Johnson Controls Frick IDC Скачать руководство пользователя страница 24

IDC INDUCED DRAFT EVAPORATIVE CONDENSERS

MAINTENANCE

S140-500 IOM (FEB 08)
Page 24

Section 5.0 Troubleshooting

Accurate troubleshooting is greatly facilitated by knowing 
proper unit capacities, dimensions, and other specifi cations.  
Detailed information for specifi c units is provided in the form 
of a drawing package shipped/submitted with the equipment 
delivery.  Reference 

Figure 5-1. IDC Series Standard Unit 

Specifi cations

 

and 

Figure 5-2. IDC Series Standard Unit 

Dimensions

 

for basic design, capacities, and troubleshooting 

data for Imeco IDC units.

Once it is found that a unit is not performing to specifi cations, 
experienced maintenance personnel know that a methodical 
troubleshooting approach signifi cantly reduces the time nec-
essary to pinpoint appropriate responses. Use of the following 
troubleshooting guide is strongly recommended to minimize 
unnecessary repair costs and downtime.

The key to effi cient use of the troubleshooting guide is to 
eliminate the simplest cause(s) until it is possible to isolate 
the specifi c problem/s that need to be rectifi ed. For example, 
a fi ve-minute determination of local ambient wet bulb tem-
perature may prove that a unit is operating under extreme 
weather conditions. A maintenance troubleshooting “log” can 
prove invaluable in keeping up-to-date on such conditions 
and issues.

The following discussion details possible conditions and re-
lated causes for troubleshooting IDC condenser units:

5.1  Condition: High Condensing Pressure

Possible Cause # 1:  IDC Unit / Cooling System Power 

Failure Or Brownout

  Check all fans, pumps, and control panels, for inter-

nal power distribution failures (such as blown fuses or 
overloads) or eliminate them from consideration. Also, 
determine if the utility or stand-by power supply back up 
has failed to supply adequate, consistent power. Should 
main or standby power supply equipment need updating, 
contact a local electrical expert or design/build contractor 
to provide for consistent power.

Possible Cause # 2:  Excessive Wet Bulb Temperature

  Wet bulb temperature can be determined by using a “sling 

sychrometer” to take a reading near the inlet of the cooling 
tower/s. Background or ambient wet bulb is determined 
with the sling sychrometer at an upwind location or by 
cross-referencing local ambient “dry bulb” and humidity 
levels.

  If background wet bulb is in specifi cation and the wet bulb 

at the inlet is out of specifi cation – exhaust air recirculation 
may be excessive. Refer to the siting discussion provided in 
Section 1.0 and consult with the cooling system engineer 
to determine if re-siting or other cooling system changes 
are needed.

Possible Cause # 3:  Insuffi cient Water Flow/Pressure 

To Spray Tree

  Check water fl ow and pressure at the IDC inlet pipe con-

nection. Even if this was checked and confi rmed at the time 
of start-up, changes to plant water supply or internal piping 
may have created additional pressure drops (line losses) 
between the pump/s and the spray tree connection.

  The IDC spray-piping tree requires 2-10 PSI at the connec-

tion at the fl ow rates (in GPM) specifi ed for the unit. This 
information is available from the local representative.

  For remote pump applications, water must be supplied 

at the pressure and fl ow rate specifi ed on the customer 
drawings. 

Possible Cause # 4:  Inadequate Water Distribution

  In the event that a few nozzles prove to be clogged or 

restricted, it may be necessary to remove the spray 

piping “tree” and clean all of the nozzles thoroughly (as 
discussed in Section 4.0 Maintenance). This will ensure 
that all nozzles are clean and properly realigned before 
re-installing the spray tree.

Possible Cause # 5:  Low Fan Output

  Check fan voltage and amp draw readings and compare 

to specifi cations. If amp draw is excessive, check airfl ow 
pathways to ascertain that no restrictions exist. Restrictions 
may be blocking fl ow through intake louvers, eliminators, 
or the fan guard. Clear all air restrictions and rotate fan to 
check for binding blade tips in the orifi ce.

  If the fan has an adjustable-pitch propeller, check an-

gle-of-attack adjustment location on each blade. All blades 
should have the same angle as specifi ed for the unit. If 
amp draw is still low, increase the setting for all fi ns by a 
fraction of a degree and take new amp draw readings.

