5
2
.1.5 Installation Clearance Data
2500mm
(98-3/8inch)
Nut with
Washer
Nut Spring
Washer
G
250mm
(9-7/8inch)
G
250mm
(9-7/8inch)
Figure 3-1-7
Warning! The height of installation for the indoor unit should be 2.5m (8-1/5ft) above.
2
.1.6
Condensate
Piping Work
Installation of
Condensate
Pipeline:
Install the
condensate
hose in accordance with the instructions in this installation manual and keep the a
rea warm
enough to prevent condensation. Problems with the piping may lead to water leaks.
(1) (Install the
condensate
hose with downward gradient (1/50 to 1/100) and no risers or traps are
used for
the hose (Figure 3-1-8).
(2) Be sure there is no crack or leak on the
condensate
hose to avoid the formation of air pocket
s
(Figure
3-1-8).
(3) When the hose is long, install supporters (Figure 3-1-9).
(4) Always use the
condensate
hose which has been insulated properly.
Condensate
hose
Arrange the
condensate
hose
lower than this
drain port
Trap
Air bleeding
Rise
√
Figure 3-1-8