SELECTION DATA
4-4
TC-16006
(7) Actual Capacity
In the example, the total indoor unit capacity is 210MBH
(= 24MBH + 24MBH + 30MBH + 36MBH + 48MBH + 48MBH),
and outdoor unit capacity is 192MBH.
Therefore, the connected indoor unit capacity ratio is about 110%.
a) Actual Capacity of Outdoor Unit
Maximum Actual Capacity of Outdoor Unit
=
1
Outdoor Unit Capacity According to Temperature Condition and Connected IDU Capacity Ratio
×
2
Correction Factor According to Piping Length and Lift
×
3
Correction Factor According to Defrosting Operation (only heating)
×
4
Correction Factor According to Altitude
Maximum Actual Capacity of Outdoor Unit
Cooling = 172,000Btu/h × 0.89 × 0.97 = 148,488Btu/h
Heating = 226,000Btu/h × 0.955 × 0.88 × 0.97 = 184,232Btu/h
b) Actual Capacity of Each Indoor Unit
Actual Capacity of Each Indoor Unit
= Actual Capacity of Outdoor Unit × Each Indoor Unit Capacity ÷ Summation of Indoor Units Capacity
< Result >
Item
Room (1)
Room (2)
Room (3)
Selected Model
HIDM024B21S
HIDM024B21S
HIDM030B21S
Actual
Capacity
Actual Maximum
Cooling Capacity
Btu/h
16,970
16,970
21,213
(kW)
(5.0)
(5.0)
(6.2)
Actual Maximum
Heating Capacity
Btu/h
18,735
18,735
23,419
(kW)
(5.5)
(5.5)
(6.9)
Design
Load
Estimated
Cooling Load
Btu/h
18,000
18,000
22,000
(kW)
(5.3)
(5.3)
(6.4)
Estimated
Heating Load
Btu/h
18,000
18,000
22,000
(kW)
(5.3)
(5.3)
(6.4)
Item
Room (4)
Room (5)
Room (6)
Total
Selected Model
HIDM036B21S
HIDM048B21S
HIDM048B21S
(1) ~ (6)
Actual
Capacity
Actual Maximum
Cooling Capacity
Btu/h
25,455
33,940
33,940
148,488
(kW)
(7.5)
(10.0)
(10.0)
(43.6)
Actual Maximum
Heating Capacity
Btu/h
28,103
37,471
37,471
163,934
(kW)
(8.2)
(11.0)
(11.0)
(48.1)
Design
Load
Estimated
Cooling Load
Btu/h
24,000
30,000
32,000
144,000
(kW)
(7.0)
(8.8)
(9.4)
(42.2)
Estimated
Heating Load
Btu/h
27,000
34,000
36,000
155,000
(kW)
(7.9)
(10.0)
(10.6)
(45.5)
1
2
3
4
Cooling
172 MBH
0.89
-
0.97
Heating
226 MBH
0.955
0.88
0.97
Note
Section 4.2
Section 4.3
Section 4.4
Section 4.5
Содержание (H
Страница 2: ......
Страница 10: ...viii TC 16006 ...
Страница 22: ......
Страница 32: ...OUTDOOR UNITS 2 10 TC 16006 2XWGRRU 8QLWV 0RGHO 9 3 DQG 9 3 LQFK PP ...
Страница 45: ...OUTDOOR UNITS TC 16006 2 23 RQWURO 6 VWHP 5HIULJHUDQW FOH 0RGHO 9 3 9 3 9 3 DQG 9 3 LQFK PP ...
Страница 64: ...OUTDOOR UNITS 2 42 TC 16006 2 460V 60Hz MODEL H Y VAHP072B41CW and H Y VAHP096B41CW ...
Страница 90: ......
Страница 124: ... 2016 Johnson Controls Inc TC 16006 Code No LIT 12012299 Issued August 2016 ...