Johnson Controls JRE Series Скачать руководство пользователя страница 28

W A T E R - S O U R C E   H E A T   P U M P S

JRE-Series

R e v. :   A u g u s t   1 9 ,   2 0 2 0

I n s t a l l a t i o n ,   O p e r a t i o n ,   M a i n t e n a n c e

28

Condenser Hot Water Reheat – Benefits and Applications

Figure 9: Condenser Hot Water Reheat Schematic

Modulating Reheat Option -

 Johnson Controls’ 

condenser hot water reheat provides an innovative 

solution to dehumidification without complicated 

refrigerant controls. Condenser water reheat utilizes one 

of the biggest advantages of a Water-Source Heat Pump 

(WSHP), the transfer of energy through the water piping 

system. Condenser Hot Water Reheat simply diverts 

condenser water through a water-to-air coil that is placed 

after the evaporator coil. If condenser water is not warm 

enough, the internal “run-around” loop increases the 

water temperature with each pass through the condenser 

coil (see figure 9, below).

Benefits -

 Proportional reheat is controlled to the 

desired leaving air temperature set point (factory set 

point of 72°F, 22°C), no matter what the water loop 

temperature is. Since dehumidification operation will 

occur under less than full load cooling conditions a 

good percentage of the time, it is important to have 

a reheat function that provides 100% reheat in the 

spring and fall when the water loop is cool. Supply air 

temperature is field adjustable to +/- 3°F [+/- 1.7°C] for 

even greater flexibility with the optional potentiometer. It 

is recommended that the reheat supply air temperature 

be set to match the space cooling setpoint so that reheat 

does not impact room temperature. Competitors without 

hydronic reheat typically use an on/off (non-modulating) 

refrigeration based reheat circuit, typically referred to as 

“Hot gas reheat” (HGR). HGR needs higher condensing 

temperatures to work well, typically 85°F [29°C] entering 

water temperature (EWT). 

With HGR, cooler water temperatures produce cooler 

supply air temperatures, which could overcool the space, 

requiring additional space heating from another source 

or a special auto-change-over relay to allow the unit to 

switch back and forth between reheat and heating. Rarely 

does HGR provide 100% reheat, like condenser water 

reheat. Condenser water reheat has a simple and easy 

to troubleshoot refrigerant circuit. No switching valves 

or hard to diagnose leaky check valves are utilized. No 

unusual refrigerant pressures occur during the reheat 

mode. Condenser Hot Water Reheat technology does 

not alter the refrigerant circuit from a standard unit 

without reheat (no complicated reheat refrigerant circuit to 

diagnose if problems occur). Plus, the water loop portion of 

the condenser water reheat option is easy to understand 

and diagnose..

Applications -

 Condenser water reheat can be applied to 

a number of common applications, such as:

•  Classrooms.

•  Condominiums.

•  Apartments.

•  Computer rooms.

•  Spaces with high latent loads like auditoriums, 

theaters, convention centers, etc.

•  Most applications where humidity is a problem.

(Note: Condenser water reheat is not for use in high 

fraction outdoor air applications or in applications 

with corrosive atmospheres, such as pool rooms.)

NOTE:

Brazed plate heat exchanger is used when connecting to a loop with no antifreeze.

Содержание JRE Series

Страница 1: ...Water Source Heat Pumps Installation Operation Maintenance Supersedes Form 14808 NOM1 0820 97B0081N06 Issue Date August 19 2020 JRE Series Water Source Heat Pump MODELS JRE 3 20 Tons...

Страница 2: ...orized Water Valve 18 Electrical Data 20 Electrical Data Reheat or Internal Secondary Pump 21 TWD Units with MPC DDC Auxiliary Diagram 22 TWD Units with LON DDC Auxiliary Diagram 23 TWD Units with Eco...

Страница 3: ...EXTENDED RANGE STANDARD RANGE YES NO NO NO YES NO NO NO YES YES NO NO NO YES NO NO NO YES F MODULATING ENTHALPY ECONOMIZER F HOT GAS BYPASS REHEAT COIL 3 WAY MOTORIZED VALVE PROPORTIONAL CONTROL CIRCU...

Страница 4: ...uipment from pallets until equipment is required for installation Unit Protection Cover rooftop units on the job site Cap the open ends of pipes In areas where painting plastering roofing or the spray...

Страница 5: ...JRE036 072 Dimensional Data Optional Rain Hood Optional Rain Hood Pipe Chase Top View of Base S e r v i c e A c c e s s 3 5 1 1 m e t e r s Service Access 3 5 1 1 m eters Size Outdoor Air Opening Wate...

Страница 6: ...96 144 Dimensional Data Top View of Base Optional Rain Hood Optional Rain Hood S e r v i c e A c c e s s 3 5 1 1 m e t e r s Service Access 3 5 1 1 m eters Size Outdoor Air Opening Water In Out IPT JR...

Страница 7: ...tion Maintenance 7 JRE168 240 Dimensional Data Pipe Chase Optional Rain Hood Optional Rain Hood S e r v i c e A c c e s s 3 5 1 1 m e t e r s S e r v i c e A c c e s s 3 5 1 1 m e t e r s Top View of...

Страница 8: ...0 Installation Operation Maintenance 8 Standard Roof Curb Model A B C D E F JRE036 48 60 72 72 25 18 35 25 72 25 35 25 14 or 24 JRE096 120 144 82 25 21 41 25 82 25 41 25 14 or 24 JRE168 240 82 25 21 7...

Страница 9: ...ntenance 9 Standard Curb with Vibration Isolation Model A B C D E F JRE036 48 60 72 72 25 18 35 25 72 25 35 25 14 or 24 JRE096 120 144 82 25 21 41 25 82 25 41 25 14 or 24 JRE168 240 82 25 21 78 88 82...

Страница 10: ...T PUMPS JRE Series Rev Au gu st 19 2020 Installation Operation Maintenance 10 Side Discharge Supply Return Roof Curb Model A B C JRE036 48 60 72 72 25 18 35 25 JRE096 120 144 82 25 21 41 25 JRE168 240...

Страница 11: ...RGY EFFI C I E NC Y Installation Operation Maintenance 11 Side Discharge Supply Roof Isolation Curb Model A B C JRE036 48 60 72 72 25 18 35 25 JRE096 120 144 82 25 21 41 25 JRE168 240 82 25 21 78 88 N...

Страница 12: ...ss to the unit side panels and all electrical connections Follow these guidelines when installing the curb 1 Set unit on curb 2 Align unit so that return air and supply air in the unit match return an...

Страница 13: ...osed geothermal loop GLHP GWHP Pipe joint compound is not necessary when Teflon threaded tape is pre applied to hose assemblies or when flared end connections are used If pipe joint compound is prefer...

Страница 14: ...de Levels 10 C 24 C 38 C Copper Cupronickel 20ppm NR NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Titanium 1000 ppm 550 ppm 375 ppm Erosion and Clogging Particulate...

Страница 15: ...accept other types of conductors Figure 2 illustrates a typical trap used with JRE Heat Pumps Multiple units within the same zone should be operated from a common temperature control Thermostat Wirin...

Страница 16: ...eratures below 60 F 15 6 C must include the optional water refrigerant circuit insulation package to prevent internal condensation Figure 3 LT1 Limit Setting Alarm Relay Comp Relay O Y2 W G C R AL1 24...

Страница 17: ...ing OFF OFF ON Humidifier ON ON OFF Outside air damper All other DIP combinations are invalid A slow closing valve may be required to help reduce water hammer Figure 4 shows typical wiring for a 24VAC...

Страница 18: ...5 Valve Wiring Figure 6 Typical Valve Wiring From Water Source IN OUT NOTE Shut off valves strainers and other required components not shown Solenoid Valve Flow Regulator To Discharge Stage 1 Stage 2...

Страница 19: ...Thermostat wire must be 18 AWG wire Representative thermostat wiring is shown in Figure 8 however actual wiring connections should be determined from the thermostat IOM and or unit wiring diagram Pra...

Страница 20: ...D E 2 13 7 83 1 1 9 2 3 0 36 6 N A N A 40 0 50 F 460 3 60 414 506 A B C 2 6 2 41 0 1 3 1 2 0 15 5 N A N A 17 0 20 F 460 3 60 414 506 D E 2 6 2 41 0 1 4 3 3 0 16 7 N A N A 18 3 20 N 575 3 60 518 633 A...

Страница 21: ...N 575 3 60 518 633 A B C 2 4 8 33 0 1 2 3 2 0 1 0 44 12 3 N A N A 13 5 15 N 575 3 60 518 633 D E 2 4 8 33 0 1 3 4 3 0 1 0 44 13 4 N A N A 14 6 15 JRE120 H 208 3 60 197 254 A B C 2 15 6 110 0 1 9 2 3...

Страница 22: ...WATER SOURCE HEAT PUMPS JRE Series Rev Au gu st 19 2020 Installation Operation Maintenance 22 Typical Wiring Diagram Units with MPC DDC Option Auxillary Diagram...

Страница 23: ...JRE Series Rev Au g u st 19 2020 THE SMART SOLUTION FOR ENERGY EFFI C I E NC Y Installation Operation Maintenance 23 Typical Wiring Diagram Units with LON DDC Option Auxillary Diagram...

Страница 24: ...WATER SOURCE HEAT PUMPS JRE Series Rev Au gu st 19 2020 Installation Operation Maintenance 24 Typical Wiring Diagram Units with Economizer Auxillary Diagram...

Страница 25: ...OLUTION FOR ENERGY EFFI C I E NC Y Installation Operation Maintenance 25 Typical Wiring Diagram Single Compressor DXM2 PMP3 460 volt units with Internal Secondary or Circulating Pump for Condenser Hot...

Страница 26: ...WATER SOURCE HEAT PUMPS JRE Series Rev Au gu st 19 2020 Installation Operation Maintenance 26 Typical Wiring Diagram Typical Two Compressor Unit DXM2...

Страница 27: ...ion modes Minimum entering air temperature while operating in the heating mode not continuous fan is the minimum entering air temperature for the standard model without the reheat option in the heatin...

Страница 28: ...t does not impact room temperature Competitors without hydronic reheat typically use an on off non modulating refrigeration based reheat circuit typically referred to as Hot gas reheat HGR HGR needs h...

Страница 29: ...2 13 24 145 6 7 6 22 5 0 3 0 7 104 8 78 4 12 40 147 1 8 5 30 0 1 4 3 2 107 2 79 1 12 00 148 1 8 9 120 15 0 0 1 0 1 94 8 76 6 14 59 144 6 6 5 22 5 0 3 0 7 98 5 76 9 13 67 145 1 7 2 30 0 1 3 3 0 100 5 7...

Страница 30: ...ith the compressor contactor s and blower relay In the heating mode the reversing valve is de energized Almost any thermostat will activate the heat pump in heating or cooling modes The DXM2 microproc...

Страница 31: ...tional control to drive the motorized valve during the reheat mode of operation The Motorized Valve is a proportional actuator three way valve combination used to divert the condenser water from the c...

Страница 32: ...26 425 0 30 0 28 0 30 0 28 450 0 31 0 29 0 32 0 29 475 0 33 0 31 500 0 35 0 32 525 0 37 550 0 38 575 0 40 Example Reheat coil loss can be determined from the above table Coil velocity FPM Airflow CFM...

Страница 33: ...from the coil Note If the reheat sensor located in the supply air stream is above 70 F it must be disabled to allow the modulating valve to shift Disable this sensor by removing the white wire from th...

Страница 34: ...tering Fluid 120 F 48 9 C 90 F 32 2 C Operating Limits Environment Units are designed for roof mount or indoor installation Power Supply A voltage variation of 10 of nameplate utilization voltage is a...

Страница 35: ...l the system and bleed off all air 10 Add antifreeze to the system in climates where ambient temperature falls below freezing using the proportion of antifreeze shown in Table 5 The volume of antifree...

Страница 36: ...able sheave on fan motor and open sheave to desired position Retighten set screw and replace belt and set belt tension as below Belt Tensioning An overly loose belt will upon motor start produce a sli...

Страница 37: ...emove the tension checker and read the forct applied from the bottom of the small O ring on the deflection force scale 6 Compare the force you have applied with the values given in the table below The...

Страница 38: ...orrosion in the system piping Unit Filters To avoid system damage ensure that the unit filter is clean Unit Fans Manually rotate fans to assure free rotation Ensure that fans are properly secured to t...

Страница 39: ...ifreeze solution Table 6 Operating Temperatures and Pressures 3 Operate each heat pump in the heating cycle imme diately after checking cooling cycle operation A time delay will prevent the compressor...

Страница 40: ...y system failures complete the following checks and data entries before the system is put into full operation External Static Sheave Setting Turns Temperatures F or C Antifreeze Pressures PSIG or kPa...

Страница 41: ...ION To avoid fouled machinery and extensive unit cleanup do not operate units without filters in place Do not use equipment as a temporary heat source during construction WARNING WARNING When replacin...

Страница 42: ...WATER SOURCE HEAT PUMPS JRE Series Rev Au gu st 19 2020 Installation Operation Maintenance 42 Notes...

Страница 43: ...JRE Series Rev Au g u st 19 2020 THE SMART SOLUTION FOR ENERGY EFFI C I E NC Y Installation Operation Maintenance 43 Notes...

Страница 44: ...improve its products As a result the design and specifications of each product at the time for order may be changed without notice and may not be as described herein Please contact Johnson Controls C...

Отзывы: