    A419ABG-3 Electronic Temperature Control Installation Instructions

Setting the Other A419 Control Functions

To set the Differential, Anti-short Cycle Delay,
Temperature Offset, or Sensor Failure operation, use
the following method:

1.  Press and hold MENU until the display changes to

flashing SP. (This takes about 2 seconds.)

2.  Press Up or Down (arrows) repeatedly until the

desired function is displayed. (See Figure 6.)

3.  Press MENU to display the function’s current

value.

4.  Press Up or Down (arrows) until the desired value

is displayed.

5.  Press MENU to save the new value. The display

returns to the sensor temperature.

IMPORTANT:

If MENU is not pressed after

changing the settings, the new settings are not
saved and the control reverts to the previously
programmed setting values.

Note: 

If no setup entry is made for 30 seconds, the

control reverts to the (normal) temperature display.

Note: 

Any saved A419 control settings are

non-volatile

 and remain in the control’s memory

during power interruptions.

IMPORTANT:

Do not set Setpoint and

Differential values which (when totaled) fall out of
A419 control’s Setpoint range (-30 to 212°F
[-34 to 100°C]). The control will not function properly
if Cut-in or Cutout values are outside of the control’s
Setpoint range.

Checkout

Before applying power, make sure installation and wire
connections are correct for your application. Then
power, operate, and observe the system and A419
control for at least three complete operating cycles
before leaving the installation.

Troubleshooting

!

  WARNING: Risk of Electrical Shock.

Do not touch any exposed metal parts with anything
other than properly insulated tools or insulated
probes of the digital voltage meter. Failure to use
properly insulated tools and probes may result in
severe personal injuries or death.

If the control system does not function properly, verify
that the control is wired, and set up properly. If the
problem persists, use the following procedures to
determine the cause of the problem:

IMPORTANT:

Follow these troubleshooting

procedures in the order presented. Do not skip any
of the steps in the procedures.

1. 

Check for proper voltage to the A419 control.

a.  Remove the cover by loosening the four

captive cover screws.

b.  Use a reliable AC voltmeter to check the

voltage between the 

COM

 and 

120V

 terminals

on terminal block 

TB1

. Refer to Figure 2.

c.  The voltage must be between 102 and

132 VAC for 120 VAC applications.

d.  If the voltage reading is not within the required

range, check the power source and input
power wires for problems.

2. 

Check for proper sensor operation.

a.  Disconnect all power sources to control.

b.  Using an accurate thermometer, take a

temperature reading at the sensor location.

c.  Disconnect the sensor from the control.

d.  Using an ohmmeter, measure the resistance

across the two sensor leads while the sensor
is at the temperature taken in Step 2b.

e.  Consult Figure 7 to verify that the measured

temperature and resistance conform to
established temperature and resistance
values.

f. 

If the measured values conform to the values
in Figure 7, proceed to Step 3.

g.  If the sensor’s measured resistance value is

substantially different from the expected
value for that temperature, check the sensor
wiring. If sensor wiring is okay, replace the
sensor.

Содержание A419ABG-3C

Страница 1: ...lity and electronic accuracy in a Type NEMA 1 high impact plastic enclosure suitable for surface or DIN rail mounting The temperature sensor supplied with the control is interchangeable with compatible Johnson Controls PENN A99 temperature sensors FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules Thes...

Страница 2: ...the sensor to the A419 control Wire insulation rating must be 90 C minimum Temperature sensor signals may be affected by electrical interference When extending sensor cable beyond 50 ft 15 2 m use a twisted pair shielded cable to reduce electrical interference A99 temperature sensors are not polarity sensitive Wire the leads to SEN and COM on the sensor terminal block TB3 See Figure 2 Keep the lea...

Страница 3: ...h IMPORTANT To ensure that the output relay operates as intended verify that all three of the jumpers are positioned properly for the application before powering the A419 control IMPORTANT The touchpad cannot be unlocked without a jumper installed across the P5 jumper pins Do not discard jumpers in case they are required in the future See Figure 4 and Figure 5 Positioning the Jumpers The P5 jumper...

Страница 4: ...blishes the minimum time that the output relay remains de energized before the next on cycle The ASd does not allow the output relay to re energize until the programmed time delay has elapsed The delay is activated when the control is first turned on and every time an on cycle ends When the delay is activated the LCD alternately flashes the sensor temperature and ASd The Anti short Cycle Delay ran...

Страница 5: ...ure If no setup entry is made for 30 seconds the control reverts to the normal temperature display IMPORTANT If MENU is not pressed after changing the setpoint value the control reverts to the previously programmed setpoint value MENU F BIN MENU Button DOWN Arrow Button UP Arrow Button Output Relay Status Indicator LED Operating Mode Indicator Temperature Units Indicator Temperature Offset Indicat...

Страница 6: ... Electrical Shock Do not touch any exposed metal parts with anything other than properly insulated tools or insulated probes of the digital voltage meter Failure to use properly insulated tools and probes may result in severe personal injuries or death If the control system does not function properly verify that the control is wired and set up properly If the problem persists use the following pro...

Страница 7: ...dicated in Figure 7 replace the A419 control i If proper operation of the A419 control is verified reconnect the load and consult the equipment manufacturer s instructions for troubleshooting the controlled equipment Fault Codes If the LCD displays an alarm or fault code SF or EE consult Table 5 for explanation Table 4 A419 Output Relay Operation in Different Operating Modes Setpoint Mode Operatin...

Страница 8: ...set WEL11A 601C Immersion Well for Mounting Sensor in Liquid Applications Technical Specifications Product A419ABG 3C Electronic Temperature Control Setpoint Range 30 to 212 F 34 to 100 C Differential Range 1 to 30F 1 to 30C Supply Voltage 120 VAC 60 Hz Power Consumption 1 8 VA Maximum SPST Output Relay Contacts Electrical Ratings Full Load Amperes N O 12 A Locked Rotor Amperes N O 72 A Non induct...

Отзывы: