A419ABG-3 Electronic Temperature Control Installation Instructions    

3

Not

Used

Male
Plug

Female
Receptacle

AC

COM

NO

TB2

Not

Used

120

C

TB1

Figure 3: Factory Power Wiring

Setup and Adjustments

!

  WARNING: Risk of Electrical Shock

Disconnect each of multiple power supplies before
making electrical connections. More than one
disconnect may be required to completely de-
energize equipment. Contact with components
carrying hazardous voltage can cause electrical
shock and may result in severe personal injury or
death.

IMPORTANT:

To ensure that the output relay

operates as intended, verify that all three of the
jumpers are positioned properly for the application
before powering the A419 control.

IMPORTANT:

The touchpad cannot be

unlocked without a jumper installed across the
P5 jumper pins. Do not discard jumpers in case they
are required in the future. See 

Figure 4

 and

Figure 5

.

Positioning the Jumpers

The 

P5 jumper 

position determines if the touchpad is

locked or unlocked.

The 

P4 jumper 

pin block has two pairs of jumper pins.

The top pair of pins (JUMP1) determines if the control
is set for Heating or Cooling mode. The bottom pair of
pins, (JUMP2) establishes whether Setpoint is at cut-in
or at cutout. See Table 2 and Figure 5.

Содержание A419ABG-3C

Страница 1: ...lity and electronic accuracy in a Type NEMA 1 high impact plastic enclosure suitable for surface or DIN rail mounting The temperature sensor supplied with the control is interchangeable with compatible Johnson Controls PENN A99 temperature sensors FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules Thes...

Страница 2: ...the sensor to the A419 control Wire insulation rating must be 90 C minimum Temperature sensor signals may be affected by electrical interference When extending sensor cable beyond 50 ft 15 2 m use a twisted pair shielded cable to reduce electrical interference A99 temperature sensors are not polarity sensitive Wire the leads to SEN and COM on the sensor terminal block TB3 See Figure 2 Keep the lea...

Страница 3: ...h IMPORTANT To ensure that the output relay operates as intended verify that all three of the jumpers are positioned properly for the application before powering the A419 control IMPORTANT The touchpad cannot be unlocked without a jumper installed across the P5 jumper pins Do not discard jumpers in case they are required in the future See Figure 4 and Figure 5 Positioning the Jumpers The P5 jumper...

Страница 4: ...blishes the minimum time that the output relay remains de energized before the next on cycle The ASd does not allow the output relay to re energize until the programmed time delay has elapsed The delay is activated when the control is first turned on and every time an on cycle ends When the delay is activated the LCD alternately flashes the sensor temperature and ASd The Anti short Cycle Delay ran...

Страница 5: ...ure If no setup entry is made for 30 seconds the control reverts to the normal temperature display IMPORTANT If MENU is not pressed after changing the setpoint value the control reverts to the previously programmed setpoint value MENU F BIN MENU Button DOWN Arrow Button UP Arrow Button Output Relay Status Indicator LED Operating Mode Indicator Temperature Units Indicator Temperature Offset Indicat...

Страница 6: ... Electrical Shock Do not touch any exposed metal parts with anything other than properly insulated tools or insulated probes of the digital voltage meter Failure to use properly insulated tools and probes may result in severe personal injuries or death If the control system does not function properly verify that the control is wired and set up properly If the problem persists use the following pro...

Страница 7: ...dicated in Figure 7 replace the A419 control i If proper operation of the A419 control is verified reconnect the load and consult the equipment manufacturer s instructions for troubleshooting the controlled equipment Fault Codes If the LCD displays an alarm or fault code SF or EE consult Table 5 for explanation Table 4 A419 Output Relay Operation in Different Operating Modes Setpoint Mode Operatin...

Страница 8: ...set WEL11A 601C Immersion Well for Mounting Sensor in Liquid Applications Technical Specifications Product A419ABG 3C Electronic Temperature Control Setpoint Range 30 to 212 F 34 to 100 C Differential Range 1 to 30F 1 to 30C Supply Voltage 120 VAC 60 Hz Power Consumption 1 8 VA Maximum SPST Output Relay Contacts Electrical Ratings Full Load Amperes N O 12 A Locked Rotor Amperes N O 72 A Non induct...

Отзывы: