OPTIONAL PARTS
3-20
TC-18004-rev.2
3.6 Duct Adapter: PD-100
Unit: inch [mm]
Installation State
Specifications
Model
Item
PD-100
Applicable Indoor Unit Model
((H,Y,C)ICS**B21S)
MBH
015 to 036
Max. Capacity of
Fresh Air Intake
cfm
(m
3
/min.)
35
(1)
Purpose
for Fresh Air Intake
Connecting Duct Diameter
inch (mm)
f
3-15/16
(f
100.0)
Material
ABS Resin (UL94V-0)
NOTES:
1. The maximum capacity for fresh air intake is shown above. Do not exceed the limit amount. (Doing so
could cause condensation.)
2. Do not install the unit where abnormal odors are in the atmosphere.
3. The duct adapter provides a maximum quantity of fresh air intake of approximately 18cfm (0.5m
3
/min)
(for 3.3 ft. (1m) straight pipe duct). When more fresh air intake is required, be sure to install the dedicated
outside air system. In this case, do not utilize the dedicated outside air system.
4. Insulate the duct and the duct connection to prevent air leakage and condensation.
The duct and insulation materials should be nonflammable.
5. Refer to the “Installation Manual for Duct Adapter” for more details.
Decorative Panel
Содержание CICS015B21S
Страница 2: ......
Страница 17: ...CEILING SUSPENDED TC 18004 rev 2 2 3 2 4 Dimensional Data Model H Y C ICS015B21S Unit inch mm ...
Страница 18: ...CEILING SUSPENDED 2 4 TC 18004 rev 2 Unit inch mm Model H Y C ICS024B21S ...
Страница 19: ...CEILING SUSPENDED TC 18004 rev 2 2 5 Models H Y C ICS030B21S and H Y C ICS036B21S Unit inch mm ...
Страница 34: ......
Страница 60: ......
Страница 66: ...Annex 4 2 Way Cassette Type Indoor Unit Models H Y C IC2018B21S and H Y C IC2024B21S ...
Страница 72: ... 2018 Johnson Controls Inc TC 18004 rev 2 Code No LIT 12013004 Revised September 2019 ...