23 Typical Wiring Diagram Units with LON DDC Option Auxillary Diagram...

Страница 24: ...WATER SOURCE HEAT PUMPS JRE Series Rev Au gu st 19 2020 Installation Operation Maintenance 24 Typical Wiring Diagram Units with Economizer Auxillary Diagram...

Страница 25: ...OLUTION FOR ENERGY EFFI C I E NC Y Installation Operation Maintenance 25 Typical Wiring Diagram Single Compressor DXM2 PMP3 460 volt units with Internal Secondary or Circulating Pump for Condenser Hot...

Страница 26: ...WATER SOURCE HEAT PUMPS JRE Series Rev Au gu st 19 2020 Installation Operation Maintenance 26 Typical Wiring Diagram Typical Two Compressor Unit DXM2...

Страница 27: ...ion modes Minimum entering air temperature while operating in the heating mode not continuous fan is the minimum entering air temperature for the standard model without the reheat option in the heatin...

Страница 28: ...t does not impact room temperature Competitors without hydronic reheat typically use an on off non modulating refrigeration based reheat circuit typically referred to as Hot gas reheat HGR HGR needs h...

Страница 29: ...2 13 24 145 6 7 6 22 5 0 3 0 7 104 8 78 4 12 40 147 1 8 5 30 0 1 4 3 2 107 2 79 1 12 00 148 1 8 9 120 15 0 0 1 0 1 94 8 76 6 14 59 144 6 6 5 22 5 0 3 0 7 98 5 76 9 13 67 145 1 7 2 30 0 1 3 3 0 100 5 7...

Страница 30: ...ith the compressor contactor s and blower relay In the heating mode the reversing valve is de energized Almost any thermostat will activate the heat pump in heating or cooling modes The DXM2 microproc...

Страница 31: ...tional control to drive the motorized valve during the reheat mode of operation The Motorized Valve is a proportional actuator three way valve combination used to divert the condenser water from the c...

Страница 32: ...26 425 0 30 0 28 0 30 0 28 450 0 31 0 29 0 32 0 29 475 0 33 0 31 500 0 35 0 32 525 0 37 550 0 38 575 0 40 Example Reheat coil loss can be determined from the above table Coil velocity FPM Airflow CFM...

Страница 33: ...from the coil Note If the reheat sensor located in the supply air stream is above 70 F it must be disabled to allow the modulating valve to shift Disable this sensor by removing the white wire from th...

Страница 34: ...tering Fluid 120 F 48 9 C 90 F 32 2 C Operating Limits Environment Units are designed for roof mount or indoor installation Power Supply A voltage variation of 10 of nameplate utilization voltage is a...

Страница 35: ...l the system and bleed off all air 10 Add antifreeze to the system in climates where ambient temperature falls below freezing using the proportion of antifreeze shown in Table 5 The volume of antifree...

Страница 36: ...able sheave on fan motor and open sheave to desired position Retighten set screw and replace belt and set belt tension as below Belt Tensioning An overly loose belt will upon motor start produce a sli...

Страница 37: ...emove the tension checker and read the forct applied from the bottom of the small O ring on the deflection force scale 6 Compare the force you have applied with the values given in the table below The...

Страница 38: ...orrosion in the system piping Unit Filters To avoid system damage ensure that the unit filter is clean Unit Fans Manually rotate fans to assure free rotation Ensure that fans are properly secured to t...

Страница 39: ...ifreeze solution Table 6 Operating Temperatures and Pressures 3 Operate each heat pump in the heating cycle imme diately after checking cooling cycle operation A time delay will prevent the compressor...

Страница 40: ...y system failures complete the following checks and data entries before the system is put into full operation External Static Sheave Setting Turns Temperatures F or C Antifreeze Pressures PSIG or kPa...

Страница 41: ...ION To avoid fouled machinery and extensive unit cleanup do not operate units without filters in place Do not use equipment as a temporary heat source during construction WARNING WARNING When replacin...

Страница 42: ...WATER SOURCE HEAT PUMPS JRE Series Rev Au gu st 19 2020 Installation Operation Maintenance 42 Notes...

Страница 43: ...JRE Series Rev Au g u st 19 2020 THE SMART SOLUTION FOR ENERGY EFFI C I E NC Y Installation Operation Maintenance 43 Notes...

Страница 44: ...improve its products As a result the design and specifications of each product at the time for order may be changed without notice and may not be as described herein Please contact Johnson Controls C...

Отзывы: