8

    A419ABG-3 Electronic Temperature Control Installation Instructions

Repairs and Replacement

Do not attempt to repair or recalibrate the
A419 temperature control. In case of a defective or
improperly functioning control, contact your nearest
Authorized Johnson Controls/PENN distributor or
sales representative.

When contacting your Johnson Controls/PENN
distributor, have the model number of the control
available. This number can be found on the label
inside the cover of the control.

Ordering Information

Refer to Table 6 to order sensors, mounting hardware
and other accessories used to install A419 controls.
Contact your nearest Johnson Controls/PENN
distributor or sales representative to order these
products.

Table 6: A419 Controls Accessories

Product Code Number

Description

A99BB-200

Temperature Sensor

: PTC Sensor with 6-1/2 ft (2 m) Non-shielded 2-Wire Lead

BKT287-1R

DIN Rail

: 12 in. (305 mm) long

BKT287-2R

DIN Rail

: 36 in. (914 mm) long

PLT344-1R

End Clamps for DIN Rail Mounting

CLK350-2C

7-Day Programmable Digital Clock

 for activating Binary Offset

WEL11A-601C

Immersion Well

 for Mounting Sensor in Liquid Applications

Technical Specifications

Product

A419ABG-3C Electronic Temperature Control

Setpoint Range

-30 to 212

°

F (-34 to 100

°

C)

Differential Range

1 to 30F

°

 (1 to 30C

°

)

Supply Voltage

120 VAC, 60 Hz

Power Consumption

1.8 VA Maximum

SPST Output Relay

Contacts Electrical

Ratings

Full Load Amperes N.O.:

12 A

Locked Rotor Amperes N.O. : 

72 A

Non-inductive Amperes N.O.: 

10 A

Pilot Duty:

125 VA @ 120 VAC

Sensor Type

PTC Sensor with 6.6 ft (2.0 m) leads

Control Ambient

Temperature

Operating:

-30 to 140

°

F (-34 to 60

°

C)

Shipping:

-40 to 185

°

F (-40 to 85

°

C)

Ambient Humidity

0 to 95% RH Noncondensing; Maximum Dew Point: 85

°

F (29

°

C)

Control Enclosure Material

Case and Cover:

NEMA 1 - High-Impact Thermoplastic

Agency Listings

UL: File E27734; CCN’s XAPX (US), XAPX7 (Canada)
FCC: CFR 47, Part 15, Class A. DOC, Class A

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, contact Application Engineering at 1-800-275-5676. Johnson Controls, Inc. shall not be liable for damages resulting from
misapplication or misuse of its products.

Controls Group

507 E. Michigan Street
P.O. Box 423

Published in U.S.A.

Milwaukee, WI  53201

www.johnsoncontrols.com

Содержание A419ABG-3C

Страница 1: ...lity and electronic accuracy in a Type NEMA 1 high impact plastic enclosure suitable for surface or DIN rail mounting The temperature sensor supplied with the control is interchangeable with compatible Johnson Controls PENN A99 temperature sensors FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules Thes...

Страница 2: ...the sensor to the A419 control Wire insulation rating must be 90 C minimum Temperature sensor signals may be affected by electrical interference When extending sensor cable beyond 50 ft 15 2 m use a twisted pair shielded cable to reduce electrical interference A99 temperature sensors are not polarity sensitive Wire the leads to SEN and COM on the sensor terminal block TB3 See Figure 2 Keep the lea...

Страница 3: ...h IMPORTANT To ensure that the output relay operates as intended verify that all three of the jumpers are positioned properly for the application before powering the A419 control IMPORTANT The touchpad cannot be unlocked without a jumper installed across the P5 jumper pins Do not discard jumpers in case they are required in the future See Figure 4 and Figure 5 Positioning the Jumpers The P5 jumper...

Страница 4: ...blishes the minimum time that the output relay remains de energized before the next on cycle The ASd does not allow the output relay to re energize until the programmed time delay has elapsed The delay is activated when the control is first turned on and every time an on cycle ends When the delay is activated the LCD alternately flashes the sensor temperature and ASd The Anti short Cycle Delay ran...

Страница 5: ...ure If no setup entry is made for 30 seconds the control reverts to the normal temperature display IMPORTANT If MENU is not pressed after changing the setpoint value the control reverts to the previously programmed setpoint value MENU F BIN MENU Button DOWN Arrow Button UP Arrow Button Output Relay Status Indicator LED Operating Mode Indicator Temperature Units Indicator Temperature Offset Indicat...

Страница 6: ... Electrical Shock Do not touch any exposed metal parts with anything other than properly insulated tools or insulated probes of the digital voltage meter Failure to use properly insulated tools and probes may result in severe personal injuries or death If the control system does not function properly verify that the control is wired and set up properly If the problem persists use the following pro...

Страница 7: ...dicated in Figure 7 replace the A419 control i If proper operation of the A419 control is verified reconnect the load and consult the equipment manufacturer s instructions for troubleshooting the controlled equipment Fault Codes If the LCD displays an alarm or fault code SF or EE consult Table 5 for explanation Table 4 A419 Output Relay Operation in Different Operating Modes Setpoint Mode Operatin...

Страница 8: ...set WEL11A 601C Immersion Well for Mounting Sensor in Liquid Applications Technical Specifications Product A419ABG 3C Electronic Temperature Control Setpoint Range 30 to 212 F 34 to 100 C Differential Range 1 to 30F 1 to 30C Supply Voltage 120 VAC 60 Hz Power Consumption 1 8 VA Maximum SPST Output Relay Contacts Electrical Ratings Full Load Amperes N O 12 A Locked Rotor Amperes N O 72 A Non induct...

Отзывы: