![Johnson Controls E-Link Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/johnson-controls/e-link/e-link_installation-instructions-manual_2024158009.webp)
E-Link Gateway Installation Instructions
9
Table 8: Equipment Quick Start Selections
APP Group Switch A
Equipment Profile Quick Starts
Switch Settings
32
16
8
4
2
1
Functionality
1
1
0
0
0
0
0
1
YK with SSS Imperial
(YORK Talk-III) J version points
2
0
0
0
0
1
0
YK with VSD Imperial
(YORK Talk-III) J version points
3
0
0
0
0
1
1
YT with SSS Imperial
(YORK Talk-III) J version points
4
0
0
0
1
0
0
YT with VSD Imperial
(YORK Talk-III) J version points
5
0
0
0
1
0
1
YS / YR with SSS Imperial
(YORK Talk-III) J version points
6
0
0
0
1
1
0
YK with SSS Metric
(YORK Talk-III) J version points
7
0
0
0
1
1
1
YK with VSD Metric
(YORK Talk-III) J version points
8
0
0
1
0
0
0
YT with SSS Metric
(YORK Talk-III) J version points
9
0
0
1
0
0
1
YT with VSD Metric
(YORK Talk-III) J version points
10
0
0
1
0
1
0
YS / YR with SSS Metric
(YORK Talk-III) J version points
11
0
0
1
0
1
1
YORK Talk II, 1200, 1 Section
(YORK Talk-II) J version points
12
0
0
1
1
0
0
YORK Talk II, 4800, 1 Section
(YORK Talk-II) J version points
13
2
0
0
1
1
0
1
YORK Talk II, 4800, 2 Sections
(YORK Talk-II) J version points
14
0
0
1
1
1
0
YD Imperial
(YORK Talk-III) J version points
15
0
0
1
1
1
1
YD Metric
(YORK Talk-III) J version points
16
0
1
0
0
0
0
ECO2 / YPAL / S100
(BACnet MS/TP via an IPU-I)
17
0
1
0
0
0
1
YK with SSS Imperial
(YORK Talk-III) K version points
18
0
1
0
0
1
0
YK with VSD Imperial
(YORK Talk-III) K version points
19
0
1
0
0
1
1
YT with SSS Imperial
(YORK Talk-III) K version points
20
0
1
0
1
0
0
YT with VSD Imperial
(YORK Talk-III) K version points
21
0
1
0
1
0
1
YS / YR with SSS Imperial
(YORK Talk-III) K version points
22
0
1
0
1
1
0
YK with SSS Metric
(YORK Talk-III) K version points
23
0
1
0
1
1
1
YK with VSD Metric
(YORK Talk-III) K version points
24
0
1
1
0
0
0
YT with SSS Metric
(YORK Talk-III) K version points
25
0
1
1
0
0
1
YT with VSD Metric
(YORK Talk-III) K version points
26
0
1
1
0
1
0
YS / YR with SSS Metric
(YORK Talk-III) K version points
27
0
1
1
0
1
1
YST Imperial
(YORK Talk-III) K version points
28
0
1
1
1
0
0
YIA Imperial
(YORK Talk-III) K version points
29
0
1
1
1
0
1
YST Metric
(YORK Talk-III) K version points
30
0
1
1
1
1
0
YIA Metric
(YORK Talk-III) K version points
31
0
1
1
1
1
1
YEWS-D1/YEAS/YGAS
(Modbus native)
32
1
0
0
0
0
0
YD Imperial
(YORK Talk-III) K version points
33
1
0
0
0
0
1
YD Metric
(YORK Talk-III) K version points
34
1
0
0
0
1
0
YMC2 Imperial
(YORK Talk-III) K version points
35
1
0
0
0
1
1
YMC2 Metric
(YORK Talk-III) K version points
63
1
1
1
1
1
1
Reserved for Field adjustments
1.
A Quick Start that references a Solid State Starter (SSS) is also applicable to a mechanical starter.
2.
Two sections are required for equipment equipped with three or more compressors, or two systems.