background image

3

 -

The electrical connections to the FMS-1655R 

are made via convenient terminal block 

connectors as shown on

 page 7.

 

 

All wiring should conform to local regulations 

and to the National Electrical Code (NEC). 

Precautions must be taken to avoid running 

communications wiring in the same conduit as 

line voltage or other conductors that supply 

highly inductive loads such as generators, 

motors, solenoids, contactors, and other 

sources of induced noise. Use 22 AWG or 

larger for all electrical wiring terminations.

1. The FMS-1655R surface mount model 

should be mounted in a location that provides 

convenient access so the display may be 

viewed with minimal glare and the touch 

screen is easily accessible to facilitate 

silencing the unit in the event of an alarm 

condition. 

2. Begin the mounting procedure by removing 

the surface mount enclosure cover from the 

Safety Halo™ backplate. Turn the set screw 

at the bottom of the enclosure clockwise until 

it has cleared the hole in the cover, thereby 

allowing it to be removed from the backplate. 

To re-secure the cover, turn the set screw 

counter-clockwise 

until is it flush with the 

cover.  

3. If this is a new construction project and 

a single-gang wall box has been installed, 

you may skip the next step. If this is a retrofit 

application and existing drywall is in place, 

then proceed with the next step to prepare 

for the mounting of the FMS-1655R surface 

mount model. 

4. There are two primary options for installing 

the FMS-1655R surface mount model in 

retrofit applications. The first option is to use 

two drywall anchors to mount the surface 

mount Safety Halo

TM

 backplate. Using the 

backplate as a template for marking and 

drilling a ¾” hole at the center, bring the low-

voltage wiring required for the FMS-1655R 

through the center hole at the backplate. The 

second option is to use an old-work low-

voltage box or bracket as shown in 

Figure 3

.

 

5. Once the surface mount Safety Halo

TM 

backplate has been properly installed, the 

electrical connections should be terminated 

before installing the cover with the display. 

Run the 4-conductor, dual twisted pair, 

electrical connection from the nearest 

controller. Refer to the wiring diagram shown 

on

 page 7 for detail

s.

 

6. Terminate the interface cable originating 

from the host controller at the 4-position and 

3-position terminal blocks on the back side 

of the FMS-1655R display, ensuring proper 

electrical connections. Power connections 

should be terminated at +V and GND 

of the 4-position terminal block, and the 

subnet connections should be terminated 

at NETWK+ and NETWK- of the 3-position 

terminal block (see page 7).  

7. With the electrical connections properly 

terminated, the surface mount enclosure 

cover may be installed by sliding the two tabs 

at the top of the inside edge into the two slots 

at the top of the Safety Halo™ backplate 

secured to the wall. Secure the FMS-1655R 

enclosure cover by turning the slotted set 

screw at the bottom of the backplate counter-

clockwise, backing it out until it is flush with 

the cover. 

Quick Start Guide

After the FMS-1655R has been properly 

installed, apply power to the companion FMS-

1655 room controller. Upon power up, you will 

hear a quick beep at the FMS-1655R which 

indicates that the initialization sequence has 

been initiated.  

The Safety Halo™ edge lighting will cycle 

through seven colors (red, green, blue, yellow, 

magenta, cyan, and white), followed by the 

three action icons shown in 

Figure 4 

that 

represent normal, caution, and alarm. 

Next, the JCI splash screen indicating the 

electronic serial number (ESN), firmware 

version numbers, and the current subnetwork 

address of the companion FMS-1655 will 

appear. This splash screen remains displayed 

for several seconds and then disappears to 

reveal the main display screen in the currently 

configured viewing mode. 

The information shown on the splash screen 

may also be re-displayed at any time by 

selecting 

About This FMS Remote Display

 on 

the 

Diagnostics 

menu.

INSTALLATION MANUAL

Fig 3. Old Work Low-voltage Box/Bracket

Содержание FMS-1655 Series

Страница 1: ...beginning installation North American Emissions Compliance United States Canada Installation This Class A digital apparatus meets all the requirements of the Canadian Interference Causing Equipment Regulations Cet appareil numérique de la Classe A respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada Risk of Property Damage Ensure that the power source conforms to the req...

Страница 2: ...ings 6 Wiring the FMS 1655R to Nearest JCI Controller 7 Notes 8 PROGRAMMING MANUAL Introduction 9 Main Setup Menu 9 Unit Setup 10 Configuring Monitor Settings 10 Configuring Audible Alert Settings 10 System Setup 11 Managing System Security Passwords 12 Adding New Passwords 12 Deleting an Existing Password 12 Purging All Passwords 12 Display Setup 12 Configuring the Safety HaloTM 12 Selecting Disp...

Страница 3: ...ry RS 485 interface Power may be supplied by FMS 165x or by separate power supply 18 to 32 Vdc Touchscreen User Interface LCDSizeandType 3 2 diagonal transmissive Resolution 240 pixels x 320 pixels portrait mode Viewing Area 50 60 mm x 66 80 mm Color Depth 18 bit or 262K colors Backlight Color White Luminous Intensity min 2500 cd m2 Mechanical Mounting Options Surface Plastic Flush Brushed Stainle...

Страница 4: ...es the setup and configuration of the remote display The display incorporates bright background color changes to indicate up to five different statuses at the companion FMS 1655 Green represents normal status whereby the monitored parameter is within defined normal operating limits Yellow indicates that the monitored parameter has drifted outside of the normal operating limits and is approaching t...

Страница 5: ...rmly to ensure maximum adhesion 5 The electrical connections must be terminated before installing the stainless steel faceplate of the FMS 1655R Run the 4 conductor dual twisted pair electrical connection from the nearest FMS 1655 Refer to the wiring diagram shown on page 7 for details 6 Terminate the interface cable originating from the host controller at the 4 position and 3 position terminal bl...

Страница 6: ...surface mount Safety HaloTM backplate has been properly installed the electrical connections should be terminated before installing the cover with the display Run the 4 conductor dual twisted pair electrical connection from the nearest controller Refer to the wiring diagram shown on page 7 for details 6 Terminate the interface cable originating from the host controller at the 4 position and 3 posi...

Страница 7: ...exclamation point action icon Figure 8 indicates that the monitored parameter has reached a critical condition and is outside of the allowable limits of the target setpoint This visual indication is supplemented by an audible alarm to indicate that attention is required The FMS 1655R incorporates a full color touchscreen display and with an intuitive menu system that allows the user to quickly set...

Страница 8: ...yed parameter in the upper LCD window gray box on the main display Tapping this field invokes a details screen which includes all six of the analog input parameters currently being monitored at the companion FMS 1655 To change which parameter is displayed on the main screen of the FMS 1655R select the individual parameter on the details screen and tap the OK button Adding Password Security The FMS...

Страница 9: ... mode is selected may be adjusted either by using the hotspots on the main display or by selecting Display Setup Set Time Date The FMS 1655R is also designed to request time and date settings periodically from the companion FMS 1655 assuming it resides on a network that has a time server available This ensures that the time and date are accurate on the FMS 1655R main display INSTALLATION MANUAL 6 ...

Страница 10: ...Due to continuous improvement JCI reserves the right to change product specifications without notice INSTALLATION MANUAL Wiring FMS 1655R to Nearest JCI Controller 7 CN7 CN3 NETWK NETWK GND V ...

Страница 11: ...s improvement TRIATEK reserves the right to change product specifications without notice Due to continuous improvement JCI reserves the right to change product specifications without notice INSTALLATION MANUAL Notes 8 ...

Страница 12: ...ivity while configuration screens automatically time out after 60 seconds This prevents unauthorized access to the user menu system should a unit be inadvertently left unattended at one of the configuration screens Main Setup Menu All of the configuration screens that allow the settings of the FMS 1655R to be configured for a specific application originate from the top level of the user interface ...

Страница 13: ... status of the companion FMS 1655 Tapping Finish at the Monitor Setup configuration screen stores that subnetwork address of the companion FMS 1655 and begins the polling process immediately Configuring Audible Alert Settings The Audible Alert option on the Unit Setup menu provides support for configuring the settings associated with the audible alarming capabilities of the FMS 1655R and invokes t...

Страница 14: ...m limits and is in need of attention This critical condition is indicated by a red background and a red exclamation point action icon The Safety Halo status indicator if enabled will flash quickly in red to indicate the Alarm status A blue background indicates that Neutral isolation mode is selected at the companion FMS 1655 This mode is indicated by an action icon represented as a red circle with...

Страница 15: ... Safety Halo option on the Display Setup menus allows you to configure the settings for the Safety Halo bezel including the Nightly Auto Dim feature This feature allows the Safety Halo to automatically reduce its brightness to the specified percentage at the specified Starting Hour and return to normal brightness at the specified Ending Hour To configure the Safety Halo select the Safety Halo opti...

Страница 16: ...FMS 1655R is designed to synchronize its local time and date with the network resident controller it is monitoring thereby allowing the time based features to operate accurately These include the Alarm Buzzer Quiet Period and the Safety HaloTM Auto Dim Period Selecting this option invokes the time configuration screen as shown in Figure 25 The colon between the hours and minutes automatically appe...

Страница 17: ...your unit Resetting the FMS 1655R The Reset Monitor option on the Diagnostics menu allows the user to perform a soft reboot of the remote display and completely re initialize the unit This option may be useful during the installation process when changes have been made to the network parameters subnetwork address Selecting this option invokes the warning message as shown in Figure 28 informing the...

Страница 18: ...Due to continuous improvement JCI reserves the right to change product specifications without notice User Menu Flow Diagram 15 PROGRAMMING MANUAL ...

Страница 19: ...Central Monitoring Station JCI FMS 1655 The Next Generation in Critical Airflow Controls FMS 1655 Room Pressure Remote Display Installation and Programming Manual LB FMS1655 RS LB FMS1655 RT Code No LIT 12013124 Rev A Issued August 2018 1 414 524 1200 Johnson Controls 5757 N Green Bay Ave P O Box 591 Milwaukee WI 53201 ...

Отзывы: