Table 4: Oversized evaporator motor electrical data
Compressor #1
Compressor #2
Evaporator
fan
Condenser
fan
Model #
Voltage
Qty
RLA
LRA
Qty
RLA
LRA
Hp
FLA
Hp
FLA
MCA
Max
fuse/
CCT.
bkr.
amp
DSV120C4 460/3/60
1
@
7.2
52.0
1
@
7.8
52.0
2.00
2.9
3.00
4.2
23.20
30
DSV120C5 575/3/60
1
@
5.7
43.08
1
@
5.7
38.9
2.00
2.3
3.00
3.4
17.43
20
DSV144C2
208–
230/3/60
1
@
17.6 136.0
1
@
19.0 123.0 3.00
8.5
3.00
8.5
58.00
70
DSV144C4 460/3/60
1
@
8.5
66.1
1
@
9.7
62.0
3.00
4.2
3.00
4.2
28.73
35
DSV144C5 575/3/60
1
@
6.3
55.3
1
@
7.4
50.0
3.00
3.4
3.00
3.4
22.08
25
DSV180C2
208–
230/3/60
2
@
25.3 184.0
5.00
14.0
5.00
14.0 84.93 110
DSV180C4 460/3/60
2
@
9.6
84.0
5.00
6.6
5.00
6.6
34.80
40
DSV180C5 575/3/60
2
@
8.4
60.0
5.00
5.3
5.00
5.3
29.50
35
DSV240C2
208–
230/3/60
2
@
32.6 240.0
7.50
20.4
7.50
20.4 114.15 125
DSV240C4 460/3/60
2
@
14.8 130.0
7.50
9.7
7.50
9.7
52.70
60
DSV240C5 575/3/60
2
@
11.1
93.7
7.50
7.8
7.50
7.8
40.58
50
DSV300C2 208-230/3/
60
2
@
35.4 240.0
7.50
20.4 10.00 25.0 125.05 150
DSV300C4 460/3/60
2
@
16.5 140.0
7.50
9.7
10.00 12.5 59.33
70
DSV300C5 575/3/60
2
@
12.9 107.6
7.50
7.8
10.00 10.0 46.83
50
31
D-Series Vertical (DSV060C-300C) Air-Cooled Self-Contained Units, C Generation with Smart Equipment Controller
Johnson Controls