3
Condensate
P
ipes
Level Instrument
Air Intake
Air Supply
B
A
B
Enlarged View
Condensate
P
ipe
As the inside of the unit is in the negative
pressure status, it is required to set up a
backwater elbow. The requirement is:
A=B
≥
(0.145P/10000+20)/25.4(inch)
P is the absolute pressure inside the unit.
The unit of the pressure is psig.
Figure 3-1-5
2
.1.4 Dimension Data
For the units: 18k
For the units: 24k~42k