background image

OUTDOOR UNITS

TC-16006

 

2-47

Ɣ 3LSLQJ%UDQFK5HVWULFWLRQ

In the following instances, there is no limit to the number of main piping branches.

,IWKHSLSLQJOHQJWK/IURPWKH0XOWL.LWDWWKH¿UVWEUDQFKWRWKHIDUWKHVWLQGRRUXQLWLVRYHUIWP
IROORZWKHLQVWUXFWLRQVEHORZZKHQSHUIRUPLQJWKH¿HOGVXSSOLHGSLSLQJZRUN

(Example 1) : Installation with Main Piping Branch (

7

3LSLQJOHQJWKIURPWKH0XOWL.LWDWWKH¿UVWEUDQFKWRWKHWHUPLQDOLQGRRUXQLWLVZLWKLQIW

90m).

(1)  If the pipe length L2 is over 131.2 ft (40m), the size of gas and liquid pipes “b and c” or “g and h” should 

be selected according to Table 

4

 (see Section 2.14.3), “Diameter of Pipe after First Branch”.

* If the size of (a) is smaller than the size of (b, g) after selecting the size according to Table 

4

 (see 

Section 2.14.3), “Diameter of Pipe after First Branch”, adjust the size of (a) so it is the same size as (b, g). 
If the size of (a) is larger than the size indicated in Table 

3

 (see Section 2.14.3), “Main Pipe Diameter” 

of (Equivalent Piping Length > 328.1ft), adjust the size of (a) so it is the same size according to Table 

3

 (see Section 2.14.3), “Main Pipe Diameter” of (Equivalent Piping Length > 328.1ft). 

In this instance, if the size of (b, c, g, h) is larger than the size of each before the branch, adjust the 
size of (b, c, g, h) to the same size as each before the branch.

 7KHGLIIHUHQFHEHWZHHQWKHSLSLQJOHQJWKIURPWKH¿UVWEUDQFKWRWKHIDUWKHVWLQGRRUXQLWDQGWKHSLSLQJ

 

OHQJWKIURPWKH¿UVWEUDQFKWRWKHFORVHVWLQGRRUXQLWPXVWEHZLWKLQIWP

* (g+h+j)-(b+d)<131.2 ft (40m)

(Example 2): Installation without Main Piping Branch (

7

)

3LSLQJOHQJWKIURPWKH0XOWL.LWDWWKH¿UVWEUDQFKWRWKHWHUPLQDOLQGRRUXQLWLVZLWKLQIW

90m).

(1)  If the pipe length L2 is over 131.2 ft (40m), the size of gas and liquid pipes “b, d and f” should be 

selected according to Table 

4

 (see Section 2.14.3), “Diameter of Pipe after First Branch”.

* If the size of (a) is smaller than the size of (b) after selecting the size according to Table 

4

 (see 

Section 2.14.3), “Diameter of Pipe after First Branch”, adjust the size of (a) so it is the same size as (b). 
If the size of (a) is larger than the size indicated in Table 

3

 (see Section 2.14.3), “Main Pipe Diameter” 

of (Equivalent Piping Length > 328.1ft), adjust the size of (a) so it is the size according to Table 

3

 (see 

Section 2.14.3), “Main Pipe Diameter” of (Equivalent Piping Length > 328.1ft). 
In this case, if the size of (b, d, f) is larger than the size of each before the branch, adjust the size of (b, 
d, f) to the same size as each before the branch.

(

7

): Main Piping Branch: 

Both branches of piping from a Multi-Kit are 
connected to the next Multi-Kits.

L2

b

a

d

c

e

g

i

f

h

Piping Length from the Multi-Kit at the first branch
to the terminal Indoor Unit is within 131.2 ~ 295.3 ft

First Branch

Multi-Kit

Terminal
Indoor Unit

The Farthest Indoor Unit
from the First Branch 

The Closest Indoor Unit
from the First Branch 

b

a

First Branch

c

e

d

f

i

j

k

h

g

Terminal
Indoor Unit

Terminal
Indoor Unit

Piping Length from the Multi-Kit at the first branch
to the terminal Indoor Unit is within 131.2 ~ 295.3 ft 

Multi-Kit

The Closest Indoor Unit
from the First Branch

The Farthest Indoor Unit
from the First Branch

L2

L2

Indoor Unit

Main Branch

a

b

c

e

f

d

Содержание (H

Страница 1: ...PLIT SYSTEM HEAT PUMP AIR CONDITIONERS Engineering Manual Technical Catalog for Outdoor Unit Outdoor Units Low Ambient VRF Heat Pump H Y VAHP072 3 4 1CW H Y VAHP096 3 4 1CW H Y VAHP144 3 4 1CW H Y VAHP168 3 4 1CW H Y VAHP192 3 4 1CW H Y VAHP288 3 4 1CW ...

Страница 2: ......

Страница 3: ...amage or injury that might occur in an earthquake if the unit is not installed correctly injuries may occur due to a falling unit Ɣ Use appropriate Personal Protective Equipment PPE such as gloves and protective goggles and where appropriate have a gas mask nearby Also use electrical protection equipment and tools VXLWHG IRU HOHFWULFDO RSHUDWLRQ SXUSRVHV HHS D TXHQFKLQJ FORWK DQG D UH H WLQJXLVKHU...

Страница 4: ...unit in any location where animals and plants can come into direct contact with the outlet air stream Exposure could adversely affect the animals and plants Ɣ Do not install the unit with any downward slope to the side of the drain boss If you do you may have GUDLQ ZDWHU ÀRZLQJ EDFN ZKLFK PD FDXVH OHDNV Ɣ Be sure the drain hose discharges water properly If connected incorrectly it may cause leaks ...

Страница 5: ...e harmful gases can be generated from decomposition Ɣ Do not position the drain pipe for the indoor unit near any sanitary sewers where corrosive gases may be present If you do toxic gases can seep into breathable air spaces and can cause respiratory LQMXULHV I WKH GUDLQSLSH LV LQVWDOOHG LQFRUUHFWO ZDWHU OHDNDJH DQG GDPDJH WR WKH FHLOLQJ ÀRRU furniture or other possessions may result If condensate...

Страница 6: ...ssibility of different refrigerant or refrigerant oil being introduced into the cycle the sizes of the charging connections have been changed from R407C type and R22 type It is necessary to prepare the appropriate tools before performing installation work Ɣ Use refrigerant pipes and joints which are approved for use with R410A Ɣ A compressor unit comprises a pressurized system Never loosen threade...

Страница 7: ...of AWG18 0 82mm2 RQGXFWRU 6WUDQGHG RSSHU 6KLHOGHG FDEOH PXVW EH FRQVLGHUHG IRU DSSOLFDWLRQV DQG URXWLQJ LQ DUHDV RI KLJK 0 DQG RWKHU sources of potentially excessive electrical noise to reduce the potential for communication errors When shielded cabling is applied proper bonding and termination of the cable shield is required DV SHU RKQVRQ RQWUROV JXLGHOLQHV 3OHQXP DQG ULVHU UDWLQJV IRU FRPPXQLFDW...

Страница 8: ...Q 6HTXHQFH 2 28 6DIHW DQG RQWURO HYLFH 6HWWLQJ 2 40 2 11 5 Electrical Wiring Diagram 2 41 2 12 Operation Range 2 43 2 13 Combinations of Indoor Units and Outdoor Units 2 44 2 14 Piping Work 2 45 2 14 1 Piping Work Conditions 2 45 2 14 2 Multi Kit Connection 2 49 3LSLQJ 6L H DQG 0XOWL LW 6HOHFWLRQ 2 50 2 14 4 Piping Connection Method 2 52 2 14 5 Piping Work between Outdoor Units 2 55 3LSLQJ 6L H EH...

Страница 9: ...ping Connection Kit 3 12 3 3 2 Multi Kit Line Branch 3 13 3 3 3 Multi Kit Header Branch 3 14 6HOHFWLRQ DWD 4 1 6HOHFWLRQ XLGH 4 1 4 2 Outdoor Unit Capacity According to Temperature Condition and Connected IDU Capacity Ratio 4 5 4 3 Correction Factor According to Piping Length 4 17 4 4 Correction Factor According to Defrosting Operation 4 19 4 5 Correction Factor According to Altitude 4 19 ...

Страница 10: ...viii TC 16006 ...

Страница 11: ... Low Ambient Temperature Conditions High heating operation is available under the ambient temp up to 15o F 10o C Also even under the ambient temp up to 13o F 25o C maintain stability for the heating operation High heating capacity is 1 5 times higher 6RT 4o F 20o C than that of our standard VRF T R 8 T R 6 20 0 20 40 60 Heating Capacity Ratio Outdoor Suction Temperature oF WB Indoor Suction Temper...

Страница 12: ...ring defrosting indoor heat exchanger piping get cold Advantage Start Up Heating Time Fast Disadvantage Defrosting Performance Normal Less frost formation on the coil э Hot Gas Bypass High defrost performance is needed э Reverse Cycle Ŷ RPSUHVVRU GRSWHG LTXLG QMHFWLRQ DGRSWLQJ LTXLG QMHFWLRQ FOH LQWR VFUROO compressor heating performance under the low ambient temp conditions is improved without us...

Страница 13: ...QG 2XWGRRU 8QLWV 7DEOH QGRRU 8QLW 0RGHOV QGRRU 8QLW 7 SH DSDFLW 0 6 8 12 15 18 24 30 36 48 72 96 Ducted Ducted High Static B 6 Ducted Medium Static 0B 6 Ducted Slim 6B 6 Ducted EconoFresh 0B DOAS 2 B 6 Non Ducted HLOLQJ 0RXQWHG D DVVHWWH B 6 HLOLQJ 0RXQWHG D DVVHWWH 0LQL 0B 6 HLOLQJ 0RXQWHG D DVVHWWH B 6 HLOLQJ 0RXQWHG D DVVHWWH B 6 DOO 0RXQWHG 7 0B 6 Ceiling Suspended 6B 6 Floor Exposed B 6 Floor...

Страница 14: ...higher than the power setting range depending on the operating control condition such as protection control KHQ WKH DERYH VHOI GHPDQG FRQWURO LV VHW SHUIRUPDQFH LV UHVWULFWHG EHFDXVH WKH URWDWLRQ IUHTXHQF RI the compressor is forcibly decreased Self Demand Function 6HWWLQJ DPSOH 6FKHGXOH 6HWWLQJ IRU DFK URXS E RPSXWHUL HG RQWUROOHU Maximum efficiency is secured within the power setting range Opera...

Страница 15: ...H FRQQHFWHG LQGRRU XQLWV EH sure the height difference of indoor units is within 49 2ft 15m Height Difference of Indoor Units 98 4ft 30m 73 Piping Length between Branch from Indoor Unit Max 12 2ft 40m 98 4ft 30m 72 Outdoor Units Max Piping Length 32 8ft 10m Height Difference 3 3ft 0 1m Height Difference between Outdoor Units and Indoor Units O U is Higher 164 1ft 50m O U is Lower 131 2ft 40m Pipin...

Страница 16: ...XWGRRU XQLW XQGHU WKH ORZ FRROLQJ ORDG FRQGLWLRQV DQG LQ WKH ORZ RXWGRRU DLU temperature approx 50o o RU OHVV WKH LQGRRU XQLW ZLOO EH 7KHUPR 2 WR SUHYHQW WKH KHDW exchanger of the indoor unit from being frosted KHQ RSHUDWLQJ WKH RXWGRRU XQLW XQGHU WKH ORZ KHDWLQJ ORDG FRQGLWLRQV DQG WKH RXWGRRU WHPSHUDWXUH LV 59o o RU PRUH WKH RXWGRRU XQLW ZLOO EH 7KHUPR 2 WR SURWHFW WKH FRPSUHVVRU IURP IDLOXUH KH...

Страница 17: ...ncy operation after an alarm occurrence Â3 NOTE  W OHDVW WZR RXWGRRU XQLWV DUH UHTXLUHG IRU WKLV IXQFWLRQ Â2 Do not perform an emergency operation for more than eight hours Doing so may damage the unit  Q HPHUJHQF RSHUDWLRQ FDQ EH SHUIRUPHG ZKHQ D VSHFL HG DODUP FRGH RFFXUV Refer to the following x Failed Outdoor Unit Even if one unit fails the other can be operated continuously 2 Compressor Com...

Страница 18: ... Example Low Sound Operation during Night Time only by Using Timer Compressor Rotation Frequency O U Fan Rotation Frequency Input Signal Night Time 55dB Equivalent Rotation Perform the electrical wiring work on site when setting input signal Night Time 55dB Equivalent Rotation Rotation Operation Function for Outdoor Unit Â1 Regulating the operation time of each outdoor unit leads to a compressor l...

Страница 19: ...URES TC 16006 1 9 Installation Transportation and Handling Using Elevator An elevator 7 can be used to transport the base unit Elevator 7 Capacity Maximum of 11 persons RRU 2SHQLQJ LQFKHV PP HSWK LQFKHV PP ...

Страница 20: ...Duct Field Supplied Ceiling Wall Air Outlet Duct Kit Field Supplied Louver Outdoor Unit Wall Outdoor Unit The recommended air outlet duct kit has flanged opening which makes the field connection work possible The airflow direction can be changed to open space by using air outlet duct kit When Open Space is Louver When Open Space is Wall NOTE I WKH RXWOHW DLU LQWDNHV VKRUW FLUFXLW WKH RSHUDWLRQ UDQ...

Страница 21: ...to 64 refrigerant systems and to connect wires for all indoor units and outdoor units Ŷ Setting of End Terminal Resistance DFWRU VHWWLQJ RI WKH 1R SLQ RI 6 LV LQ WKH 21 SRVLWLRQ KHQ WKH QXPEHU RI RXWGRRU XQLWV LQ WKH VDPH 1 V VWHP LV WZR RU PRUH VHW WKH 1R SLQ RI 6 DW 2 DW WKH VHFRQG XQLW I RQO RQH RXWGRRU XQLW LV XVHG QR VHWWLQJ LV UHTXLUHG Corresponds to H LINK II System 7KH RXWGRRU XQLWV LQ WKH...

Страница 22: ......

Страница 23: ...LSWLRQV DPSOH H V A HP 192 B 4 1 CW 1RPHQFODWXUH HVFULSWLRQ LWDFKL UDQG RUN UDQG H VRF V A Air Source A 3 HDW 3XPS HP 072 72 MBH 096 96 MBH 144 144 MBH 168 168 MBH 192 192 MBH 288 288 MBH 192 B R410A B 9ROWV 3KDVH 9ROWV 3KDVH 4 VW HQHUDWLRQ 1 CW Low Ambient CW 2 Outdoor Units ...

Страница 24: ... 460V DVH 8QLW DSDFLW 0 72 96 0RGHO 9 3 9 3 RPELQDWLRQ RI DVH 8QLWV DSDFLW 0 144 168 192 288 0RGHO 9 3 9 3 9 3 9 3 Combination 9 3 9 3 9 3 9 3 9 3 9 3 9 3 9 3 9 3 Voltage DSDFLW 0 0RGHO 1DPH 208 230V DVH 8QLW 72 9 3 DVH 8QLW 96 9 3 72 72 144 9 3 96 72 168 9 3 96 96 192 9 3 96 96 96 288 9 3 460V DVH 8QLW 72 9 3 DVH 8QLW 96 9 3 72 72 144 9 3 96 72 168 9 3 96 96 192 9 3 96 96 96 288 9 3 Ɣ RPELQDWLRQV...

Страница 25: ...8QLW HIURVW 0HWKRG DV LQH LQ PP LTXLG LQH LQ PP Weight DSDFLW 1RPLQDO IILFLHQF 5DWLQJV RROLQJ 2SHUDWLQJ 5DQJH HDWLQJ 2SHUDWLQJ 5DQJH 2XWHU LPHQVLRQV 3DFNDJH LPHQVLRQV Connection Ratio Heat Exchanger RPSUHVVRU 7 SH Fan 2YHU FXUUHQW SURWHFWLRQ 2YHU KHDW SURWHFWLRQ 2YHU FXUUHQW SURWHFWLRQ 2YHU KHDW SURWHFWLRQ Electrical 6RXQG 3UHVVXUH HYHO 3URWHFWLRQ HYLFHV LJK SUHVVXUH VZLWFK DW SVL 03D LJK SUHVVXUH...

Страница 26: ...HUDQW FOH RW DV SDVV 5HYHUVHG 5HIULJHUDQW FOH RW DV SDVV 5HYHUVHG 5HIULJHUDQW FOH RW DV SDVV DV LQH LQ PP LTXLG LQH LQ PP 7 SH Fan DSDFLW 1RPLQDO IILFLHQF 5DWLQJV RROLQJ 2SHUDWLQJ 5DQJH HDWLQJ 2SHUDWLQJ 5DQJH 2XWHU LPHQVLRQV 3DFNDJH LPHQVLRQV Electrical 6RXQG 3UHVVXUH HYHO 3URWHFWLRQ HYLFHV Weight Connection Ratio Heat Exchanger RPSUHVVRU 2YHU FXUUHQW SURWHFWLRQ 2YHU KHDW SURWHFWLRQ 2YHU FXUUHQW S...

Страница 27: ...HWKRG 5HYHUVHG 5HIULJHUDQW FOH RW DV SDVV DV LQH LQ PP LTXLG LQH LQ PP 7 SH Fan DSDFLW 1RPLQDO IILFLHQF 5DWLQJV RROLQJ 2SHUDWLQJ 5DQJH HDWLQJ 2SHUDWLQJ 5DQJH 2XWHU LPHQVLRQV 3DFNDJH LPHQVLRQV Electrical 6RXQG 3UHVVXUH HYHO 3URWHFWLRQ HYLFHV Weight Connection Ratio Heat Exchanger RPSUHVVRU Refrigerant Main Refrigerant 3LSLQJ HDW 3XPS 2YHU FXUUHQW SURWHFWLRQ 2YHU KHDW SURWHFWLRQ 2YHU FXUUHQW SURWHFW...

Страница 28: ...W 0HWKRG DV LQH LQ PP LTXLG LQH LQ PP DSDFLW 1RPLQDO IILFLHQF 5DWLQJV RROLQJ 2SHUDWLQJ 5DQJH HDWLQJ 2SHUDWLQJ 5DQJH 2XWHU LPHQVLRQV 3DFNDJH LPHQVLRQV Weight Connection Ratio Heat Exchanger RPSUHVVRU 7 SH 2YHU FXUUHQW SURWHFWLRQ 2YHU FXUUHQW SURWHFWLRQ Fan Electrical 6RXQG 3UHVVXUH HYHO 3URWHFWLRQ HYLFHV LJK SUHVVXUH VZLWFK DW SVL 03D 5HYHUVHG 5HIULJHUDQW FOH RW DV SDVV 5HYHUVHG 5HIULJHUDQW FOH RW ...

Страница 29: ...UDQW FOH RW DV SDVV 5HYHUVHG 5HIULJHUDQW FOH RW DV SDVV 5HYHUVHG 5HIULJHUDQW FOH RW DV SDVV DV LQH LQ PP LTXLG LQH LQ PP DSDFLW 1RPLQDO IILFLHQF 5DWLQJV RROLQJ 2SHUDWLQJ 5DQJH HDWLQJ 2SHUDWLQJ 5DQJH 2XWHU LPHQVLRQV 3DFNDJH LPHQVLRQV Weight Connection Ratio Heat Exchanger RPSUHVVRU 7 SH Fan Electrical 6RXQG 3UHVVXUH HYHO 3URWHFWLRQ HYLFHV LJK SUHVVXUH VZLWFK DW SVL 03D LJK SUHVVXUH VZLWFK DW SVL 03...

Страница 30: ...RG 5HYHUVHG 5HIULJHUDQW FOH RW DV SDVV DV LQH LQ PP LTXLG LQH LQ PP DSDFLW 1RPLQDO IILFLHQF 5DWLQJV RROLQJ 2SHUDWLQJ 5DQJH HDWLQJ 2SHUDWLQJ 5DQJH 2XWHU LPHQVLRQV 3DFNDJH LPHQVLRQV Weight Connection Ratio Heat Exchanger RPSUHVVRU 7 SH Fan Refrigerant Main Refrigerant 3LSLQJ HDW 3XPS Electrical 6RXQG 3UHVVXUH HYHO 3URWHFWLRQ HYLFHV LJK SUHVVXUH VZLWFK DW SVL 03D 2YHU FXUUHQW SURWHFWLRQ 2YHU KHDW SUR...

Страница 31: ...99 9 3 68 1 8 31 1 4 1398 9 3 68 1 8 31 1 4 1398 9 3 68 1 8 31 1 4 1398 9 3 68 1 8 31 1 4 2097 460V 0RGHO Height LQ PP LGWK LQ PP HSWK LQ PP Weight OEV NJ 9 3 68 1 8 48 1 8 31 1 4 787 9 3 68 1 8 48 1 8 31 1 4 787 9 3 68 1 8 31 1 4 9 3 68 1 8 31 1 4 9 3 68 1 8 31 1 4 9 3 68 1 8 31 1 4 2361 127 LWK D FRPELQDWLRQ PRGHO WKH DERYH WDEOHV VKRZ DQ H DPSOH ZLGWK WKDW KDV D LQ PP FOHDUDQFH EHWZHHQ WKH EDVH...

Страница 32: ...OUTDOOR UNITS 2 10 TC 16006 2XWGRRU 8QLWV 0RGHO 9 3 DQG 9 3 LQFK PP ...

Страница 33: ...UTDOOR UNITS TC 16006 2 11 0RGHO 9 3 9 3 DQG 9 3 LQFK PP 2XWGRRU 8QLW 0RGHO RPELQDWLRQ RI DVH 8QLW 0RGHOV 287 225 81 7 287 225 81 7 9 3 9 3 9 3 9 3 9 3 9 3 9 3 9 3 9 3 9 3 9 3 9 3 9 3 9 3 9 3 9 3 9 3 9 3 ...

Страница 34: ...OUTDOOR UNITS 2 12 TC 16006 0RGHO 9 3 LQFK PP 2XWGRRU 8QLW 0RGHO RPELQDWLRQ RI DVH 8QLW 0RGHOV 287 225 81 7 287 225 81 7 287 225 81 7 9 3 9 3 9 3 9 3 9 3 9 3 9 3 9 3 ...

Страница 35: ...QJ 9DOYH 10 6WRS 9DOYH DV 11 6WRS 9DOYH LTXLG 12 6ROHQRLG 9DOYH IRXU SLHFHV No Part Name 13 KHFN RLQW RZ 14 KHFN RLQW LJK KHFN RLQW IRU 2LO 16 Electrical Control Box 1 17 Electrical Control Box 2 18 RZ 3UHVVXUH 6HQVRU 19 LJK 3UHVVXUH 6HQVRU 20 LJK 3UHVVXUH 6ZLWFK IRU 3URWHFWLRQ WZR SLHFHV 21 6WUDLQHU VHYHQ SLHFHV 22 KHFN 9DOYH IRXU SLHFHV 23 UDQNFDVH HDWHU YH SLHFHV 24 RXEOH 7XEH 7 SH HDW FKDQJHU ...

Страница 36: ...LQJ 9DOYH 10 6WRS 9DOYH DV 11 6WRS 9DOYH LTXLG 12 6ROHQRLG 9DOYH IRXU SLHFHV 13 KHFN RLQW RZ No Part Name 14 KHFN RLQW LJK KHFN RLQW IRU 2LO 16 Electrical Control Box 1 17 Electrical Control Box 2 18 RZ 3UHVVXUH 6HQVRU 19 LJK 3UHVVXUH 6HQVRU 20 LJK 3UHVVXUH 6ZLWFK IRU 3URWHFWLRQ WZR SLHFHV 21 6WUDLQHU VHYHQ SLHFHV 22 KHFN 9DOYH IRXU SLHFHV 23 UDQNFDVH HDWHU YH SLHFHV 24 RXEOH 7XEH 7 SH HDW FKDQJHU...

Страница 37: ...H LDPHWHU DQ 3URSHOOHU DQ Number Unit 2XWHU LDPHWHU Iin PP Nominal Airflow cfm P3 PLQ ULS 3URRI 7 SH QFORVXUH 6WDUWLQJ 0HWKRG QYHUWHU 1RPLQDO 2XWSXW 4XDQWLW QVXODWLRQ ODVV 660 660 660 3 E E E 3 3 6884 6884 6884 3 3 3 204 204 204 204 204 0RGHO HDW FKDQJHU 7 SH 3 3 1 1 0D LPXP 2SHUDWLQJ 3UHVVXUH 7RWDO DFH UHD Number of Coil Unit 1 1 2XWGRRU DQ 6884 6884 2XWGRRU DQ 0RWRU 660 660 1 1 E E 0RGHO HDW FKD...

Страница 38: ...RQ WKH IURQW VLGH LV RYHU LQFKHV PP KLJK D VSDFH RI LQFK PP h2 IRU WKH IURQW VLGH LV UHTXLUHG I WKH ZDOO RQ WKH UHDU VLGH LV RYHU LQFKHV PP KLJK D VSDFH RI LQFK PP h1 IRU WKH UHDU VLGH LV UHTXLUHG KHQ WKH XQLWV DUH VXUURXQGHG E ZDOOV RQ PRUH WKDQ WZR VLGHV WKH JXUH DERYH LQGLFDWHV UHTXLUHG VSDFLQJ RU ZDOOV RQ PRUH WKDQ WZR VLGHV VHFXUH WKH VHUYLFH VSDFH DV VKRZQ LQ WKH IROORZLQJ JXUHV I WKH VSDFH ...

Страница 39: ... inch Min 13 32 1 Side Space Front Side Front Side 1 If the field supplied snow protection hood or the air outlet duct is adopted the space of minimum 1 31 32 inch is required Min 11 13 16 h1 2 Unit inch Min 13 32 1 Front Side Top View Min 19 11 16 h2 2 No limit for side wall height Min 11 13 16 Min 13 32 1 Front Side Top View No limit for side wall height Min 11 13 16 Min 15 3 4 Min 7 7 8 Front S...

Страница 40: ... 6LQJOH QVWDOODWLRQ QVWDOODWLRQ LQ WKH 6DPH LUHFWLRQ 5HDU WR 5HDU QVWDOODWLRQ 0XOWLSOH 6HULDO QVWDOODWLRQ 1 Group Maximum of Six Outdoor Units Min 3 3 ft Top View Front Side No limit for side wall height No limit for side wall height Min 7 7 8 Min 7 7 8 Min 19 11 16 h2 2 Min 7 7 8 Min 7 7 8 Front Side Min 35 7 16 Min 31 1 2 2 Open Min 31 1 2 2 Open Min 11 13 16 h1 2 Min 7 7 8 Min 7 7 8 Min 31 1 2 ...

Страница 41: ...Weight OEV NJ HQWHU RI UDYLW LQFK PP 2XWHU LPHQVLRQV LQFK PP X Y Z A B C 9 3 9 3 699 20 7 8 12 22 13 16 48 1 8 31 1 4 68 1 8 460V 0RGHO Net Weight OEV NJ HQWHU RI UDYLW LQFK PP 2XWHU LPHQVLRQV LQFK PP X Y Z A B C 9 3 9 3 787 19 11 16 11 13 16 48 1 8 31 1 4 68 1 8 ...

Страница 42: ...V 0RGHO Unit Main Power SSOLFDEOH Voltage 3RZHU 6XSSO RPSUHVVRU Fan Motor 92 PH Max Min 0 0 67 5 237 N 9 3 460 3 60 414 24 30 87 1 2 9 9 3 24 30 87 1 2 9 9 3 24 24 30 30 110 1 2 1 2 9 9 9 3 24 24 30 30 110 1 2 1 2 9 9 9 3 24 24 30 30 110 1 2 1 2 9 9 9 3 24 24 24 30 30 30 133 1 2 1 2 1 2 9 9 9 92 5DWHG 8QLW 3RZHU 6XSSO 9ROWDJH 9 67 6WDUWLQJ XUUHQW 3 3KDVH I 5 5DWHG RDG PSDFLW UHTXHQF 237 5DWHG 0RWR...

Страница 43: ...WLRQ VRXQG LV PHDVXUHG LQ DQ DQHFKRLF FKDPEHU RZHYHU WKH DFWXDO RSHUDWLRQ VRXQG PD DSSHDU ORXGHU EHFDXVH RI DPELHQW QRLVH RU HFKRLQJ H VXUH WR FKHFN DPELHQW FRQGLWLRQV EHIRUH LQVWDOODWLRQ 7KH VRXQG RI WKH DLU LQOHW VLGH LV G KLJKHU WKDQ WKDW RI WKH IURQW VLGH ...

Страница 44: ...VRXQG LV PHDVXUHG LQ DQ DQHFKRLF FKDPEHU RZHYHU WKH DFWXDO RSHUDWLRQ VRXQG PD DSSHDU ORXGHU EHFDXVH RI DPELHQW QRLVH RU HFKRLQJ H VXUH WR FKHFN DPELHQW FRQGLWLRQV EHIRUH LQVWDOODWLRQ 7KH VRXQG RI WKH DLU LQOHW VLGH LV G KLJKHU WKDQ WKDW RI WKH IURQW VLGH ...

Страница 45: ...OUTDOOR UNITS TC 16006 2 23 RQWURO 6 VWHP 5HIULJHUDQW FOH 0RGHO 9 3 9 3 9 3 DQG 9 3 LQFK PP ...

Страница 46: ...t Exchanger SH 3 FRQWURO LV FDUULHG RXW WR DFKLHYH WKH WDUJHWHG YDOXH of I U heat exchanger SH RROLQJ 6HWWLQJ I U Heat Exchanger SH Cooling Setting 3 FRQWURO LV FDUULHG RXW WR DFKLHYH WKH WDUJHWHG YDOXH of I U heat exchanger SH I U Heat Exchanger SH Control Heating Setting I U Heat Exchanger SC Heating Setting RQWUROV VXSHUFRROLQJ RI 8 OLTXLG WKHUPLVWRU WR DFKLHYH WKH WDUJHWHG YDOXH 2XWGRRU DQ 3G ...

Страница 47: ...QLW 2XWGRRU 8QLW QYHUWHU RPSUHVVRU L HG 6SHHG RPSUHVVRU QYHUWHU RPSUHVVRU L HG 6SHHG RPSUHVVRU DVW 7LPH 1 3 2 4 7KLV 7LPH 2 4 1 3 Next Time 1 3 2 4 9 3 9 3 DQG 9 3 Inverter Compressor Fixed Speed Compressor Outdoor Unit A Outdoor Unit B Inverter Compressor Fixed Speed Compressor 127 7KHUPR 21 7KH RXWGRRU XQLW DQG VRPH LQGRRU XQLWV DUH UXQQLQJ 7KHUPR 2 7KH RXWGRRU XQLW DQG VRPH LQGRRU XQLWV VWD RQ ...

Страница 48: ...z Target Frequency Hz 1 One Inverter 1 One Fixed Speed Comp 1 One Inverter Comp 90 9 3 9 3 DQG 9 3 Compressor Operation Status 1 One Inverter Comp 2 Two Inverter Comp 2 Two Inverter 1 One Fixed Speed Comp 2 Two Inverter 2 Two Fixed Speed Comp 31 65 62 100 61 66 121 126 181 186 Frequency of Inverter Comp Hz Target Frequency Hz 9 3 31 65 62 100 61 66 92 131 152 191 212 251 272 311 Compressor Operati...

Страница 49: ...stor for Liquid Pipe Suction Gas Pressure Sensor PS Discharge Gas Pressure Sensor Pd Thermistor for Ambient Temperature TA THM7 Discharge Gas Thermistor TD1 THM8 Discharge Gas Thermistor TD2 THM9 Thermistor for Evaporation Liquid Line Temperature TE THM10 Thermistor for Evaporation Gas Line Temperature TG THM11 Thermistor for Supercool Temperature at Bypass Line TBG THM23 Thermistor for Supercool ...

Страница 50: ... Controller Low High Medium ON Lower than Activation Level OFF Higher than Activation Level Switch Increasing Set Temp Switch Decreasing Set Temp Airflow Change Over Switch Set Operation Mode at COOL I U Indoor Unit O U Outdoor Unit Power to I U ON Press Temp Switch Press FAN Switch Press RUN STOP Switch Float Switch to 1 Cooling Operation Higher than Set Temp Thermo ON Lower than Set Temp Thermo ...

Страница 51: ...of Auto Louver Stop of Auto Louver only for Decorative Panel or Indoor Unit with Auto Louver RUN indicator OFF COOL Set Fan Speed and Set Temp Indications Continuously ON Power to I U PCB OFF Electronic Expansion Valve in I U Fixed Opening LCD Indication OFF Power to I U OFF Press RUN STOP Switch MIF Operation OFF MD Operation OFF I U Indoor Unit ...

Страница 52: ...ation Mode at DRY I U Indoor Unit O U Outdoor Unit MD Operation ON DRY Indication Indication of Set Temp Switch Increasing Set Temp Switch Decreasing Set Temp Float Switch Press RUN STOP Switch to 2 PID Control for I U Electric Expansion Valve Higher than Set Temp Thermo ON Lower than Set Temp Thermo OFF I U Air Intake Temp Outdoor Temp DRY Operation 3 min Yes No RUN indicator lights MIF Operation...

Страница 53: ...Auto Louver Stop of Auto Louver only for Decorative Panel or Indoor Unit with Auto Louver RUN Indicator OFF COOL Set Fan Speed and Set Temp Indications Continuously ON Power to I U PCB OFF Electronic Expansion Valve in I U Fixed Opening LCD Indication OFF Power to I U OFF Press RUN STOP Switch MIF Operation OFF MD Operation OFF I U Indoor Unit ...

Страница 54: ...EAT Power to I U PCB ON only for Indoor Unit with Auto Louver Auto louver 0 Reset Low High Medium Switch Increasing Set Temp Switch Decreasing Set Temp Airflow Changeover Switch HEAT Indication HIGH Indication LOW Indication Indication of Set Temp MEDIUM Indication Start of Communication between I U and O U Start of Communication between I U and Wired Controller I U Indoor Unit O U Outdoor Unit PI...

Страница 55: ... O U Outdoor Unit Heat Rejection Operation 2 min after 2 min Indoor Fan Motor MIF OFF STOP Power to I U PCB OFF Electronic Expansion Valve in I U and O U Fixed Opening RUN Indicator OFF HEAT Set Airflow and Set Temp Indications Continuously ON LCD Indication OFF Power to I U OFF Operation at SLo Fan Speed I U Air Outlet Temp MIF Operation at SLo Fan Speed I U Air Outlet Temp 122 F 50 C 122 F 50 C ...

Страница 56: ...OFF Fixed Opening Degree of Electronic Expansion Valve Fixed Opening Degree of Electronic Expansion Valve PID Control for Super Cooling Electronic Expansion Valve PID Control for Super Cooling Electronic Expansion Valve High Frequency Operation High Frequency Operation Reverse Cycle Defrosting Completion Hot Gas Bypass Defrosting Completion Heating Operation 1 2 Indoor Fan MIF OFF Indoor Fan MIF O...

Страница 57: ...QW 3URWHFWLRQ RQWURO Pc3 P04 QYHUWHU LQ 7HPSHUDWXUH QFUHDVH 3URWHFWLRQ RQWURO Pc4 3 LVFKDUJH 7HPSHUDWXUH QFUHDVH 3URWHFWLRQ RQWURO 3F P06 RZ 3UHVVXUH HFUHDVH 3URWHFWLRQ RQWURO Without P09 LJK 3UHVVXUH HFUHDVH 3URWHFWLRQ RQWURO P0A HPDQG XUUHQW RQWURO 3 G RZ 3UHVVXUH QFUHDVH 3URWHFWLRQ RQWURO E RZ RPSUHVVLRQ 5DWLR 3URWHFWLRQ XQFWLRQ 7KLV IXQFWLRQ LV DFWLYDWHG WR SURWHFW WKH FRPSUHVVRU GXULQJ RFFXUU...

Страница 58: ...QW 3URWHFWLRQ RQWURO LV SHUIRUPHG LQ RUGHU WR SUHYHQW DQ LQYHUWHU WULS FDXVHG E DQ LQFUHDVH RI LQYHUWHU VHFRQGDU FXUUHQW YDOXH 1RUPDO 2SHUDWLRQ UHTXHQF RUFHG HFUHDVH VHF 3URKLELWLRQ RI UHTXHQF QFUHDVH FHSW UHTXHQF HFUHDVH 2QO LQY HWDLOV RI RQWURO 127 LWK D FRPELQDWLRQ RI EDVH XQLWV WKH FRQWURO LQ WKH JXUH LV SHUIRUPHG IRU WKH HQWLUH QXPEHU RI RXWGRRU XQLWV WR EH FRQQHFWHG 7KH LQYHUWHU FXUUHQW YDOX...

Страница 59: ...GHWHFWHG LQ HDFK RXWGRRU XQLW DQG WKLV FRQWURO XVHV WKH PD LPXP YDOXH 7G HWHFWHG 9DOXH RI LVFKDUJH DV 7KHUPLVWRU EQRUPDO 6WRSSDJH 6WRSSDJH DXVH G 3 RZ 3UHVVXUH HFUHDVH 3URWHFWLRQ RQWURO RZ 3UHVVXUH HFUHDVH 3URWHFWLRQ RQWURO LV SHUIRUPHG LQ RUGHU WR SURWHFW WKH FRPSUHVVRU IURP D WUDQVLWLRQDO GHFUHDVH RI VXFWLRQ SUHVVXUH 127 LWK D FRPELQDWLRQ RI EDVH XQLWV WKH FRQWURO LQ WKH JXUH LV SHUIRUPHG IRU WK...

Страница 60: ...PHG XQGHU WKH IROORZLQJ FRQGLWLRQV D 7KH GHPDQG VLJQDO LV LQSXW IURP WKH FHQWUDOL HG RSHUDWLRQ FRQWUROOHU E 7KH GHPDQG VLJQDO LV LQSXW DW WKH H WHUQDO LQSXW WHUPLQDOV RI WKH RXWGRRU XQLW IURP H WHUQDO HTXLSPHQW VXFK DV D EXLOGLQJ PDQDJHPHQW V VWHP RU D XWLOLW ZLWK D VPDUW PHWHU F 7KH GHPDQG IXQFWLRQ VHWWLQJV DUH VHW IURP WKH RXWGRRU XQLW 3 G 7KH ZDYH IXQFWLRQ LV VHW IURP WKH RXWGRRU XQLW 3 H 7KH G...

Страница 61: ...UHDVH 2QO 3ULRULW RI 3URWHFWLRQ RQWURO 5DQN 2UGHU QGLFDWLRQ 3URWHFWLRQ RQWURO 3HUIRUPHG 1 P01 3UHVVXUH 5DWLR 3URWHFWLRQ RQWURO 2 P02 LJK 3UHVVXUH QFUHDVH 3URWHFWLRQ RQWURO 3 P03 QYHUWHU XUUHQW 3URWHFWLRQ RQWURO 4 P04 QYHUWHU LQ 7HPSHUDWXUH QFUHDVH 3URWHFWLRQ RQWURO 3 LVFKDUJH 7HPSHUDWXUH QFUHDVH 3URWHFWLRQ RQWURO 6 P06 RZ 3UHVVXUH HFUHDVH 3URWHFWLRQ RQWURO 7 P0A HPDQG XUUHQW RQWURO 8 3 G RZ 3UHVVX...

Страница 62: ...RU 2YHU XUUHQW QYHUWHU XUUHQW 3URWHFWLRQ RQWURO 3UHVVXUH 6ZLWFK XW 2XW SVL 601 601 LVFKDUJH 7HPSHUDWXUH QFUHDVH 3URWHFWLRQ RQWURO IRU VHF IRU VHF for 10min for 10min UHDNHU 2YHU HDW RU L HG 6SHHG RPSUHVVRU 2YHU XUUHQW EQRUPDOLW 5XQQLQJ XUUHQW Control 32 32 29 29 Breaker 32 32 2YHU HDW LVFKDUJH 7HPSHUDWXUH QFUHDVH 3URWHFWLRQ RQWURO IRU VHF for 10min IRU VHF for 10min For Fan Motor 2YHU XUUHQW 3URWH...

Страница 63: ...OUTDOOR UNITS TC 16006 2 41 2 11 5 Electrical Wiring Diagram 1 208 230V 60Hz MODEL H Y VAHP072B31CW and H Y VAHP096B31CW ...

Страница 64: ...OUTDOOR UNITS 2 42 TC 16006 2 460V 60Hz MODEL H Y VAHP072B41CW and H Y VAHP096B41CW ...

Страница 65: ... the snow protection hood optional part is required 4 When operating the outdoor unit under the low cooling load conditions and in the low outdoor air temperature approx 50o F DB 10o C DB or less the indoor unit will be Thermo OFF to prevent the heat exchanger of the indoor unit from being frosted 5 When operating the outdoor unit under the low heating load conditions and the outdoor temperature i...

Страница 66: ...door air temperature is lower than 14o F 10o C select the combination of indoor units and outdoor unit as the total capacity of indoors not to exceed the capacity of outdoor unit Table 2 2 System Combination NOTES 1 The connectable indoor unit capacity ratio can be calculated as follows Connectable Indoor Unit Capacity Ratio Total Indoor Unit Capacity Total Outdoor Unit Capacity 2 For the system u...

Страница 67: ...length Ex2 d e f g h Maximum Piping Length Ex1 a c The actual piping length between the stop valve of the outdoor unit or the piping connection kit1 and the terminal indoor unit Ex2 f h Piping Length The actual length of pipe that takes no account for equivalent lengths for pressure drops of elbows Equivalent Piping Length The combination of the straight pipe length plus the equivalent length of e...

Страница 68: ... details 2 The piping length between outdoor units should be La Lb Lc 32 8 ft 10m If the piping length is incorrect there may be a failure of outdoor units caused by a refrigerant back up 3 Maintain a straight line distance of 19 11 16 inch 500mm or more for piping after the piping connection kit 4 The condition of refrigerant piping installation is different depending on the connected number of i...

Страница 69: ... h j b d 131 2 ft 40m Example 2 Installation without Main Piping Branch 7 3LSLQJ OHQJWK IURP WKH 0XOWL LW DW WKH UVW EUDQFK WR WKH WHUPLQDO LQGRRU XQLW LV ZLWKLQ IW 90m 1 If the pipe length L2 is over 131 2 ft 40m the size of gas and liquid pipes b d and f should be selected according to Table 4 see Section 2 14 3 Diameter of Pipe after First Branch If the size of a is smaller than the size of b a...

Страница 70: ... and operating limit in overload operation 2 For the system under which all the indoor units are not supposed to operate simultaneously the total indoor unit capacity is available 100 or more against the outdoor unit capacity Refer to Table 2 2 System Combination Section 2 13 for detail 3 When operating the outdoor unit in cold area with temperatures of 14o F 10o C or under the high heating load c...

Страница 71: ... Pipe Branch Connection Branch Pipe Branch Pipe Straight Length Min 1 6 ft Main Pipe Branch Connection Branch Pipe Branch Pipe Main Pipe Branch Connection Branch Pipe Branch Pipe Bending Radius Min 1 6 ft CORRECT CORRECT CORRECT INCORRECT Upper Side Upper Side Upper Side Upper Side Piping Form from Multi Kit to Indoor Unit Outdoor Unit Outdoor Unit Multi Kit Ex Recommended To prevent pipe damage u...

Страница 72: ... Header Branches Model 36 60 4 MH NP224A 36 72 8 MH NP288A Line Branch Header Branch C Line Branch after First Branch Total Indoor Unit Capacity MBH Model 86 MW NP282A2 87 125 MW NP452A2 126 185 MW NP692A2 186 MW NP902A2 NOTE If C Line Branch after First Branch is larger than B First Branch use the same model as B First Branch Multi Kit Optional Parts 1 1 4 4 5 5 5 5 4 5 5 1 3 2 D C C B A Maintain...

Страница 73: ...re the reducer HOG VXSSOLHG NOTE If the size of 4 Pipe after First Branch is larger than the size of 3 Main Pipe adjust the size of 4 Pipe after First Branch to the same size as 3 Main Pipe 5 Diameter of Pipe between Multi Kit and Indoor Unit Indoor Unit Capacity MBH Gas Liquid 6 15 1 2 12 7 1 4 6 35 1 18 48 5 8 15 88 3 8 9 52 72 3 4 19 05 3 8 9 52 96 7 8 22 2 3 8 9 52 1 When liquid piping length ...

Страница 74: ...s 2 1 and 2 2 4 Seal the gap between the bottom base or front piping cover and pipes with the insulation 1 Piping can be installed in three directions front rear or bottom side from the bottom base For vibration protection properly secure piping connections and check that no excessive force is applied to the stop valve Front Side Bottom Side Rear Side Bottom Base For Piping from Bottom Base Seal t...

Страница 75: ...SLQJ LV H SRVHG WR WKH UH KLJK WHPSHUDWXUH RLO ZLOO VSXUW DQG FDXVH D UH RU LQMXU Stop Valve for Liquid Pipe End of Closing Pipe Service Port Stop Valve for Gas Pipe Closing Pipe Cut Detail of Closing Pipe Soundproof Cover Compressor Oil Return Pipe Torch Metal Plate Closing Pipe Stop Valve Body Field Work Side Model Type Tightening Torque 72 and 96 24 3 31 0 ft lbs 33 42 N m Liquid Valve 7LJKWHQ ...

Страница 76: ... 2 Refrigerant Gas Piping Connection φ3 8 9 52 Refrigerant Liquid Piping Connection Konckout Square Hole for Piping Cover 3 7 16 88 5 11 16 145 8 1 16 205 3 3 8 85 3 1 4 82 9 13 16 250 5 1 8 130 4 1 4 108 5 3 16 132 4 5 16 110 7 1 2 190 2 9 16 65 11 3 8 289 10 13 16 275 Refrigerant Piping Outlet For Refrigerant Gas and Liquid Piping Knockout Square Hole φ1 3 4 43 7 Power Supply Wiring Outlet Knock...

Страница 77: ...maximum clearance of 11 13 16 inch 300mm between the piping connection kit and the bottom of the outdoor unit Also install an oil trap minimum 7 7 8 inch 200mm between the piping connection kit and the outdoor unit 2 14 5 Piping Work between Outdoor Units Outdoor Unit B Outdoor Unit A Outdoor Unit C Piping Connection Kit 1 Piping Connection Kit 2 L L C A B L Indoor Unit Side Outdoor Unit B Outdoor...

Страница 78: ...shown LQ WKH JXUH 5 For servicing if the pipe is installed in front of the outdoor unit make sure minimum clearance of 19 11 16 inch 500mm between the outdoor unit and piping connection kits When the compressor is replaced minimum clearance of 19 11 16 inch 500mm is required 7KH UHIULJHUDQW V VWHP PD EH GDPDJHG LI WKH VORSH RI WKH SLSLQJ FRQQHFWLRQ NLW H FHHGV 15R NOTICE Less than 6 6 ft Less than...

Страница 79: ...uid Accessory Pipe L Shape Accessory Pipe L Shape Accessory Pipe L Shape Accessory Pipe L Shape Liquid Piping Field Supplied Liquid Piping Field Supplied Liquid Piping Field Supplied Gas Piping Field Supplied Gas Piping Field Supplied Gas Piping Field Supplied Foundation for Outdoor Unit Accessory Pipe Z Shape Accessory Pipe Z Shape Piping Connection Kit 1 Liquid Piping Connection Kit 1 Gas Base F...

Страница 80: ...8 15 88 5 8 15 88 5 8 15 88 b Gas 7 8 22 2 7 8 22 2 7 8 22 2 Liquid 3 8 9 52 3 8 9 52 3 8 9 52 c Gas 7 8 22 2 7 8 22 2 7 8 22 2 Liquid 3 8 9 52 3 8 9 52 3 8 9 52 Install the outdoor unit and piping connections in accordance to whatever is applicable to your situation Refer to the table for the outdoor unit model the piping connection kit model and the piping diameter Base Unit Two Units Combinatio...

Страница 81: ...9 52 Three Units Combination Indoor Unit on Left Side Indoor Unit on Right Side Install the outdoor unit and piping connections in accordance to whatever is applicable to your situation Refer to the table for the outdoor unit model the piping connection kit model and the piping diameter Outdoor Unit A To Indoor Units Outdoor Unit B Outdoor Unit C Piping Connection Kit 1 Piping Connection Kit 2 a c...

Страница 82: ...LV D FDSDFLW VKRUWDJH RI WKH SRZHU FLUFXLW LW ZLOO FDXVH DQ HOHFWULF VKRFN RU D UH Ɣ KHFN WKDW WKH JURXQG ZLUH LV VHFXUHO FRQQHFWHG I WKH XQLW LV QRW FRUUHFWO JURXQGHG LW PD OHDG WR DQ HOHFWULFDO VKRFN R QRW FRQQHFW WKH JURXQG ZLULQJ WR JDV SLSLQJ ZDWHU SLSLQJ OLJKWLQJ FRQGXFWRU RU WHOHSKRQH JURXQG FDEOHV 1 Power Source Wiring Supply the power sources to each outdoor unit and indoor unit group res...

Страница 83: ... cabling shall be a minimum of AWG18 0 82mm2 2 Conductor Stranded Copper Shielded cable must be considered for applications and routing in areas of high EMI and other sources of potentially excessive electrical noise to reduce the potential for communication errors When shielded cabling is applied proper bonding and termination of the cable shield is required as per Johnson Controls guidelines Ple...

Страница 84: ...sory 4 Tighten screws for the terminal block according to the following table Required Tightening Torque Size Tightening Torque M4 0 7 to 1 0 IWÂOEV 1 0 to 1 3 1ÂP M5 1 5 to 1 8 IWÂOEV 2 0 to 2 4 1ÂP M6 3 0 to 3 7 IWÂOEV 4 0 to 5 0 1ÂP M8 6 6 to 8 1 IWÂOEV 9 0 to 11 0 1ÂP M10 13 3 to 17 0 IWÂOEV 18 0 to 23 0 1ÂP Secure with a cable clamp PVC Tube VW 1 600V Accessory Cable Clamp For Securing Power ...

Страница 85: ... unit 2 Connect a power supply wiring to each indoor unit group connected to the same outdoor unit Total operating current be less than 12A Connect a Ground Fault Circuit Interrupter GFCI fuse and main switch S to each indoor unit group 3 Connect the communication cable between indoor units and outdoor units as shown in Figure 2 3 4 Connect the communication cables in the same refrigerant system u...

Страница 86: ...tween outdoor units in the same refrigerant system to the terminals 3 and 4 on TB2 x Communication Cabling NOTES 1 For the combination units DSW settings of Main and Sub are required 2 An alarm occurs if the communication cables between main outdoor unit and sub outdoor units are connected to the terminals 1 and 2 for H LINK system 3 In an alarm is triggered on the LCD of Main outdoor unit follow ...

Страница 87: ...Box or Pull Box GFCI GFCI GFCI GFCI GFCI S S S Outdoor Unit A Main Ground Ground Outdoor Unit B Sub Controller Cable Controller Cable Wired Controller Wired Controller No 0 System Indoor Units No 1 System Indoor Units 1 208 230V 60Hz TB Terminal Block PCB Printed Circuit Board Field Wiring Communication Line DC5V Non Pole Communication H LINK System Field Supplied Optional Accessory 3 208 230V 60H...

Страница 88: ...s lbs 3 W3 Calculation Method for Additional Refrigerant Charge W3 lbs If the capacity of combined Indoor Unit is larger than 072 MBH the additional refrigerant charge must be 2 2 lbs unit 2 2 lbs unit lbs 4 W4 The Ratio of Indoor Unit Connection Capacity Indoor Unit Total Capacity Outdoor Unit Capacity Additional Charge W4 lbs Determine the ratio of indoor unit connection capacity Condition Refri...

Страница 89: ...rior to shipment If there is a combination of base units calculate the total refrigerant charge prior to shipment of those combined outdoor units 2 Record of Additional Charge Total refrigerant charge of this system is calculated in the following formula Total Ref Charge WT lbs W0 lbs lbs NOTE When refrigerant is recovered or charged due to repairs operating or adjusting the unit record the refrig...

Страница 90: ......

Страница 91: ...PN TP10L for Right Side Air Inlet PN TP10R 3 2 3 Snow Protection Hood for Top Side Air Outlet ASG TP20FBS1 for Rear Side Air Inlet ASG TP20BBS1 for Left Side Air Inlet ASG TP20LS2 for Right Side Air Inlet ASG TP20RS2 Toppling Prevention Tool ASG SW20A 3 3 Piping Kit 3 3 1 Piping Connection Kit MC NP20A1 MC NP30A1 3 3 2 Multi Kit Line Branch MW NP282A2 MW NP452A2 MW NP692A2 MW NP902A2 3 3 3 Header ...

Страница 92: ...e may freeze resulting in a cracked pipe 3ODFH WKH RXWGRRU XQLW RQ D ÀDW IRXQGDWLRQ RU EORFN DQG SODFH LW DW OHDVW LQFKHV PP KLJKHU WKDQ WKH ground For smooth drainage install the outdoor unit with a slight incline on the drainage side rear side Installation Position Example Capacity 72 000 Btu h Drain Cap Position Two Places Drain Pipe Field Supplied Drain Adapter Position Two Places Drain Adapte...

Страница 93: ...ries Installation Position Installation Notice 1 Secure enough service space with consideration for attaching detaching the protection net 2 Do not step on the protection net or the outdoor unit in order to prevent falls and injuries 3 Fallen leaves or other objects may get caught in the protection net Be sure to clean the net periodically 4 Be sure to securely tighten the protection net with the ...

