A419ABG-3 Electronic Temperature Control Installation Instructions    

7

-40

-20

0

20

40

60

80

100

120

140

160

180

200

220

240

260

500 700 900 1100 1300 1500 1700 1900 2100

Resistance in Ohms

Temperature (°F)

-40

-20

0

20

40

60

80

100

120

Temperature (°C)

Figure 7: Temperature vs. Sensor Resistance

3. 

Check the A419 for proper operation.

Note: 

Perform 

Troubleshooting

 Steps 1 and 2 before

performing this step.

a.  Disconnect the load from the output relay

terminals.

b.  Ensure that the Touchpad Lock jumper is

installed, so that the touchpad is unlocked.

c.  Reconnect the sensor leads and supply

power to the control.

d.  Replace the cover.

e.  Check the control settings for proper values.

f. 

Press and hold MENU until Setpoint
appears. (This takes about 2 seconds.)

g. Press 

the 

Up

 and 

Down

 (arrows) to change

the Setpoint temperature above and below
the sensor temperature until the relay
energizes and de-energizes as shown in
Figure 7.

Note: 

If the anti-short cycle delay has a set

delay-time value greater than 0 minutes when the
control is powered On, the relay does not energize
until the time delay has elapsed.

h.  If the output relay does 

not

 perform as

indicated in Figure 7, replace the A419 control.

i.  If proper operation of the A419 control is

verified, reconnect the load and consult the
equipment manufacturer’s instructions for
troubleshooting the controlled equipment.

Fault Codes

If the LCD displays an alarm or fault code (

SF

 or 

EE

),

consult Table 5 for explanation.

Table 4: A419 Output Relay Operation in Different Operating Modes

Setpoint
Mode

Operating
Mode

Output Relay Is Energized (closing
the NO and COM contacts) at…

Output Relay Is De-Energized (opening
the NO and COM contacts) at…

Cooling

Setpoint plus differential

Setpoint

Cutout

Heating

Setpoint minus differential

Setpoint

Cooling

Setpoint

Setpoint minus differential

Cut-in

Heating

Setpoint

Setpoint plus differential

Table 5: Fault Codes Defined

Fault Code

Definition

System Status

Solution

SF

flashing alternately

with 

OP

Open temperature
sensor or sensor wiring

Output functions according to
the selected sensor failure mode
(SF setting)

See 

Troubleshooting

 section.

Cycle power to reset the control.

SF

flashing alternately

with 

SH

Shorted temperature
sensor or sensor wiring

Output functions according to
the selected sensor failure mode
(SF setting)

See 

Troubleshooting

 section.

Cycle power to reset the control.

EE

Program failure

Output is off

Reset the control by pressing

MENU

. If problems persist, replace

the control.

Содержание A419ABG-3C

Страница 1: ...lity and electronic accuracy in a Type NEMA 1 high impact plastic enclosure suitable for surface or DIN rail mounting The temperature sensor supplied with the control is interchangeable with compatible Johnson Controls PENN A99 temperature sensors FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules Thes...

Страница 2: ...the sensor to the A419 control Wire insulation rating must be 90 C minimum Temperature sensor signals may be affected by electrical interference When extending sensor cable beyond 50 ft 15 2 m use a twisted pair shielded cable to reduce electrical interference A99 temperature sensors are not polarity sensitive Wire the leads to SEN and COM on the sensor terminal block TB3 See Figure 2 Keep the lea...

Страница 3: ...h IMPORTANT To ensure that the output relay operates as intended verify that all three of the jumpers are positioned properly for the application before powering the A419 control IMPORTANT The touchpad cannot be unlocked without a jumper installed across the P5 jumper pins Do not discard jumpers in case they are required in the future See Figure 4 and Figure 5 Positioning the Jumpers The P5 jumper...

Страница 4: ...blishes the minimum time that the output relay remains de energized before the next on cycle The ASd does not allow the output relay to re energize until the programmed time delay has elapsed The delay is activated when the control is first turned on and every time an on cycle ends When the delay is activated the LCD alternately flashes the sensor temperature and ASd The Anti short Cycle Delay ran...

Страница 5: ...ure If no setup entry is made for 30 seconds the control reverts to the normal temperature display IMPORTANT If MENU is not pressed after changing the setpoint value the control reverts to the previously programmed setpoint value MENU F BIN MENU Button DOWN Arrow Button UP Arrow Button Output Relay Status Indicator LED Operating Mode Indicator Temperature Units Indicator Temperature Offset Indicat...

Страница 6: ... Electrical Shock Do not touch any exposed metal parts with anything other than properly insulated tools or insulated probes of the digital voltage meter Failure to use properly insulated tools and probes may result in severe personal injuries or death If the control system does not function properly verify that the control is wired and set up properly If the problem persists use the following pro...

Страница 7: ...dicated in Figure 7 replace the A419 control i If proper operation of the A419 control is verified reconnect the load and consult the equipment manufacturer s instructions for troubleshooting the controlled equipment Fault Codes If the LCD displays an alarm or fault code SF or EE consult Table 5 for explanation Table 4 A419 Output Relay Operation in Different Operating Modes Setpoint Mode Operatin...

Страница 8: ...set WEL11A 601C Immersion Well for Mounting Sensor in Liquid Applications Technical Specifications Product A419ABG 3C Electronic Temperature Control Setpoint Range 30 to 212 F 34 to 100 C Differential Range 1 to 30F 1 to 30C Supply Voltage 120 VAC 60 Hz Power Consumption 1 8 VA Maximum SPST Output Relay Contacts Electrical Ratings Full Load Amperes N O 12 A Locked Rotor Amperes N O 72 A Non induct...

Отзывы: