Figure 12: End-of-Line switch positions
To set the EOL switch on a controller:
1. Determine the physical location of the controller on the SA or FC bus.
2. Determine if the controller must be set as a terminating device on the bus.
Note:
The EOL termination rules for SA buses and FC buses are different. Refer to the
FX-
PC Series ControllersMS/TP Communications Bus Technical Bulletin (LIT-12011670)
or
MS/TP
Communications Bus for BCPro System Technical Bulletin (LIT-12011908)
for detailed information
regarding EOL termination rules and EOL switch settings on SA and FC buses.
3. If the controller is a terminating device on the FC bus, set the EOL switch to ON. If the
controller is not a terminating device on the bus, set the EOL switch to Off.
When a controller is connected to power with its EOL switch set to ON, the amber EOL LED on the
controller cover is lit.
Commissioning the Controllers
You commission the FX-PCA controllers with the CCT software, either via a Bluetooth Wireless
Commissioning Converter, a ZigBee® wireless dongle, or in BACnet Router mode when connected
to a Facility Explorer Supervisory Controller. Refer to the
Controller Tool Help (LIT-12011147)
for
detailed information on commissioning controllers.
Note:
The MAP Gateway serves as a replacement for the BTCVT, which is no longer available
for purchase, but continues to be supported.
Troubleshooting the Controllers
Observe the Status LEDs on the front of the controller and see Table 7 to troubleshoot the
controller.