Possible Cause # 6:  Inadequate Water Treatment

  Check scale buildup on coil. Scale buildup 1/32" thick can 

cause a 30% capacity reduction (as rated in cooling tons 
per hour). 

Possible Cause # 7:

 

Improperly Sized Or Applied Ancil-
lary Component Or System Piping

  Check system piping against system designer’s plans and 

specifi cations. Look for unusual mixed piping sizes/materi-
als, excessive vertical/horizontal distances, “add-on” fl ow 
restricting devices, and poor quality pipe-fi tting and support 
anchors.

Possible Cause # 8:  IDC Unit Experiencing “Recircula-

tion” Due To Improper Siting

  Recirculation of warm, moist exhaust air can rob up to 

30% of the IDC unit’s cooling capacity. Since this is a 
highly variable condition depending on weather conditions 
and the operational timing of nearby cooling units, plant 
maintenance is encouraged to consult with the cooling 
system design engineer.

  Generally speaking, an IDC unit should be located above 

roof level, as far away as possible from other exhaust 
stacks, and upwind of higher wind-diverting structures. 
Any diversion from these rules-of-thumb should be re-
examined by the system design engineer.

Possible Cause # 9:  Noncondensables In Receiver or 

Condenser

  Check condenser and receiver to determine if non-con-

densables have contaminated the system. If non-condens-
ables are found, proceed with repairs as prescribed by the 
refrigeration equipment/system supplier (e.g., evacuating 
the refrigerant lines/system and recharging after eliminat-
ing leak or source of contamination).

5.2  Condition: Excessive Deposits, Scale, Or

Turbidity

Possible Cause # 1:  Inadequate Filtration Or Treatment 

Of Spray Water

  Filtration is an inherent requirement for evaporative cooling 

systems due to the concentration of dissolved solids and 
“washing” of air particulate. Recommended fi lters types 
include bag, mesh, centrifugal, and sand & gravel.

  Filtration equipment must be maintained regularly. All fi lters 

(partial/side fl ow designs in particular) must be cleaned or 
back-fl ushed regularly.

  In the event that plant-cooling system seems to have 

inadequate fi ltration, Imeco recommends that the system 
design engineer consult with a local water treatment ex-
pert. Until the situation is resolved, blow-down rates should 

Содержание Frick IDC

Страница 1: ...om for the latest version of this publication IDC INDUCED DRAFT EVAPORATIVE CONDENSERS Form S140 500 IOM FEB 2008 INSTALLATION OPERATION MAINTENANCE File SERVICE MANUAL Section 140 Replaces S140 500 I...

Страница 2: ...rt up Operation 16 3 1 Initial Start up for new IDC Units 16 3 2 Initial and Seasonal Start Up 16 3 3 24 Hour Run In 17 3 4 Daily Operation 17 3 5 Seasonal Start up Shutdown 17 3 6 Winter Operations 1...

Страница 3: ...gure 2 2 Eliminator Orientation Cross Section 12 Figure 2 3 Louver Installation 12 Figure 2 4a Assembly and Placement 13 Figure 2 4b Assembly and Placement 14 Figure 2 5a Vibration Isolator Feet 15 Fi...

Страница 4: ...d utilizes the finest in engineered design materials and corrosion protection to provide a rugged long lasting unit This manual provides the information needed for safe installation operation and main...

Страница 5: ...ports and installing the IDC condenser Adequate space must be continuously available to allow adequate airflow to the IDC inlet louvers to prevent discharge air recirculation Figure 1 2 IDC Unit to Un...

Страница 6: ...IDC INDUCED DRAFT EVAPORATIVE CONDENSERS INSTALLATION S140 500 IOM FEB 08 Page 6 Figure 1 2 IDC Unit to Unit Spacing Requirements...

Страница 7: ...IDC INDUCED DRAFT EVAPORATIVE CONDENSERS INSTALLATION S140 500 IOM FEB 08 Page 7 Figure 1 3 IDC Unit to Wall Spacing Requirements Multiple Cell and Multiple Unit Installation...

Страница 8: ...et set Belt tension gage Tape measure 2 2 Foundation Information IDC units are shipped in two pieces a pan section and the fan coil section As the unit s base the pan section must first be anchored to...

Страница 9: ...DENSERS INSTALLATION S140 500 IOM FEB 08 Page 9 Figure 2 1a 12 x 12 Foundation Layout OVERALL MODEL APPLICABLE CELLS LENGTH WIDTH 420 540 A 145 141 840 2S 1080 2S A D 145 286 840 2E 1080 2E A B 294 14...

