Installation Instructions

Issue Date June 16, 2003

© 2003 Johnson Controls, Inc.

1

Part No. 24-7664-2543, Rev. —

www.johnsoncontrols.com

A419ABG-3C Electronic Temperature Control

Application

IMPORTANT: 

Use this A419ABG-3C Electronic

Temperature Control only as an operating control.
Where failure or malfunction of the A419ABG-3C
Electronic Temperature Control could lead to
personal injury or property damage to the controlled
equipment or other property, additional precautions
must be designed into the system. Incorporate and
maintain other devices such as supervisory or alarm
systems or safety or limit controls intended to warn
of, or protect against, failure or malfunction of the
A419ABG-3C Electronic Temperature Control.

The A419 Electronic Temperature Control is a
single-stage, electronic temperature control. Pre-wired
cords with plug and receptacle ends are provided for
quick and simple installation.

The control features a lockable, three-button touchpad
for setup and adjustment and a Liquid Crystal Display
(LCD) which displays the sensed temperature and
other control functions. A front panel Light-Emitting
Diode (LED) indicates the output relay status. The
control has a setpoint range of -30 to 212°F
(-34 to 100°C) and is available in 120 VAC models.
See the 

Technical Specifications

 section.

The A419 control has heating and cooling modes with
adjustable setpoint and differential, an adjustable
anti-short cycle delay, and a temperature offset
(setback) function. The control provides remote
sensing capability, and electronic accuracy in a
Type NEMA 1 high-impact plastic enclosure suitable
for surface or DIN rail mounting. The temperature
sensor supplied with the control is interchangeable
with compatible Johnson Controls/PENN® A99
temperature sensors.

FCC Compliance

This equipment has been tested and found to comply
with the limits for a Class A digital device pursuant to
Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful
interference when the equipment is operated in a
commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the
instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in
a residential area is likely to cause harmful
interference, in which case the user will be required to
correct the interference at his/her own expense.

Canadian DOC Compliance

This digital apparatus does not exceed the Class A
limits for radio noise emissions from digital apparatus
set out in the Radio Interference Regulations of the
Canadian Department of Communications.

Installation

Refer to the following guidelines, procedures and
illustrations when installing an A419 control.

Parts Included

Pre-wired cords with plug and receptacle ends are
provided for quick and simple installation.

Each A419 control includes a Johnson Controls/PENN
A99 temperature sensor. The sensor may be removed
and replaced with any compatible Johnson Controls®
A99 temperature sensor, or the wire leads on the
sensor may be extended.

See the 

Mounting 

and 

Wiring

 sections for additional

guidelines and restrictions when mounting and wiring
the control.

Содержание A419ABG-3C

Страница 1: ...lity and electronic accuracy in a Type NEMA 1 high impact plastic enclosure suitable for surface or DIN rail mounting The temperature sensor supplied with the control is interchangeable with compatible Johnson Controls PENN A99 temperature sensors FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules Thes...

Страница 2: ...the sensor to the A419 control Wire insulation rating must be 90 C minimum Temperature sensor signals may be affected by electrical interference When extending sensor cable beyond 50 ft 15 2 m use a twisted pair shielded cable to reduce electrical interference A99 temperature sensors are not polarity sensitive Wire the leads to SEN and COM on the sensor terminal block TB3 See Figure 2 Keep the lea...

Страница 3: ...h IMPORTANT To ensure that the output relay operates as intended verify that all three of the jumpers are positioned properly for the application before powering the A419 control IMPORTANT The touchpad cannot be unlocked without a jumper installed across the P5 jumper pins Do not discard jumpers in case they are required in the future See Figure 4 and Figure 5 Positioning the Jumpers The P5 jumper...

Страница 4: ...blishes the minimum time that the output relay remains de energized before the next on cycle The ASd does not allow the output relay to re energize until the programmed time delay has elapsed The delay is activated when the control is first turned on and every time an on cycle ends When the delay is activated the LCD alternately flashes the sensor temperature and ASd The Anti short Cycle Delay ran...

Страница 5: ...ure If no setup entry is made for 30 seconds the control reverts to the normal temperature display IMPORTANT If MENU is not pressed after changing the setpoint value the control reverts to the previously programmed setpoint value MENU F BIN MENU Button DOWN Arrow Button UP Arrow Button Output Relay Status Indicator LED Operating Mode Indicator Temperature Units Indicator Temperature Offset Indicat...

Страница 6: ... Electrical Shock Do not touch any exposed metal parts with anything other than properly insulated tools or insulated probes of the digital voltage meter Failure to use properly insulated tools and probes may result in severe personal injuries or death If the control system does not function properly verify that the control is wired and set up properly If the problem persists use the following pro...

Страница 7: ...dicated in Figure 7 replace the A419 control i If proper operation of the A419 control is verified reconnect the load and consult the equipment manufacturer s instructions for troubleshooting the controlled equipment Fault Codes If the LCD displays an alarm or fault code SF or EE consult Table 5 for explanation Table 4 A419 Output Relay Operation in Different Operating Modes Setpoint Mode Operatin...

Страница 8: ...set WEL11A 601C Immersion Well for Mounting Sensor in Liquid Applications Technical Specifications Product A419ABG 3C Electronic Temperature Control Setpoint Range 30 to 212 F 34 to 100 C Differential Range 1 to 30F 1 to 30C Supply Voltage 120 VAC 60 Hz Power Consumption 1 8 VA Maximum SPST Output Relay Contacts Electrical Ratings Full Load Amperes N O 12 A Locked Rotor Amperes N O 72 A Non induct...

Отзывы: