SELECTION DATA
TC-16006
4-17
Correction Factor for Cooling Capacity According to Piping Length
The cooling capacity should be corrected according to the following formula:
CCA=CC x F
CCA: Actual Corrected Cooling Capacity
CC: Cooling Capacity in the Performance Table
F:
Correction Factor Based on the Equivalent Piping Length
7KHFRUUHFWLRQIDFWRUVDUHVKRZQLQWKH¿JXUH
Equivalent Piping Length for
• One 90
o
Elbow is 1.6ft (0.5m).
• One 180
o
Bend is 4.9ft (1.5m).
• One Multi-Kit is 1.6ft (0.5m).
4.3 Correction Factor According to Piping Length
< Cooling Capacity >
H:
Vertical Distance Between Indoor Unit and Outdoor Unit
EL:
Equivalent Total Distance Between Indoor Unit and
Outdoor Unit (Equivalent One-Way Piping Length)
H>0: Position of Outdoor Unit Higher Than Position of Indoor Unit
L:
Actual One-Way Piping Length Between Indoor Unit and
Outdoor
Unit
/LTXLGSLSLQJVL]HIRU(/IW>P@DQG(/IW>P@DUHGLIIHUHQW
Refer to Installation Manual or Engineering Manual for details.
-H
L
Indoor Unit
Unit
Outdoor
+H
L
Outdoor Unit
Unit
Indoor
Содержание (H
Страница 2: ......
Страница 10: ...viii TC 16006 ...
Страница 22: ......
Страница 32: ...OUTDOOR UNITS 2 10 TC 16006 2XWGRRU 8QLWV 0RGHO 9 3 DQG 9 3 LQFK PP ...
Страница 45: ...OUTDOOR UNITS TC 16006 2 23 RQWURO 6 VWHP 5HIULJHUDQW FOH 0RGHO 9 3 9 3 9 3 DQG 9 3 LQFK PP ...
Страница 64: ...OUTDOOR UNITS 2 42 TC 16006 2 460V 60Hz MODEL H Y VAHP072B41CW and H Y VAHP096B41CW ...
Страница 90: ......
Страница 124: ... 2016 Johnson Controls Inc TC 16006 Code No LIT 12012299 Issued August 2016 ...