Table 32: SEC parameters for DSV180C–300C units with discrete speeds evaporator fan
Menu/sub-menu
Parameter
Factory value
Standard
T-Stat Only
Yes
# Refrig Sys
2
Commission
Options
# Ht Pump Stgs
0
Occ Mode
1
External
OCC
Off Dur Unocc
No
Clg-En
Yes
# Clg Stgs
4
C1-En
Yes
C2-En
Yes
C3-En
Yes
C4-En
Yes
Low Amb-En
2
No
Lead Lag-En
3
No
Clg OAT Cutout-En
Yes
Clg OAT Cutout
45
SAT Cool Limit-En
Yes
Sat Cool Limit-SP
45
Cooling
Freeze-SP
26
Htg-En
4
No
Heating
# Htg Stgs
0
Fan Ctl-Type
Fixed Variable
Fan On Occ
No
Fan On Dly Cool
0
Fan Off Dly Cool
30
Fan Only % Cmd
0
1 Clg Stg -% Cmd
50
2 Clg Stg -% Cmd
60
3 Clg Stg -% Cmd
75
Details
Fan
Setup
4 Clg Stg -% Cmd
100
Note:
1. Factory shipped units equipped with Occ jumper on UCB
2. Do not enable low ambient
3. Do not enable LeadLag
4. Field supplied option
D-Series Vertical (DSV060C-300C) Air-Cooled Self-Contained Units, C Generation with Smart Equipment Controller
86
Johnson Controls