![Johnson Controls E-Link Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/johnson-controls/e-link/e-link_installation-instructions-manual_2024158004.webp)
E-Link Gateway Installation Instructions
4
IPU-II Panel Installation
(Installation Kit Not Available in Europe)
1.
Attach the E-Link Gateway board to the panel in
the upper right side of the enclosure using the four
expansion screws and nuts provided in the IPU-II
Panel Installation Kit (see Figure 3).
2.
Attach the 24 VAC transformer to the panel to the
left of the E-Link board using two screws (see
Figure 3).
3.
Connect the communications cable (included with
the kit) between the E-Link board and IPU-II Micro
board.
4.
Connect the transformer to the terminal block.
5.
Connect the transformer to E-Link. Secure the
wiring with tie-wraps.
6.
Connect the resistor if the RS-485 2-wire operation
is required.
7.
Connect the communications cable shielded
ground to the ground screw.
The E-Link Gateway is now ready to be configured
using Quick Start; see the
section in this document.
Micro Board
24 VAC
Transformer
Expansion
Nut
Expansion
Nut
Screw
Sheet
Metal
Screw
Resistor
Secondary
Power
Wiring
Harness
Tie
Wrap
TB5
TB2
E-LINK
Transformer
Secondary
Ground
Communication
Wiring Harness
Com
Ground
T B 1
T B 5
The Resistor is used for BAS
RS485 2 Wire Connection.
Connect one end of the
Resistor to the COM of
TB5 (24 VAC) and the other
to Port 1 COM.
Use this resistor only if the
BAS wiring utilizes a 2 Wire
communication trunk
Communication Wiring Harness:
Connect to Micro Board
TB1 as Follows:
Wire Color / Terminal
Red / +
Black / -
+
-
REF
SHLD
TB 1 RS485
FI
G
:I
P
U
p
nli
ns
t
Terminal block location
for YCAL-D, YCAL-E, and YLAA.
Terminal block location
for YCAL-C, YCWL, and
Primary Power
Wiring Harness
TB2
TB5
YCUL-C.
Figure 3: IPU-II Panel Installation (Installation Kit Not Available in Europe)