OUTDOOR UNITS
TC-16006
2-51
4
[Diameter of Pipe after First Branch]
Total
Indoor Unit Capacity
(MBH)
Piping Length between First Branch and Indoor Unit
< 131.2 ft (40m)
> 131.2 ft (40m) *1)
Gas
Liquid
Gas
Liquid
< 41
5/8 (15.88)
3/8 (9.52)
3/4 (19.05)
1/2 (12.7)
42 - 65
3/4 (19.05)
3/8 (9.52)
7/8 (22.2)
1/2 (12.7)
66 - 86
7/8 (22.2)
3/8 (9.52)
1-1/8 (28.58)
1/2 (12.7)
87 - 113
1-1/8 (28.58)
1/2 (12.7)
1-1/8 (28.58)
5/8 (15.88)
114 - 125
1-1/8 (28.58)
1/2 (12.7)
1-3/8 (34.93)
5/8 (15.88)
126 - 155
1-1/8 (28.58)
5/8 (15.88)
1-3/8 (34.93)
3/4 (19.05)
156 - 185
1-3/8 (34.93)
5/8 (15.88)
1-3/8 (34.93)
3/4 (19.05)
186 - 257
1-3/8 (34.93)
3/4 (19.05)
1-5/8 (41.28)
7/8 (22.2)
> 258
1-5/8 (41.28)
3/4 (19.05)
1-5/8 (41.28)
7/8 (22.2)
,ISLSLQJOHQJWKIURPWKHPXOWLNLWDWWKH¿UVWEUDQFKWRWKHWHUPLQDOLQGRRUXQLWH[FHHGVIWPDFFRUGLQJWR
“Piping Branch Restriction” in Section 2.14.1 when installing. In some cases, it is required to prepare the reducer
¿HOGVXSSOLHG
NOTE:
If the size of
4
“Pipe after First Branch” is larger than the size of
3
“Main Pipe”, adjust the size of
4
“Pipe after First
Branch” to the same size as
3
“Main Pipe”.
5
[Diameter of Pipe between Multi-Kit and Indoor Unit]
Indoor Unit Capacity
(MBH)
Gas
Liquid
6 - 15
1/2 (12.7)
1/4 (6.35) *1)
18 - 48
5/8 (15.88)
3/8 (9.52)
72
3/4 (19.05)
3/8 (9.52)
96
7/8 (22.2)
3/8 (9.52)
*1): When liquid piping length is longer than 49.2 ft (15m), use 3/8 inch (9.52mm) diameter piping
with the reducer (accessory pipe for Multi-Kit).
NOTE:
The pipe diameter should be the same as the indoor unit piping connection size.
3
[Main Pipe Diameter]
(Base Unit or Piping Connection Kit 1 to First Branch)
Outdoor Unit
Capacity
(MBH)
Equivalent Piping Length
< 328.1 ft (100m)
> 328.1 ft (100m) *1)
Gas
Liquid
Gas
Liquid
72, 96
7/8 (22.2)
3/8 (9.52)
1-1/8 (28.58)
1/2 (12.7)
144 - 192
1-1/8 (28.58)
5/8 (15.88)
1-3/8 (34.93)
3/4 (19.05)
288
1-3/8 (34.93)
3/4 (19.05)
1-5/8 (41.28)
7/8 (22.2)
,QVRPHFDVHVLWLVUHTXLUHGWRSUHSDUHWKHUHGXFHU¿HOGVXSSOLHG
Piping Size < inch (mm) >
5HIHUWRWKH¿JXUHRQWKHSUHYLRXVSDJH
Содержание (H
Страница 2: ......
Страница 10: ...viii TC 16006 ...
Страница 22: ......
Страница 32: ...OUTDOOR UNITS 2 10 TC 16006 2XWGRRU 8QLWV 0RGHO 9 3 DQG 9 3 LQFK PP ...
Страница 45: ...OUTDOOR UNITS TC 16006 2 23 RQWURO 6 VWHP 5HIULJHUDQW FOH 0RGHO 9 3 9 3 9 3 DQG 9 3 LQFK PP ...
Страница 64: ...OUTDOOR UNITS 2 42 TC 16006 2 460V 60Hz MODEL H Y VAHP072B41CW and H Y VAHP096B41CW ...
Страница 90: ......
Страница 124: ... 2016 Johnson Controls Inc TC 16006 Code No LIT 12012299 Issued August 2016 ...