Страница 94: ...BS1 3 Hood for Left Side Air Inlet ASG TP20LS2 4 Hood for Right Side Air Inlet ASG TP20RS2 5 Toppling Prevention Tool ASG SW20A Front Side Right Side Rear Side View from P Detailed Views of A and B Detail A Detail B Detail P Punch Mark four places Drill a pilot hole into the punch PDUN DQG PRXQW WKH LQJ SODWH Airflow Direction Front Side Airflow Direction Rear Side ...

Страница 95: ... air discharge direction of the snow protection hood If there DUH REVWDFOHV WKH PD FDXVH D VKRUW FLUFXLW RU DQ LQVXI FLHQW DLUÀRZ UDWH 4 Do not install other outdoor units in the direction of air outlet If the air blown out of the snow protection hood is sucked into the other outdoor unit it may cause a malfunction 5 The wind loads which the outdoor unit receives change by attaching the snow prote...

Страница 96: ... care when installing or assembling Ɣ 6HOHFWLRQ RI QVWDOODWLRQ 3ODFH 1 Install the outdoor unit at a suitable height with consideration for snow accumulation Increase the base height or additionally provide a frame under the unit higher than snow accumulation and install the outdoor unit securely with anchor bolts 2 Secure enough service space with consideration for snow accumulation height and sn...

Страница 97: ...ate 1 3 Faceplate 1 1 4 Faceplate 2 1 5 Faceplate 3 1 6 Horizontal Plate 1 7 Fixing Plate for Left Side Front Side 1 8 Fixing Plate for Left Side Rear Side 1 9 Fixing Plate for Right Side Front Side 1 10 Fixing Plate for Right Side Rear Side 1 No Item Qty 1 Right Side Plate 1 2 Left Side Plate 1 3 Faceplate Top Side 1 4 Faceplate Bottom Side 1 Details of A Details of A Details of B ...

Страница 98: ... mm Hood for Left Side Air Inlet Hood for Right Side Air Inlet Installation Dimension No Item Qty 1 Right Side Plate 1 2 Left Side Plate 1 3 Faceplate Top Side 1 4 Faceplate Bottom Side 1 Details of A Details of B Details of A Details of B ...

Страница 99: ...lized to prevent the outdoor unit from overturning It is not possible to use the toppling prevention tool along with the Wind Prevention Tool No Accessory Qty 1 Eyebolt SUS M6 with Square Washer Spring Washer and Nut 4 sets for each 2 Securing Plate SUS 4 3 Wire SUS f1 16 inch 2mm x 66 ft 20m 1 4 Fastening Fitting 8 Hole for M8 Hole for M6 ...

Страница 100: ...TIONAL PARTS 3 10 TC 16006 Item Model Piping Connection Kit MC NP20A1 MC NP30A1 Multi Kit Line Branch MW NP282A2 MW NP452A2 MW NP692A2 MW NP902A2 Line Branch MH NP224A MH NP288A 3 3 Piping Connection Kit ...

Страница 101: ...anches Model 36 60 4 MH NP224A 36 72 8 MH NP288A Line Branch Header Branch C Line Branch after First Branch Total Indoor Unit Capacity MBH Model 86 MW NP282A2 87 125 MW NP452A2 126 185 MW NP692A2 186 MW NP902A2 NOTE If C Line Branch after First Branch is larger than B First Branch use the same model as B First Branch Multi Kit Piping Connection Kit D C C B A Gas Pipe Liquid Pipe A A Outdoor Unit B...

Страница 102: ... OD 1 ID 3 4 ID 7 8 OD 1 1 4 ID 1 3 8 OD 1 1 2 ID 1 5 8 Piping Connection Kit 2 ID 1 1 2 ID 1 1 4 ID 1 1 4 ID 1 1 8 ID 1 ID 1 1 4 To Outdoor Unit To Piping Connection Kit 1 ID 1 2 ID 3 8 ID 3 4 ID 5 8 ID 3 4 ID 7 8 ID 3 4 ID 5 8 To Outdoor Unit To Piping Connection Kit 1 OD 1 1 4 ID 1 1 8 ID 1 ID 1 2 ID 5 8 OD 3 4 ID 3 8 ID 1 1 8 ID 1 OD 1 1 4 ID 1 3 8 OD 1 1 4 ID 1 1 4 OD 1 1 4 ID 1 1 8 ID 7 8 OD...

Страница 103: ...Indoor Unit To Main Piping OD 1 1 8 ID 1 ID 5 8 ID 7 8 ID 3 4 ID 1 2 ID 3 8 OD 1 4 ID 5 8 OD 1 2 MW NP692A2 ID 1 2 ID 5 8 ID 1 1 8 ID 1 1 8 ID 1 ID 3 4 ID 7 8 ID 7 8 To Outdoor Unit To Indoor Unit To Main Piping ID 3 8 ID 3 4 ID 5 8 ID 1 2 ID 3 8 ID 1 2 ID 5 8 ID 5 8 ID 7 8 ID 1 4 To Outdoor Unit To Indoor Unit To Main Piping OD 1 1 8 ID 1 ID 5 8 ID 7 8 ID 3 4 ID 1 2 ID 3 8 OD 1 4 ID 1 1 8 OD 7 8 ...

Страница 104: ...der Closing Pipe φ3 8 φ3 8 For Closing For Closing For Gas Line For Liquid Line For Gas Line For Liquid Line For Gas Line For Liquid Line For Liquid Line Qty 2 Qty 2 Qty 6 Qty 6 Qty 4 Qty 2 Qty 8 Unit inch ID Inner Diameter OD Outer Diameter 3 3 3 Multi Kit Header Branch MH NP224A and MH NP288A Piping Connection Size 7KH HQGV RI WKH PXOWL NLWV DUH QLVKHG DV VKRZQ LQ WKH IROORZLQJ JXUHV XW WKH HQG ...

Страница 105: ...tu h 6 700 9 000 13 500 17 000 20 000 27 000 34 000 40 000 54 000 kW 2 0 2 6 4 0 5 0 5 9 7 9 10 0 11 7 15 8 H I C4 012 B 2 1 S Nomenclature Description H Hitachi Brand Y York Brand T Tag in the Bag H Indoor Unit I Indoor Unit Type C4 4 Way Cassette Type C4M 4 Way Cassette Mini Type C2 2 Way Cassette Type C1 1 Way Cassette Type DH Ducted High Static Type DM Ducted Medium Static Type DS Ducted Slim ...

Страница 106: ...H 072 B R410A B 3 208 230Volts 3Phase 60Hz 4 460Volts 3Phase 60Hz 4 1 1st Generation 1 CW Low Ambient CW Model H Y VAHP072B31CW H Y VAHP096B31CW H Y VAHP144B31CW H Y VAHP072B41CW H Y VAHP096B41CW H Y VAHP144B41CW Nominal Cooling Capacity Btu h 72 000 96 000 144 000 kW 21 1 28 1 42 2 Nominal Heating Capacity Btu h 81 000 108 000 162 000 kW 23 7 31 7 47 5 Model H Y VAHP168B31CW H Y VAHP192B31CW H Y ...

Страница 107: ...S HIDM024B21S HIDM030B21S Nominal Cooling Capacity Btu h 24 000 24 000 30 000 kW 7 0 7 0 8 8 Nominal Heating Capacity Btu h 27 000 27 000 34 000 kW 7 9 7 9 10 0 Item Room 4 Room 5 Room 6 Total Selected Model HIDM036B21S HIDM048B21S HIDM048B21S 1 6 Nominal Cooling Capacity Btu h 36 000 48 000 48 000 210 000 kW 10 6 14 1 14 1 61 6 Nominal Heating Capacity Btu h 40 000 54 000 54 000 236 000 kW 11 7 1...

Страница 108: ...Indoor Unit Capacity Summation of Indoor Units Capacity Result Item Room 1 Room 2 Room 3 Selected Model HIDM024B21S HIDM024B21S HIDM030B21S Actual Capacity Actual Maximum Cooling Capacity Btu h 16 970 16 970 21 213 kW 5 0 5 0 6 2 Actual Maximum Heating Capacity Btu h 18 735 18 735 23 419 kW 5 5 5 5 6 9 Design Load Estimated Cooling Load Btu h 18 000 18 000 22 000 kW 5 3 5 3 6 4 Estimated Heating L...

Страница 109: ...3 82 3 71 83 3 62 84 3 54 86 3 16 14 52 2 94 52 2 71 53 2 57 54 2 43 55 2 29 56 2 24 56 2 19 58 1 95 18 77 4 72 79 4 37 80 4 15 81 3 93 82 3 71 83 3 59 84 3 49 86 3 15 18 52 2 92 52 2 70 53 2 57 54 2 43 55 2 29 56 2 22 56 2 15 58 1 95 23 77 4 68 78 4 35 80 4 14 81 3 93 82 3 72 83 3 56 85 3 42 86 3 14 23 51 2 89 52 2 69 53 2 56 54 2 43 55 2 30 56 2 20 56 2 11 58 1 94 32 77 4 60 78 4 32 80 4 12 81 3...

Страница 110: ... 107 7 87 111 7 84 115 7 82 120 7 80 74 64 5 33 66 5 31 69 5 30 72 5 28 75 5 27 78 5 26 81 5 24 84 5 23 78 91 8 11 94 8 08 98 8 07 102 8 06 106 8 06 110 8 05 114 8 04 118 8 03 78 63 5 44 65 5 42 68 5 41 71 5 41 74 5 40 77 5 39 80 5 39 83 5 38 82 89 8 40 92 8 38 96 8 36 100 8 35 104 8 34 108 8 34 112 8 34 116 8 34 82 62 5 63 64 5 62 67 5 61 70 5 60 72 5 59 75 5 59 78 5 59 81 5 59 86 87 8 81 90 8 79...

Страница 111: ...2 108 13 14 110 12 46 110 11 84 112 11 36 14 154 9 52 158 8 76 160 8 32 162 7 86 164 7 42 166 7 24 168 7 08 172 6 32 14 104 5 88 104 5 42 106 5 14 108 4 86 110 4 58 112 4 48 112 4 38 116 3 90 18 154 9 44 157 8 74 160 8 30 162 7 86 164 7 42 166 7 18 169 6 98 172 6 30 18 103 5 84 104 5 40 106 5 14 108 4 86 110 4 58 112 4 44 112 4 30 116 3 90 23 154 9 36 156 8 70 160 8 28 162 7 86 164 7 44 166 7 12 1...

Страница 112: ...12 27 182 12 03 188 11 77 193 11 54 200 11 35 74 114 8 77 117 8 57 120 8 41 124 8 23 127 8 06 131 7 90 135 7 73 139 7 61 78 162 13 38 166 13 09 171 12 84 176 12 60 181 12 36 186 12 13 191 11 91 197 11 73 78 113 8 97 116 8 77 119 8 61 123 8 45 126 8 28 130 8 13 134 7 99 138 7 85 82 160 13 98 164 13 69 169 13 42 173 13 17 178 12 91 183 12 68 188 12 48 194 12 29 82 111 9 37 114 9 17 118 9 01 122 8 83...

Страница 113: ...8 231 15 64 240 15 60 74 128 10 66 132 10 62 138 10 60 144 10 56 150 10 54 156 10 52 162 10 48 168 10 46 78 181 16 22 187 16 16 195 16 14 203 16 12 211 16 12 220 16 10 228 16 08 236 16 06 78 127 10 88 131 10 84 137 10 82 143 10 82 147 10 80 153 10 78 159 10 78 165 10 76 82 178 16 80 184 16 76 192 16 72 200 16 70 208 16 68 216 16 68 223 16 68 231 16 68 82 125 11 26 129 11 24 134 11 22 140 11 20 144...

Страница 114: ... 15 99 199 15 93 208 15 90 217 15 84 224 15 81 233 15 78 242 15 72 251 15 69 78 272 24 33 281 24 24 293 24 21 305 24 18 317 24 18 329 24 15 341 24 12 354 24 09 78 190 16 32 196 16 26 205 16 23 214 16 23 221 16 20 230 16 17 239 16 17 248 16 14 82 267 25 20 276 25 14 288 25 08 299 25 05 311 25 02 323 25 02 335 25 02 347 25 02 82 187 16 89 193 16 86 202 16 83 211 16 80 217 16 77 226 16 77 234 16 77 2...

Страница 115: ...3 99 65 4 10 65 4 20 64 4 44 64 4 62 64 4 86 51 88 4 92 88 5 27 88 5 55 88 5 79 89 6 04 88 6 29 87 6 48 87 6 87 51 66 3 47 66 3 64 65 3 78 65 3 86 65 3 96 64 4 16 64 4 32 64 4 53 55 88 4 67 88 4 98 88 5 23 88 5 44 89 5 66 88 5 87 87 6 03 87 6 38 55 66 3 30 66 3 44 65 3 56 65 3 63 65 3 71 64 3 88 64 4 02 64 4 21 59 88 4 38 88 4 68 88 4 91 88 5 12 89 5 33 88 5 54 87 5 70 87 5 77 59 66 3 09 66 3 23 6...

Страница 116: ...8 68 78 9 04 77 9 31 76 9 47 76 9 63 74 10 52 73 11 20 72 11 55 15 110 10 76 109 11 28 108 11 69 108 12 01 108 12 34 105 13 49 104 14 34 102 14 80 15 79 8 08 78 8 39 77 8 63 76 8 80 76 8 97 74 9 84 73 10 49 72 10 75 19 110 10 25 109 10 74 108 11 12 108 11 42 108 11 72 105 12 76 104 13 54 102 13 98 19 79 7 66 78 7 96 77 8 19 76 8 36 76 8 52 74 9 30 73 9 89 72 10 16 23 111 9 74 110 10 19 109 10 55 1...

Страница 117: ...68 130 7 98 130 8 20 130 8 40 128 8 88 128 9 24 128 9 72 51 176 9 84 176 10 54 176 11 10 176 11 58 178 12 08 176 12 58 174 12 96 174 13 74 51 132 6 94 132 7 28 130 7 56 130 7 72 130 7 92 128 8 32 128 8 64 128 9 06 55 176 9 34 176 9 96 176 10 46 176 10 88 178 11 32 176 11 74 174 12 06 174 12 76 55 132 6 60 132 6 88 130 7 12 130 7 26 130 7 42 128 7 76 128 8 04 128 8 42 59 176 8 76 176 9 36 176 9 82 ...

Страница 118: ... 189 21 69 185 23 27 183 24 43 181 25 42 15 137 14 03 135 14 64 134 15 10 133 15 44 133 15 77 130 16 97 129 17 87 128 18 49 19 191 17 72 190 18 66 189 19 38 189 19 95 189 20 52 185 21 98 183 23 06 181 24 01 19 137 13 25 135 13 83 134 14 27 133 14 60 133 14 92 130 16 02 129 16 85 128 17 46 23 192 16 76 191 17 62 190 18 30 189 18 83 189 19 36 186 20 68 184 21 68 181 22 61 23 137 12 47 135 13 02 134 ...

Страница 119: ...0 26 98 208 28 68 204 29 60 15 158 16 16 156 16 78 154 17 26 152 17 60 152 17 94 148 19 68 146 20 98 144 21 50 19 221 20 50 219 21 48 217 22 24 216 22 84 216 23 44 211 25 52 208 27 08 204 27 96 19 158 15 32 156 15 92 154 16 38 152 16 72 152 17 04 148 18 60 146 19 78 144 20 32 23 222 19 48 220 20 38 218 21 10 216 21 66 216 22 22 212 24 06 208 25 46 204 26 34 23 158 14 50 156 15 06 154 15 52 152 15 ...

Страница 120: ...44 40 15 237 24 24 234 25 17 231 25 89 228 26 40 228 26 91 222 29 52 219 31 47 216 32 25 19 331 30 75 328 32 22 325 33 36 324 34 26 324 35 16 316 38 28 312 40 62 306 41 94 19 237 22 98 234 23 88 231 24 57 228 25 08 228 25 56 222 27 90 219 29 67 216 30 48 23 332 29 22 329 30 57 326 31 65 324 32 49 324 33 33 317 36 09 312 38 19 306 39 51 23 237 21 75 234 22 59 231 23 28 228 23 73 228 24 21 222 26 31...

Страница 121: ...0o Elbow is 1 6ft 0 5m One 180o Bend is 4 9ft 1 5m One Multi Kit is 1 6ft 0 5m 4 3 Correction Factor According to Piping Length Cooling Capacity H Vertical Distance Between Indoor Unit and Outdoor Unit EL Equivalent Total Distance Between Indoor Unit and Outdoor Unit Equivalent One Way Piping Length H 0 Position of Outdoor Unit Higher Than Position of Indoor Unit L Actual One Way Piping Length Bet...

Страница 122: ...acity According to Piping Length The heating capacity should be corrected according to the following formula HCA HC x F HCA Actual Corrected Heating Capacity HC Heating Capacity in the Performance Table F Correction Factor Based on the Equivalent Piping Length 7KH FRUUHFWLRQ IDFWRUV DUH VKRZQ LQ WKH JXUH Equivalent Piping Length for One 90o Elbow is 1 6ft 0 5m One 180o Bend is 4 9ft 1 5m One Multi...

Страница 123: ...s like snowfall or operation in a transitional period Outdoor Air Temp o F DB o C DB Humidity 85 RH 19 7 2 23 5 0 27 2 8 31 0 6 35 1 7 39 3 9 41 5 0 43 6 1 45 7 2 47 8 3 Correction Factor 0 95 0 93 0 89 0 87 0 88 0 90 0 92 0 96 1 0 1 0 Altitude ft 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 m 0 305 610 914 1219 1524 1829 2133 2438 2743 3048 Correction Factor 1 00 0 97 0 93 0 90 0 87 0 83 ...

Страница 124: ... 2016 Johnson Controls Inc TC 16006 Code No LIT 12012299 Issued August 2016 ...

Отзывы: