Johnson Controls E-Link Скачать руководство пользователя страница 12

E-Link Gateway Installation Instructions

12

Electrical Noise Mitigation to Equipment

The likelihood of transient voltage is greatly reduced if 
the E-Link Gateway is close-coupled to the Micro 
Panel. Close-coupling requires that the E-Link 
Gateway and Micro Panel share the same line voltage 
power source and are physically close to one another. 
Typically, the E-link Gateway is mounted on the Micro 
Panel enclosure. This scenario ensures a short 
communication cable, which is usually protected 
entirely within the two enclosures.

Electrical Noise Mitigation
for E-Link to BAS

When the E-Link is used in an electrically hostile 
environment (for example, with VSD-enabled 
equipment), a double-shielded cable should be used to 
help mitigate the adverse effects electrical noise can 
have on the system. The double-shielded cable should 
connect the E-Link’s BAS port (Port 1 or Port 4) to the 
next controller(s) in the daisy-chained network. 

The outer shield of the double-shielded cable should 
be grounded directly at the 

low noise end

 (the end 

most distant from the VSD), and ideally, indirectly 
through an appropriate capacitor at the 

high noise end

 

(the end closest to the VSD). If a capacitor is not 
available, the outer shield may be left unconnected, or 
tied directly to ground. The best results on the site 
determine the specific termination strategy employed.

The inner shield of the double-shielded cable should be 
grounded directly at the 

low noise end

 (the end most 

distant from the VSD), and left open at the 

high noise 

end

 (the end closest to the VSD).

Types of Communication Ports

The E-Link Gateway uses three communication 
protocols to connect to other devices: RS-485 and FFT 
are used for multi-drop networking, whereas RS-232 is 
primarily used for point-to-point connectivity.

RS-485

The RS-485 standard uses three conductors to 
connect network nodes: two signal wires and a 
reference. The E-Link Gateway uses either a third wire 
for the reference or the building’s infrastructure. The 
wiring method depends on the port being used: an 
electrically isolated Port 1 typically uses a third wire, 
whereas Ports 2 and 3 normally use chassis or building 
ground for the reference.

Setup and Adjustments

There are a number of settings that you may make on 
an E-Link Gateway or to the connected equipment.

Network Termination

Terminate all End-of-Line (EOL) devices at either end 
of the RS-485 bus (that connect to only one set of 
RS-485 network wires). EOL termination provides 
biasing of the network, and assists in returning the 
signal to a normal state in the event of voltage 
transients. If the E-link Gateway happens to be the 
end-of-line device, terminate the network by setting the 
EOL switch located above each of the 
E-Link Gateway’s RS-485 ports to the ON position.   

Media Access Control (MAC) Address

The E-Link Gateway’s network hardware address is set 
on a single 8-way DIP switch. Switch 8, the T switch, is 
reserved to invoke Terminal mode on Port 3, leaving 
the remaining 7 switches for setting the address. Refer 
to the 

E-Link Gateway Commissioning and 

Troubleshooting Technical Bulletin 
(LIT-12011238)

 for more details.

The network address is binary weighted, allowing you 
to set up to 127 unique addresses.

APP Group A

APP Group A uses a 6-way DIP switch to select the 
desired equipment’s profile. This switch is also binary 
weighted, allowing up to 63 unique selections.

IMPORTANT:

Do not run communication cables in 

close proximity to, or parallel with, high-voltage 
power cables (maintain at least 457.2 mm [18 in.] of 
separation, or use a grounded metal conduit).

IMPORTANT:

Ensure that the EOL switches are 

not set to the ON position for controllers that do not 
terminate the RS-485 network.

Figure 8: RS-485 EOL Switches

Figure 9: MAC Dip Switch

Содержание E-Link

Страница 1: ...Gateway circuit board a transformer is included inside the enclosure that converts a 120 or 240 volt input to 24 VAC power North American Emissions Compliance United States Canada Installation The E...

Страница 2: ...YLPA 031 01095 YORK Talk 2 4 800 bps YCAS YCWS YCRS 031 02478 YORK Talk 2 4 800 bps YCAV YCIV YVAA 031 01065 YORK Talk 2 1 200 bps YIA YPC YG YB 031 01730 YORK Talk 3 YN OM RETROFITS CR 031 02430 YORK...

Страница 3: ...re jumper JP27 is set for RS 232 see Figure 20 6 Connect the power harness included with the kit from J2 on the E Link Gateway to J21 on the Optiview Micro Panel see Figure 20 The E Link Gateway is no...

Страница 4: ...ground screw The E Link Gateway is now ready to be configured using Quick Start see the Commissioning a Standard Application section in this document Micro Board 24 VAC Transformer Expansion Nut Expa...

Страница 5: ...ateway enclosure to the Micro Panel 6 Complete wiring as described in the Applying Power section in this document Note Use of bulkhead pipe couplers provides sufficient clearance to allow removal of t...

Страница 6: ...e metal of both enclosures Scraping the paint around the knockouts usually helps provide a better electrical connection between the joining parts 1 Connect a 1 29 1 02 mm 16 18 AWG wire from a reliabl...

Страница 7: ...to the Johnson Controls Portal Products and Services Delivery Products Service Field Support Equipment Integration YORK Equipment Data Maps 3 Press hold a few seconds then release the push button show...

Страница 8: ...1 through 16 all use the J version point lists whereas Quick Starts 17 through 33 use the K version The primary difference between the two categories is that Quick Starts 1 through 16 have limited net...

Страница 9: ...IPU I 17 0 1 0 0 0 1 YK with SSS Imperial YORK Talk III K version points 18 0 1 0 0 1 0 YK with VSD Imperial YORK Talk III K version points 19 0 1 0 0 1 1 YT with SSS Imperial YORK Talk III K version...

Страница 10: ...600 N 8 1 Terminal 4 2 5 0 1 0 0 N2 9 600 N 8 1 MS TP 38 400 N 8 1 Terminal 5 2 5 0 1 0 1 Modbus 19 200 N 8 1 MS TP 38 400 N 8 1 Terminal 6 2 5 0 1 1 0 Modbus 19 200 N 8 2 MS TP 38 400 N 8 1 Terminal...

Страница 11: ...nzorbs on each RS 485 port to protect against damaging electrical spikes and stray voltage The equipment panel should also be equipped with protection against electrical disturbances Whereas OptiView...

Страница 12: ...ctivity RS 485 The RS 485 standard uses three conductors to connect network nodes two signal wires and a reference The E Link Gateway uses either a third wire for the reference or the building s infra...

Страница 13: ...ch setting 1 Since the E Link Gateway uses a one to one relationship with the chiller panel this switch is normally set to 0 YORK Talk address 1 However in a master slave configuration set the master...

Страница 14: ...itude POWER HARNESS Latitude 3 8 in Screw 8 x 32 OptiView 2 Position Connector 4 Position Connector 4 Position Connector 4 Position Connector Screw Tap Thread M4 x 32 mm Latitude FIG OptiVwKt YMC2 COM...

Страница 15: ...Transformer Primary Power Wiring Harness Communication Wiring Harness Resistor Secondary Power Wiring Harness Tie Wrap FIG IPUII Kt Figure 15 E Link IPU II Panel Installation Kit YK ELNKSTK 0 Contents...

Страница 16: ...is dated after 11 2000 the chiller ID is software selectable through the micro panel SHIELD BLUE WHITE Open 031 02050 000 TB1 TB6 NOTE The chiller ID is software selectable through the micro panel ke...

Страница 17: ...E Link Gateway Installation Instructions 17 Figure 18 E Link Gateway to YORK Talk II Equipment Connections Continued See Table 1 for board cross reference...

Страница 18: ...s in locations U4 and U5 The transfer rate on the chiller must be set to 4800 baud Frick RWBII Plus Jumpers Jumpers RWBII Rev B and Lower RX Jumpers RWBII Rev C and Higher U5 U4 Port 2 Port 1 SHIELD P...

Страница 19: ...lk 3 Rs232 Optiview Microboard 031 01730 XXX SHIELD PORT 2B RS232 TX RX COMSHLD Open E Link E Link 12 VDC SHIELD Open Equipment Cable York Talk 2 RS485 4800 baud SHIELD COM SHLD PORT 2A RS485 Open E L...

Страница 20: ...xxx I O Board 331 02496 101 IPU I Board YPAL ECO2 1 J4 2 3 4 5 P3 P3 GND 5V Equipment Cable BACnet MS TP 38400 baud FIG YPAL YPAL ECO2 Setup for MS TP Bus BLUE WHITE SHIELD GRD COM SHLD PORT 2A RS485...

Страница 21: ...s a pre wired E Link Port 2 Terminal Block RS485 4800 baud SHIELD PORT 2A RS485 Open E Link 031 02550 xxx I O Board 031 02630 xxx IPU II Board T 1 RS485 REF SHLD IPU II P1 Setup for York Talk 2 FIG ST...

Страница 22: ...E Link Gateway Installation Instructions 22 Figure 23 E Link Gateway to Wuxi STC YEWS D1 YEAS YGAS Equipment Connection Fig wuxi_stc...

Страница 23: ...E Link Gateway Installation Instructions 23 Figure 24 E Link Gateway Communication Port Connections to a BAS System...

Страница 24: ...if this connection has not been made elsewhere in the configuration Repair Information If the E Link Gateway fails to operate within its specifications replace the unit For a replacement E Link Gatew...

Страница 25: ...PP Switch Group A 6 Position Dip Switch Port 2A RS485 Equipment Port Supporting BACnet MS TP and YORK Talk II Protocols with Available EOL Termination Switch Port 2B RS232 Equipment Port Supporting YO...

Страница 26: ...Installation Instructions 26 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2011 Johnson Controls Inc Bu...

Отзывы: