Table 3: FX-PCX17 and FX-PCX27 terminal blocks, functions, ratings, requirements, and cables
Terminal block
label
Terminal
label
Function, ratings, requirements
Determine wire size
and maximum cable
length
Analog Output - Voltage Mode (0–10 VDC)
10 VDC maximum output voltage
10 mA maximum output current
Required an external load of 1,000 ohm or
more.
Note:
The Analog Output (AO) operates
in the Voltage Mode when connected to
devices with impedances greater than
1,000 ohm. Devices that drop below
1,000 ohm may not operate as intended
for Voltage Mode applications.
See Guideline
A
in
Analog Output - Current Mode (4–20 mA)
Requires and external load between 0 and
300 ohm.
Note:
The Analog Output (AO) operates
in the Current Mode when connected to
devices with impedances less than 300
ohm. Devices that exceed 300 ohm may
not operate as intended for Current
Mode applications.
See Guideline
B
in
OUT
n
Binary Output Mode - 24 VAC/DC Field-
effect Transistor (FET)
Connects OUT
n
to OCOM
n
when activated.
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current (hold current)
See Guideline
B
in
Universal
(Outputs)
(FX-PCX27)
OCOM
n
Universal Output (UO) Common
Isolated from all other terminal commons,
including other UO Commons.
Same as OUT
17
FX-PCX17 and FX-PCX27 Expansion Input/Output Module Installation Instructions