background image

FRICK

®

 QUANTUM

™ 

HD VILTER

®

 RETROFIT

INSTALLATION INSTRUCTIONS

090.040-I02 (AUG 2014)

page 10

To install correctly, run a separate, properly sized (10 or 8 
AWG  typically)  insulated  ground  along  with  and  taken  to 
ground  with,  the  3-phase  ground  at  the  3-phase  supply 
transformer (plant). This will require that the 3-phase ground 
and the control power ground be electrically isolated except 
for the connection at the plant supply transformer. 
This  style  of  grounding  should  steer  the  noise  (EMI/RFI) 
to earth ground, reducing the potential for it to affect the 
sensitive equipment, which could occur if the grounds were 
left coupled.

NOTICE

If all other recommendations for grounding are followed, 

this process should not be necessary.

CONDUIT

All national and local codes must be followed for conduit 
with regard to materials, spacing and grounding. In addition, 

Johnson  Controls-Frick  requirements  must  be  followed 
where they exceed or match national or local codes. Con-
versely, there is no allowance for any practices that are 
substandard to what is required by national or local codes. 

Johnson Controls-Frick conduit requirements:
•  For 

variable frequency drives

 (VFDs) of any type, threaded 

metallic  or  threaded  PVC-coated  metallic  is  required 
for both the power feed (line side) from the source and 
between the VFD output and the motor (load side).

•  PVC  conduit  is  acceptable 

only

  when 

VFD rated cable

 

of the proper conductor size and ground is used. This 
applies to both the line side and load side of the drive. 
When VFD rated cable is not used, threaded metallic or 
threaded PVC-coated metallic must be used. 

•  When threaded metallic or threaded PVC-coated metallic 

is used, it must be grounded at both ends. 

•  When not required to be in metal or other material by 

national  or  local  codes,  conduits  for  the  power  feed 
(3-phase) of constant speed starters may be PVC. 

•  When not required to be in metal or other material by 

national  or  local  codes,  conduits  between  a  constant 
speed starter and the motor (3-phase) may be PVC. 

•  Any unshielded control voltage, signal, analog, or com-

munication wiring that does not maintain 12 inches of 
separation  from  any  3-phase  conductors  for  every  33 
feet (10 meters) of parallel run must be in metal conduit 
which will be grounded. 

Separation: (0-33 feet, 0-10 meters – 12 inches, .3 meters), 
(33-66 feet, 10-20 meters – 24 inches, .6 meters) 
•  Since  PVC  conduit  does  absolutely  nothing  to  protect 

lower  voltage  lines  from  the  magnetic  field  effects  of 
higher voltage conductors, running either the lower or 
the higher voltage lines in PVC, does not reduce these 
requirements on separation. Only running in metal conduit 
can relieve these requirements. 

•  Due to the level of EMI that can be induced onto lower 

voltage lines when running multiple feeders in a trench, 
control power, communications, analog, or signal wiring 
cannot be run in trenches that house multiple conduits/
electrical ducts carrying 3-phase power to starters/vfd 
or motors. 

•  Control power, communications, analog, or signal wir-

ing should be run overhead (preferred) or in a separate 
trench.  If  these  lines  are  not  in  threaded  metallic  or 
threaded PVC-coated metallic, abiding by the separation 
requirements noted above is necessary.

•  Though not recommended, if cable trays are used, 

metal-

lic

 dividers must be used for separation of conductors of 

unlike voltages and types (AC or DC).

NOTICE

When  in  doubt  contact  the  factory  or  use  threaded 
metallic or threaded pVC coated metallic conduit.

WIRING pRACTICES

Do not mix wires of different voltages in the same conduit. 
An  example  of  this  would  be  the  installation  of  a  screw 
compressor package where the motor voltage is 480 volts 
and the electronic control panel power is 120 volts. The 480 
volt circuit must be run from the motor starter to the motor 
in its own conduit. The 120 volt circuit must be run from the 
motor starter control transformer to the electronic control 
panel in its own separate conduit. If the two circuits are run 
in the same conduit, transients on the 480 volt circuit will be 
induced onto the 120 volt circuit causing functional problems 
with the electronic control panel. Metallic dividers must be 
used in wire way systems (conduit trays) to separate unlike 
voltages. The same rule applies for 120 volt wires and 220 
volt wires. Also, never run low voltage wires for DC analog 
devices or serial communications in the same conduit with 
any AC wiring including 120 volt wires. See Figure below.

Figure 8. Separation Of Different Voltage Circuits
Never run any wires through an electronic control panel 
that do not relate to the function of the panel.

 Electronic 

control panels should never be used as a junction box.  These 
wires may be carrying large transients that will interfere with 
the operation of the control panel.

