Rigging
WARNING
Prior to mounting unit, check individual unit weights (Table 1 ) and verify lifting capacity of lifting
equipment exceeds weight of units by safe margins. Failure to do so may result in unit damage,
personal injury, or even death.
To ensure safe installation of the unit, ensure the base of the unit is continuously supported.
WARNING
Determine the actual center of gravity of the unit by performing a test lift. Lifting an unbalanced unit
can cause personal injury, or even death.
Installation site
CAUTION
Lock all electrical power supply switches in the OFF position before installing the unit. Failure to
disconnect the power supply may result in electrical shock or even death.
Location
To ensure the unit operates at maximum efficiencies, choose a dry indoor area where the
temperature is controlled between 50.0°F and 115.0°F. When choosing a location to install the
unit, consider the surrounding area. Occupants may object to common vibration and sound levels
associated with the unit.
WARNING
Failure to allow adequate space between units, condenser intake and discharge may result in poor unit
performance and possible unit failure.
Install thermostats, air supplies, and returns so that each unit operates only on an individual unit
control. To assure fast drainage of the condensate run-off, the unit can be slightly pitched in the
same direction as the drain pan outlet.
Unit
Operating weight
(condenser only)
Shipping weight
(condenser only)
DSV060C
920 (620)
980 (675)
DSV096C
1240 (810)
1290 (865)
DSV120C
1325 (860)
1385 (915)
11