E-Link Gateway Installation Instructions
10
Table 9: BAS Output Protocol Quick Start Selections
APP Group
Switch B
Output Protocol Quick Starts
Switch Settings
8
4
2
1
Port 1
Port 3
Port 4
0
1
1.
When making edits to User Report 4 (Port Configuration), Group Application Switch B
must
be set to zero. This setting
ensures that the edits are stored. Otherwise, the edits are overwritten to the default values assigned to the particular Group
Switch B setting the next time E-Link is reset, or power is cycled. Edits made in any other User Reports do not require
alterations to either bank of Group Application switches. For standard set-up, not requiring modifications via User Report 4,
use application switch B, settings 1 to 14.
0
0
0
0
MS/TP, AUTO, N, 8, 1
Modbus, 19,200, N, 8, 1
Terminal
1
2.
The Terminal setting on Port 4 is restricted for factory use only.
To comply with the L
ON
M
ARK
® specification, all data transmitted on the L
ON
W
ORKS
network must be expressed in SI units
(metric units). The L
ON
W
ORKS
ProtoCessor performs no unit conversions; it assumes that the data supplied is already
correctly expressed.
0
0
0
1
MS/TP, AUTO, N, 8, 1
Modbus, 19,200, N, 8, 1
Terminal
2
0
0
1
0
MS/TP, AUTO, N, 8, 1
Modbus, 19,200, N, 8, 2
Terminal
3
0
0
1
1
MS/TP, AUTO, N, 8, 1
N2, 9,600, N, 8, 1
Terminal
4
0
1
0
0
N2, 9,600, N, 8, 1
MS/TP, 38,400, N, 8, 1
Terminal
5
0
1
0
1
Modbus, 19,200, N, 8, 1
MS/TP, 38,400, N, 8, 1
Terminal
6
0
1
1
0
Modbus, 19,200, N, 8, 2
MS/TP, 38,400, N, 8, 1
Terminal
7
0
1
1
1
Modbus, 9,600, E, 8, 1
MS/TP, 38,400, N, 8, 1
Terminal
8
1
0
0
0
Modbus, 9,600, N, 8, 1
MS/TP, 38,400, N, 8, 1
Terminal
9
3.
Use Quick Start 9 and 11 if the equipment is supplying the data in SI units (the E-Link is not required to perform any
conversions, so it operates in pass-through mode).
1
0
0
1
N2, 9,600, N, 8, 1
Modbus, 19,200, N, 8, 1
L
ON
W
ORKS
– Pass through
10
4, 5,
6
4.
Use Quick Start 10 and 12 if the equipment is supplying the data in Imperial units and the E-Link is required to convert these
units into SI.
5.
Setting Switch T = ON, on the MAC address, forces TERMINAL mode of Port 3, at 57,600 baud, N, 8, 1. This setting is only
required to debug the E-Link Gateway’s operation, or access the User Reports.
6.
Select Quick Starts 9 and 10 when connecting the E-Link Gateway to an ECO2 unit.
1
0
1
0
N2, 9,600, N, 8, 1
Modbus, 19,200, N, 8, 1
L
ON
W
ORKS
– Conversion
1
0
1
1
Modbus, 19,200, N, 8, 2
N2, 9,600, N, 8, 1
L
ON
W
ORKS
– Pass through
12
1
1
0
0
Modbus, 19,200, N, 8, 2
N2, 9,600, N, 8, 1
L
ON
W
ORKS
– Conversion
13
1
1
0
1
Modbus, 9,600, E, 8, 1
Modbus, 19,200, N, 8, 2
Terminal
1
1
1
0
MS/TP, 38,400, N, 8, 1
N2, 9,600, N, 8, 1
Terminal
15
7
7.
Quick Starts 15 on APP Group B, and 63 on APP Group A, are reserved for field adjustments.
1
1
1
1
Reserved
Reserved
Terminal