 An extreme example of 

this would be to run 480 volts from the starter through 
the electronic control panel to an oil pump motor.

When running conduit to the electronic control panel, use 
the access holes (knockouts) provided by the manufacturer. 
These holes are strategically placed so that the field wiring 
does not interfere with the electronics in the panel. Never 
allow field wiring to come in close proximity with the con-
troller boards since this will almost always cause problems.

Содержание Frick QUANTUM HD VILTER

Страница 1: ...ck for the latest version of this publication Contents Vilter Retrofit Installation Instructions Frick Quantum HD Retrofit Panels 2 Introduction 2 Instructions 3 Calibration of Temperature Pressure Sensors 6 Calibration of Capacity Volume Slides 6 Installation Of Electronic Equipment Wire Sizing 8 Voltage Source 8 Grounding 9 VFD Applications 9 Conduit 10 Wiring Practices 10 Communications 12 UPS ...

Страница 2: ...ONTROL PANEL These instructions are based on the installer having a fun damental knowledge of refrigeration design and installation Instructions are for conversion to the standard design unit Special package and or control modifications furnished on the existing unit will require deviation from these instructions Contact Frick if you have any questions concerns or prob lems Frick does not take res...

Страница 3: ...eat venting and recovery procedure if neces sary 4 If an oil separator temperature probe well is to be installed drain the oil from the oil separator 5 Take digital photographs of all internal connections of the existing controller to use as a reference when making the connections on the replacement controller Remove the existing panel from the compressor package DO NOT CUT WIRES OR TUBING LINES T...

Страница 4: ... to be replaced with the optical actuators before proceeding The position feedback cable from the capacity and volume slide actuators will be routed back to the QUANTUM HD and through 2 of the 4 holes in the 3 4 strain relief that is provided The capacity slide actuator is the one that is physically higher on the compressor To avoid any incidental damage disconnect the cables for control and signa...

Страница 5: ...12 24 vdc is labeled with the part number and acceptable voltage output range The voltages for the 5 12 24 vdc supplies are as follows 5 vdc range 5 10 5 20 vdc 12 vdc range 12 10 12 20 vdc 24 vdc range 24 2 24 5 vdc The power supplies accept both 120 or 220 VAC input range 100 240 VAC 24 At this point the operating display on the controller should be seen Log in to the controller using a default ...

Страница 6: ...n procedure using the value from the gauge 13 Step to the pre oil filter pressure setting on the Pressure Calibration display Calibration of Capacity Volume Slides Go to Menu Calibration Capacity Volume Once on this screen you can attach the power and signal cables at the optical actuators for the capacity and volume slides The optical actuators used for capacity and volume slide positioning provi...

Страница 7: ... board The red LED will begin flashing at a fast rate 2 Touch the Decrease Volume button on the QUANTUM HD calibration page to drive the volume slide to it s minimum physical position Watching the photo chopper on the actuator control board it will be evident when the volume slide is at the physical stop as the photo chopper will suddenly slow and stop 3 Quickly touch the Decrease Volume button to...

Страница 8: ...pressor package or a Central Control System panel NOTICE It is very important to read the installation instructions thoroughly before beginning the project Make sure you have drawings and instructions with your equipment If not call the manufacturer and request the proper instructions and drawings Every manufacturer of elec tronic equipment should have a knowledgeable staff willing to answer your ...

Страница 9: ... must also be insulated to avoid inadvertent contact at multiple points to ground which could create Ground Loops In many installations that are having electronic control prob lems this essential wire is usually missing is not insulated or improperly sized NEC size ratings are for safety purposes and not necessarily for adequate relaying of noise EMI to earth ground to avoid possible interference ...

Страница 10: ...tage lines in PVC does not reduce these requirements on separation Only running in metal conduit can relieve these requirements Due to the level of EMI that can be induced onto lower voltage lines when running multiple feeders in a trench control power communications analog or signal wiring cannot be run in trenches that house multiple conduits electrical ducts carrying 3 phase power to starters v...

Страница 11: ...e conduit and the enclosure so that if water gets on top of the enclosure it cannot run in between the conduit and the enclosure This is extremely important in outdoor applications NOTICE It is simply NEVER a good practice to enter through the top of an electronic control panel or starter panel that does not already have knockouts provided If knockouts are not provided for this purpose it is obvio...

Страница 12: ...c does not advise nor support the use of uninterrupted power supply systems for use with the Quantum HD panel With a UPS system providing shutdown protection for a Frick Quantum panel the panel may not see the loss of the 3 phase voltage on the motor because the UPS may prevent the motor starter contactor from dropping out With the starter contactor still energized the compressor auxiliary will co...

Отзывы: