54
P6 Drive-to-main-control communication error
Lc Compressor Startup Failure
Lc is displayed on
the wired controller
Lc is displayed in
the mainboard 88
indicating
l
ight
Replace the
mainboard. Does it
work normally?
Replace the
compressor
Work
s
normally
Yes
No
P5 Compressor current protection
H7 Compressor motor desynchronizing
H5 IPM protection
Ld Phase loss
P5,
H7,
H5
or
Ld
is
displayed
in
the
mainboard
88
indicating
l
ight
Is the compressor
phase sequence right?
Yes
Replace the mainboard.
Does it work normally
˛
No
Replace the compressor
Work normally
Yes
adjust the
compressor
phase sequence
Is the compressor wire
terminals tightened
˛
Tighten the
compressor wire
terminals
Yes
No
No
P5,
H7,
H5
or
Ld
is
displayed
on
wired zone
controller