OUTDOOR UNITS
TC-16006
2-47
Ɣ 3LSLQJ%UDQFK5HVWULFWLRQ
In the following instances, there is no limit to the number of main piping branches.
,IWKHSLSLQJOHQJWK/IURPWKH0XOWL.LWDWWKH¿UVWEUDQFKWRWKHIDUWKHVWLQGRRUXQLWLVRYHUIWP
IROORZWKHLQVWUXFWLRQVEHORZZKHQSHUIRUPLQJWKH¿HOGVXSSOLHGSLSLQJZRUN
(Example 1) : Installation with Main Piping Branch (
7
)
3LSLQJOHQJWKIURPWKH0XOWL.LWDWWKH¿UVWEUDQFKWRWKHWHUPLQDOLQGRRUXQLWLVZLWKLQIW
90m).
(1) If the pipe length L2 is over 131.2 ft (40m), the size of gas and liquid pipes “b and c” or “g and h” should
be selected according to Table
4
(see Section 2.14.3), “Diameter of Pipe after First Branch”.
* If the size of (a) is smaller than the size of (b, g) after selecting the size according to Table
4
(see
Section 2.14.3), “Diameter of Pipe after First Branch”, adjust the size of (a) so it is the same size as (b, g).
If the size of (a) is larger than the size indicated in Table
3
(see Section 2.14.3), “Main Pipe Diameter”
of (Equivalent Piping Length > 328.1ft), adjust the size of (a) so it is the same size according to Table
3
(see Section 2.14.3), “Main Pipe Diameter” of (Equivalent Piping Length > 328.1ft).
In this instance, if the size of (b, c, g, h) is larger than the size of each before the branch, adjust the
size of (b, c, g, h) to the same size as each before the branch.
7KHGLIIHUHQFHEHWZHHQWKHSLSLQJOHQJWKIURPWKH¿UVWEUDQFKWRWKHIDUWKHVWLQGRRUXQLWDQGWKHSLSLQJ
OHQJWKIURPWKH¿UVWEUDQFKWRWKHFORVHVWLQGRRUXQLWPXVWEHZLWKLQIWP
* (g+h+j)-(b+d)<131.2 ft (40m)
(Example 2): Installation without Main Piping Branch (
7
)
3LSLQJOHQJWKIURPWKH0XOWL.LWDWWKH¿UVWEUDQFKWRWKHWHUPLQDOLQGRRUXQLWLVZLWKLQIW
90m).
(1) If the pipe length L2 is over 131.2 ft (40m), the size of gas and liquid pipes “b, d and f” should be
selected according to Table
4
(see Section 2.14.3), “Diameter of Pipe after First Branch”.
* If the size of (a) is smaller than the size of (b) after selecting the size according to Table
4
(see
Section 2.14.3), “Diameter of Pipe after First Branch”, adjust the size of (a) so it is the same size as (b).
If the size of (a) is larger than the size indicated in Table
3
(see Section 2.14.3), “Main Pipe Diameter”
of (Equivalent Piping Length > 328.1ft), adjust the size of (a) so it is the size according to Table
3
(see
Section 2.14.3), “Main Pipe Diameter” of (Equivalent Piping Length > 328.1ft).
In this case, if the size of (b, d, f) is larger than the size of each before the branch, adjust the size of (b,
d, f) to the same size as each before the branch.
(
7
): Main Piping Branch:
Both branches of piping from a Multi-Kit are
connected to the next Multi-Kits.
L2
b
a
d
c
e
g
i
f
h
Piping Length from the Multi-Kit at the first branch
to the terminal Indoor Unit is within 131.2 ~ 295.3 ft
First Branch
Multi-Kit
Terminal
Indoor Unit
The Farthest Indoor Unit
from the First Branch
The Closest Indoor Unit
from the First Branch
b
a
First Branch
c
e
d
f
i
j
k
h
g
Terminal
Indoor Unit
Terminal
Indoor Unit
Piping Length from the Multi-Kit at the first branch
to the terminal Indoor Unit is within 131.2 ~ 295.3 ft
Multi-Kit
The Closest Indoor Unit
from the First Branch
ࠉ
The Farthest Indoor Unit
from the First Branch
ࠉ
L2
L2
Indoor Unit
Main Branch
a
b
c
e
f
d
Содержание (H
Страница 2: ......
Страница 10: ...viii TC 16006 ...
Страница 22: ......
Страница 32: ...OUTDOOR UNITS 2 10 TC 16006 2XWGRRU 8QLWV 0RGHO 9 3 DQG 9 3 LQFK PP ...
Страница 45: ...OUTDOOR UNITS TC 16006 2 23 RQWURO 6 VWHP 5HIULJHUDQW FOH 0RGHO 9 3 9 3 9 3 DQG 9 3 LQFK PP ...
Страница 64: ...OUTDOOR UNITS 2 42 TC 16006 2 460V 60Hz MODEL H Y VAHP072B41CW and H Y VAHP096B41CW ...
Страница 90: ......
Страница 124: ... 2016 Johnson Controls Inc TC 16006 Code No LIT 12012299 Issued August 2016 ...