Johnson Controls E-Link Скачать руководство пользователя страница 8

E-Link Gateway Installation Instructions

8

6.

Place the equipment in remote operating mode to 
accept commands from the E-Link Gateway. Refer 
to the equipment installation literature for the 
proper configuration settings.

For all chillers that use the YORK Talk protocols, check 
that the Port 2 communication LEDs, Red (TX) and 
Green (RX), are flashing. This scenario indicates that 
the chiller panel is being polled and is responding. See 
Figure  for the location of Port 2 communication LEDs.

What You Should Know before 
Using Quick Starts

The E-Link is designed to use a set of predefined data 
maps to associate equipment data with a set of fixed 
BAS network variables. You are not able to make any 
field changes to these data maps; attempting to do so 
results in the automatic reversal of any edits that you 
may have made. For any field patches, refer to your 
local 

FSC (Field Support Center)

 for guidance.

The data maps used by the E-Link Gateway are based 
on a collection of version controlled equipment point 
lists, which are supplied by the equipment business for 
the purpose of integrating equipment into BAS 
networks. Unless noted otherwise, the equipment’s 
data is available in these supported BAS protocols: 
BACnet MS/TP, N2, 

L

ON

W

ORKS

, and Modbus RTU.

The first release of the E-Link was positioned to 
provide the equivalent functionality as offered by the 
YORK MicroGateway. That release requires you to 
reference point lists which are version J or earlier. All 
subsequent E-link releases use point lists version K or 
later.

Quick Starts 1 through 16 all use the J version point 
lists, whereas Quick Starts 17 through 33 use the K 
version. The primary difference between the two 
categories is that Quick Starts 1 through 16 have 
limited network visible points. In this case, the available 
points are those which were originally available at the 
time when the MicroGateway was first released.

Quick Starts 17 and higher offer a much richer 
equipment point compliment that is more reflective of 
what the equipment currently makes available today. 
These Quick Starts also create profiles that use more 
descriptive BACnet point names, use engineering 
units, and follow the BACnet Testing Laboratories™ 
(BTL) guidelines for compliance as a B-ASC controller.

In most cases, using a Quick Start that corresponds to 
the equipment being integrated is sufficient to configure 
the E-Link Gateway for operating on the BAS network; 
however, in some circumstances, you will be required 
to provide further customizing by connecting a laptop 
computer onto Port 3 and then accessing the User 
Reports (refer to the

 E-Link Gateway Commissioning 

and Troubleshooting Technical Bulletin [LIT-12011238]

 

for more information).

Table 6:  LED Status indication

Flash Rate

Status LED Indication

LED Off

No database configuration is loaded, or no 
input power is present.

1 Flash

Terminal mode has been invoked (Switch 
T is on).

2 Flashes

An equipment to E-Link communications 
error has occurred.

3 Flashes

A Quick Start has a configuration error.

LED On

No errors with custom/field modified 
application.

Flashing 
Continuously

No errors with factory standard 
application.

Table 7:  E-Link Releases

Firmware/Database Revision

Point Lists

SSM4567 JCF0003BL.BIN

J and earlier only

SSM4567 JCF0008BL.BIN

J and earlier, or K

Содержание E-Link

Страница 1: ...Gateway circuit board a transformer is included inside the enclosure that converts a 120 or 240 volt input to 24 VAC power North American Emissions Compliance United States Canada Installation The E...

Страница 2: ...YLPA 031 01095 YORK Talk 2 4 800 bps YCAS YCWS YCRS 031 02478 YORK Talk 2 4 800 bps YCAV YCIV YVAA 031 01065 YORK Talk 2 1 200 bps YIA YPC YG YB 031 01730 YORK Talk 3 YN OM RETROFITS CR 031 02430 YORK...

Страница 3: ...re jumper JP27 is set for RS 232 see Figure 20 6 Connect the power harness included with the kit from J2 on the E Link Gateway to J21 on the Optiview Micro Panel see Figure 20 The E Link Gateway is no...

Страница 4: ...ground screw The E Link Gateway is now ready to be configured using Quick Start see the Commissioning a Standard Application section in this document Micro Board 24 VAC Transformer Expansion Nut Expa...

Страница 5: ...ateway enclosure to the Micro Panel 6 Complete wiring as described in the Applying Power section in this document Note Use of bulkhead pipe couplers provides sufficient clearance to allow removal of t...

Страница 6: ...e metal of both enclosures Scraping the paint around the knockouts usually helps provide a better electrical connection between the joining parts 1 Connect a 1 29 1 02 mm 16 18 AWG wire from a reliabl...

Страница 7: ...to the Johnson Controls Portal Products and Services Delivery Products Service Field Support Equipment Integration YORK Equipment Data Maps 3 Press hold a few seconds then release the push button show...

Страница 8: ...1 through 16 all use the J version point lists whereas Quick Starts 17 through 33 use the K version The primary difference between the two categories is that Quick Starts 1 through 16 have limited net...

Страница 9: ...IPU I 17 0 1 0 0 0 1 YK with SSS Imperial YORK Talk III K version points 18 0 1 0 0 1 0 YK with VSD Imperial YORK Talk III K version points 19 0 1 0 0 1 1 YT with SSS Imperial YORK Talk III K version...

Страница 10: ...600 N 8 1 Terminal 4 2 5 0 1 0 0 N2 9 600 N 8 1 MS TP 38 400 N 8 1 Terminal 5 2 5 0 1 0 1 Modbus 19 200 N 8 1 MS TP 38 400 N 8 1 Terminal 6 2 5 0 1 1 0 Modbus 19 200 N 8 2 MS TP 38 400 N 8 1 Terminal...

Страница 11: ...nzorbs on each RS 485 port to protect against damaging electrical spikes and stray voltage The equipment panel should also be equipped with protection against electrical disturbances Whereas OptiView...

Страница 12: ...ctivity RS 485 The RS 485 standard uses three conductors to connect network nodes two signal wires and a reference The E Link Gateway uses either a third wire for the reference or the building s infra...

Страница 13: ...ch setting 1 Since the E Link Gateway uses a one to one relationship with the chiller panel this switch is normally set to 0 YORK Talk address 1 However in a master slave configuration set the master...

Страница 14: ...itude POWER HARNESS Latitude 3 8 in Screw 8 x 32 OptiView 2 Position Connector 4 Position Connector 4 Position Connector 4 Position Connector Screw Tap Thread M4 x 32 mm Latitude FIG OptiVwKt YMC2 COM...

Страница 15: ...Transformer Primary Power Wiring Harness Communication Wiring Harness Resistor Secondary Power Wiring Harness Tie Wrap FIG IPUII Kt Figure 15 E Link IPU II Panel Installation Kit YK ELNKSTK 0 Contents...

Страница 16: ...is dated after 11 2000 the chiller ID is software selectable through the micro panel SHIELD BLUE WHITE Open 031 02050 000 TB1 TB6 NOTE The chiller ID is software selectable through the micro panel ke...

Страница 17: ...E Link Gateway Installation Instructions 17 Figure 18 E Link Gateway to YORK Talk II Equipment Connections Continued See Table 1 for board cross reference...

Страница 18: ...s in locations U4 and U5 The transfer rate on the chiller must be set to 4800 baud Frick RWBII Plus Jumpers Jumpers RWBII Rev B and Lower RX Jumpers RWBII Rev C and Higher U5 U4 Port 2 Port 1 SHIELD P...

Страница 19: ...lk 3 Rs232 Optiview Microboard 031 01730 XXX SHIELD PORT 2B RS232 TX RX COMSHLD Open E Link E Link 12 VDC SHIELD Open Equipment Cable York Talk 2 RS485 4800 baud SHIELD COM SHLD PORT 2A RS485 Open E L...

Страница 20: ...xxx I O Board 331 02496 101 IPU I Board YPAL ECO2 1 J4 2 3 4 5 P3 P3 GND 5V Equipment Cable BACnet MS TP 38400 baud FIG YPAL YPAL ECO2 Setup for MS TP Bus BLUE WHITE SHIELD GRD COM SHLD PORT 2A RS485...

Страница 21: ...s a pre wired E Link Port 2 Terminal Block RS485 4800 baud SHIELD PORT 2A RS485 Open E Link 031 02550 xxx I O Board 031 02630 xxx IPU II Board T 1 RS485 REF SHLD IPU II P1 Setup for York Talk 2 FIG ST...

Страница 22: ...E Link Gateway Installation Instructions 22 Figure 23 E Link Gateway to Wuxi STC YEWS D1 YEAS YGAS Equipment Connection Fig wuxi_stc...

Страница 23: ...E Link Gateway Installation Instructions 23 Figure 24 E Link Gateway Communication Port Connections to a BAS System...

Страница 24: ...if this connection has not been made elsewhere in the configuration Repair Information If the E Link Gateway fails to operate within its specifications replace the unit For a replacement E Link Gatew...

Страница 25: ...PP Switch Group A 6 Position Dip Switch Port 2A RS485 Equipment Port Supporting BACnet MS TP and YORK Talk II Protocols with Available EOL Termination Switch Port 2B RS232 Equipment Port Supporting YO...

Страница 26: ...Installation Instructions 26 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2011 Johnson Controls Inc Bu...

Отзывы: