Setting of Fan Speed
● Select the function selection mode from the wired controller and set the high speed mode to “High Speed 1”
before attaching the air filter (optional).
● When using this air filter (optional), the airflow volume of “High 2” will be equal to “High”.
● The standard airflow volume will be valid during the heating Thermo-OFF. If the high speed mode is
required, set “Hi Speed at Heating Thermo-OFF” from the wired controller.
● The setting details of the wired controller should be referred to in the “Installation Manual” for the wired
controller.
Liquid Crystal Display
(LCD)
of Wired Controller
(CIW01)
Setting of “High Speed 1”
Setting of “Hi Speed
at Heating Thermo-OFF”
OK
Function Selection:01-03
04
23
C2
--
C3
00
C4
00
C5
01
C6
00
Item
Setting
/
Adj.
Entr
Rtrn
Sel.
“High Speed Mode”
High Speed 1: 01
High Speed 2: 02
Back
Back
OK
Function Selection:01-03
04
23
C2
--
C3
00
C4
00
C5
00
C6
01
Item
Setting
/
Adj.
Entr
Rtrn
Sel.
“Available”
“Hi Speed at
Heating Thermo-OFF”
Back
Back
1
Open the air inlet grille for the filter box (optional).
2
Check the fixed position of the support attached to the side rail and central rail. The fixed position of the
support before shipping should be as in the figure above and is unnecessary to adjust. Loosen the screw
if it is necessary, but do not remove.
3
Secure the air filter (optional) by pushing the filter to the filter box frame and rotating the filter holder on
the central rail 90° after attaching to the indoor unit.
Insert the air filter (optional) into the filter box while paying attention to the “AIR FLOW” direction on the
air filter (optional) so it isn’t upside down.
4
Close the air inlet grille tightly and securely. Refer to the “Installation Manual” for the filter box (optional)
if the air inlet grille fails to close.
NOTE:
Reposition the filter holder to the position before shipping when removing the air filter (optional).
Install the air filters (optional) one at a time. Otherwise, they may fall and cause injury and breakage if
installing two filters simultaneously.
Attaching Air Filter (Optional) to Indoor Unit
A
A
Air Filter
(Optional)
Air Inlet Grille
Filter Box
(Optional)
Side Panel
Indoor Unit
AIR
FLOW
AIR
FLOW
3-1/8 inches
(80mm)
90°
Side Panel
Screw
Support
Side Rail
Filter Holder
Cross Section A-A (View from the Front)
Central Rail
Support
Air Filter
(Optional)
Air Inlet Grille
Insert the air filter (optional) at the side rail.
Then push the other side up.
Side Rail
Support
Fixed Position of the Support
Fix the support
at the top of the
elliptical hole.
Install the air filter (optional) according to the following procedures
1
to
4
.
Содержание CICS015B21S
Страница 2: ......
Страница 17: ...CEILING SUSPENDED TC 18004 rev 2 2 3 2 4 Dimensional Data Model H Y C ICS015B21S Unit inch mm ...
Страница 18: ...CEILING SUSPENDED 2 4 TC 18004 rev 2 Unit inch mm Model H Y C ICS024B21S ...
Страница 19: ...CEILING SUSPENDED TC 18004 rev 2 2 5 Models H Y C ICS030B21S and H Y C ICS036B21S Unit inch mm ...
Страница 34: ......
Страница 60: ......
Страница 66: ...Annex 4 2 Way Cassette Type Indoor Unit Models H Y C IC2018B21S and H Y C IC2024B21S ...
Страница 72: ... 2018 Johnson Controls Inc TC 18004 rev 2 Code No LIT 12013004 Revised September 2019 ...