Parts Included
• One controller with removable terminal blocks (Power and SA/FC bus are removable)
• One installation instructions sheet
Materials and special tools needed
• Three fasteners appropriate for the mounting surface (M4 screws or #8 screws)
• One 20 cm (8 in.) or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount
(only)
• Small straight-blade screwdriver for securing wires in the terminal blocks
Mounting
Observe these guidelines when mounting an FX-PCX controller:
• Ensure the mounting surface can support the controller, DIN rail, and any user-supplied
enclosure.
• Mount the controller horizontally on 35 mm DIN rail whenever possible.
• Mount the controller in the proper mounting position (see Figure 1).
• Mount the controller on a hard, even surface whenever possible in wall-mount applications.
• Use shims or washers to mount the controller securely and evenly on the mounting surface.
• Mount the controller in an area free of corrosive vapors and observe the Ambient Conditions
requirements in
.
• Provide for sufficient space around the controller for cable and wire connections for easy cover
removal and good ventilation through the controller (50 mm [2 in.] minimum on the top, bottom,
and front of the controller).
• Do not mount the controller on surfaces prone to vibration, such as duct work.
• Do not mount the controller in areas where electromagnetic emissions from other devices or
wiring can interfere with controller communication.
Observe these additional guidelines when mounting an FX-PCX controller in a panel or enclosure:
• Mount the controller so that the enclosure walls do not obstruct cover removal or ventilation
through the controller.
• Mount the controller so that the power transformer and other devices do not radiate excessive
heat to the controller.
• Do not install the controller in an airtight enclosure.
FX-PCX17 and FX-PCX27 Expansion Input/Output Module Installation Instructions
2