24
(8) Connection of drainage branch pipe to the standpipe or horizontal pipe of drainage main pipe.
(9) The horizontal pipe cannot be connected to the vertical pipe at a same height. It can be connected
in a manner as shown below:
NO.1: Attach the 3-way connection of the
condensate
pipe joint as shown in Figure 3-1-55.
NO.2: Attach the drain elbow as shown in Figure 3-1-56.
NO.3: Attach the horizontal pipe as shown in Figure 3-1-57.
3-way connection of
condensate
pipe joint
Connection of drain elbow
Connection of horizontal pipe
Figure 3-1-55
Figure 3-1-56
Figure 3-1-57
2
.3.10 Precautions When Doing Riser Piping Work
(1) Make sure that heat insulation work is executed on the following
two
spots to prevent any possible
water leakage due to condensation.
1) Connect the
condensate
hose to the drain lift pipe, and insulate them.
2) Connect the
condensate
hose to the drain outlet on the indoor unit, and tighten it with the clamp.
Figure 3-1-58
(2) Make sure the lift pipe is at most 280mm (11inch).
(3) Stand the lift pipe vertically, and make sure it is not further than 300mm (11-3/4inch) from the
base of the drain outlet.
(4)
Secure a downward gradient of 1/100 or more for the drain pipe. To accomplish this
,
mount
supporting brackets at an interval of 1~1.5m (3-2/7~5feet).
Содержание DHR18CSB21S
Страница 44: ...36 Cassette Type Unit Single phase units 18k Single phase units 24k 30k Single phase units 36k 42k ...
Страница 64: ...56 H6 DC fan error ...
Страница 73: ...65 Model DHR24CSB21S Model DHR30CSB21S ...
Страница 74: ...66 Model DHR36CSB21S Model DHR42CSB21S ...
Страница 77: ...69 8 2 3 Cassette Type Model DHR18NKB21S Model DHR24NKB21S DHR30NKB21S DHR36NKB21S DHR42NKB21S ...
Страница 78: ...70 Model DHR48NKB21S ...
Страница 79: ...71 ...