Страница 10: ...NSERS INSTALLATION S140 500 IOM FEB 08 Page 10 Figure 2 1b 12 x 18 Foundation Layout OVERALL MODEL APPLICABLE CELLS LENGTH WIDTH 575 835 A 211 141 1120 2S 1620 2S A D 211 286 1150 2E 1670 2E A B 426 1...

Страница 11: ...NSERS INSTALLATION S140 500 IOM FEB 08 Page 11 Figure 2 1c 12 x 20 Foundation Layout OVERALL MODEL APPLICABLE CELLS LENGTH WIDTH 870 990 A 245 141 1690 2S 1920 2S A D 245 286 1740 2E 1980 2E A B 494 1...

Страница 12: ...5 a b Vibration Isolator Installation and the following instructions ISOLATOR FEET INSTALLATION 1 Refer to the submitted foundation layout drawing for the correct location of each isolator and suppor...

Страница 13: ...d Placement NOTES 1 The hook of the crane must be a minimum height above the top of the section being lifted to prevent excessive strain on the lifters 2 Safety slings and skidding should be removed b...

Страница 14: ...IDC INDUCED DRAFT EVAPORATIVE CONDENSERS INSTALLATION S140 500 IOM FEB 08 Page 14 Figure 2 4b Assembly and Placement...

Страница 15: ...aterally with the weight on the isolators If it is necessary to move the unit remove the weight from the isolators by raising the unit before moving Failure to follow this procedure could result in da...

Страница 16: ...art up and operate any electrical cool ing equipment such as an IDC condenser unit it is essential that all personnel associated with have a basic knowledge of how and why the unit operates in normal...

Страница 17: ...ol of the pan water level The system consists of a weather protected electric float switch with stilling chamber mounted on the pan section and a weather protected solenoid valve mounted on the water...

Страница 18: ...NTHS MONTHS MONTHS Inspect General Condition of Unit X X Clean debris from unit X X X Clean and flush sump X X X Clean sump strainer X X X Check and adjust sump water level X X Inspect heat transfer s...

Страница 19: ...L NUMBER PART NUMBER RECOMMENDED STOCK LEVEL FAN BELTS __________________________________________________ One Set FAN BEARINGS _______________________________________________ One Set FAN BUSHING _____...

Страница 20: ...earings used on the belt drive IDC units are prelubricated with grease chosen for its chemical and mechanical stability in an evaporitive cooling environment The type of grease used is lithium complex...

Страница 21: ...e belt span s mid point as measured between the tangent of belt contact for both sheaves Reference Figure 4 5 Belt Tensioning Schematic 4 7 New Belt Run in During initial startup of new belts a belt r...

Страница 22: ...is an important part of the water treatment process During passivation operate the condenser as follows Clean all surfaces Maintain pH levels as close to 7 0 as possible Do not allow the pH to fall b...

Страница 23: ...compound or Zinc solder If surrounding components will not be damaged by flame lev el heat a blowtorch can be used to slowly heat the scratch to the melt point of a Zinc solder rod Apply the Zinc unti...

Страница 24: ...remote pump applications water must be supplied at the pressure and flow rate specified on the customer drawings Possible Cause 4 Inadequate Water Distribution In the event that a few nozzles prove to...

Страница 25: ...eup valve assembly and refill basin to operat ing level Possible Cause 3 Pump Output Incorrect Take flows and pressure readings from pump piping in question Determine if pump may be throttled with mea...

Страница 26: ...00 44 25 2 140 70 686 95 040 28 013 840 2S 595 8 162 594 2 15 1 430 2 5 2 6 PE 2 10 PE 1 200 198 00 30 25 850 32 198 45 022 11 957 870 2S 617 0 169 732 2 20 1 430 2 5 2 6 PE 2 10 PE 1 200 198 00 30 2...

Страница 27: ...IDC INDUCED DRAFT EVAPORATIVE CONDENSERS INSTALLATION OPERATION MAINTENANCE S140 500 IOM FEB 08 Page 27 Figure 5 2 Standard IDC Series Unit Dimensions...

Страница 28: ...ns precise control 24 hours a day seven days a week I Q NET distributed architecture mean faster easier economical installations I Q NET delivers increased operating efficiency and lowers energy costs...

Отзывы: