Figure 9: Double front grille discharge plenum
Figure 10: Single front grille discharge plenum
Low ambient damper installation
If the unit must operate at an outdoor ambient below 50.0°F, install the optional low ambient
damper kit. This kit maintains an acceptable condensing pressure. Install the damper directly
onto the intake duct connection (see Figure 11). Determine the damper position by the refrigerant
pressure. Depending on a proportional pressure control module's output signal, a direct-coupled
electric damper actuator motor drives the damper open or closed.
A pressure transducer senses the high-side refrigerant pressure through a service access port.
The port is located on the liquid refrigerant line leaving the condenser. The pressure controller,
complete with terminal connection blocks for wiring, attaches to a fieldinstalled mounting bracket.