background image

Part No. 24-11443-00006, Rev. B

9

NS8000 Series

Technical specifications

Supply voltage

9.8 VDC to 16.5 VDC; 15 VDC nominal (from SA bus)

Current consumption

Base current 

draw (all 

models)

Screen off

18 mA maximum (non-transmitting)

Screen on

45 mA maximum

CO

2

 models

13 mA maximum additional current (during measurement)

Note:

 SA bus applications are limited to a power load of 210 mA. The best practice when configuring an 

SA bus is to limit the total available operating power consumption to 120 mA or less. This power level 

allows you to connect a BTCVT Wireless Commissioning Converter temporarily or a DIS1710 Local 

Controller Display to the bus for commissioning, adjusting, and monitoring.

Terminations

Modular jack and

 

screw terminal block

Network sensor 

addressing

LCD full color graphical models

Configurable through graphical user interface

Wire size

Modular jack models

24 AWG or 26 AWG (0.5 mm or 0.4 mm diameter); three twisted 

pair (six conductors)

Screw terminal block models

18 AWG to 22 AWG (1 mm to 0.6 mm diameter); 22 AWG
(0.6 mm diameter)

Communication rate

Auto-detect: 9.6 kbps, 19.2 kbps, 38.4 kbps, or 76.8 kbps

Temperature measurement range

32.0°F/0°C to 104°F/40°C

Temperature sensor type

Digital temperature sensor

Humidity sensor type

Thin film capacitive sensor

Ambient conditions

Operating

32°F to 122°F (0°C to 50°C); 10% to 90% RH, noncondensing; 

85°F (29°C) maximum dew point

Storage

-40°F to 122°F (-40°C to 50°C); 5% to 95% RH, noncondensing

Temperature resolution

±0.5°F/±0.5°C

Temperature accuracy

NS Series Network Zone Sensor

±1°F/±0.6°C

Temperature element only

±0.36°F/±0.2°C at 70°F/21°C

Humidity element 

accuracy

NSB8BHxxxx-0 models

±3% RH for 20% to 80% RH at 50°F to 95°F (10°C to 35°C)
±6% RH for 10% to 20% and 80% to 90% RH at 50°F to 95°F 

(10°C to 35°C)

CO

2

 measurement range

0 ppm - 2000 ppm

CO

2

 sensor accuracy

Accuracy

±30 ppm +3% of CO

2

 reading at 77°F (25°C) and 978 hPa

(1,000 ft/300 m)

Temperature dependence

±1.4 ppm/°F (± 2.5 ppm/°C)

Pressure dependence

See Table 3 for CO

2

 altitude compensation.

CO

2

 sensor operation range

32°F to 122°F (0°C to 50°C)

Time constant

10 minutes nominal at 10 fpm airflow

Default temperature setpoint adjustment range

50°F/10°C to 86°F/30°C in 0.5° increments

CO

 sensor lifespan

10 years under standard operating conditions

LCD lifespan

Screen timeout set to off

>10 years

Screen timeout set to dim

At least 6 years

Dimensions (height x width x depth)

3.4 in. x 5 in. x 1.1 in. (85.3 mm x 127.55 mm x 26.8 mm)

Shipping weight

0.4 lb/0.18 kg

Содержание 24-11443-00006

Страница 1: ...es dispositifs de sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du network sensor Mounting 466 72 0 74 5 40 CO2 F 466 ppm 72 CO2 40 North American Emissions Compliance United States This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These l...

Страница 2: ...Note Locate the network sensor away from steam or water pipes warm air stacks unconditioned areas not heated or cooled or sources of electrical interference Height requirements may vary depending on the site Network sensors without CO2 sensing are shock and vibration resistant but not shock and vibration proof Be careful not to drop the unit or mount it where it could be exposed to excessive vibra...

Страница 3: ...adhere to these wiring details causes the network sensor to function incorrectly You will not be able to connect to the system using the Bluetooth Wireless Comissioning Converter BTCVT Mobile Access Portal Gateway MAP or the handheld VAV balancing tool and you will not be able to expand the system with future offerings IMPORTANT Do not connect the SA bus ground the modular phone jack GND or the sc...

Страница 4: ...Part No 24 11443 00006 Rev B 4 NS8000 Series 5 2 1 4 SA SA COM 15 VDC 15 VDC COM 15 VDC 1 2 5 6 4 3 COM SA SA 3 ...

Страница 5: ...e setpoint temperature Network Network connection to host controller over SA bus No No network Sensor not connected to host controller No Settings Settings menu Settings lock Lockout mode Temperature Displays current temperature No Setting enabled Toggle setting is blue Setting disabled Toggle setting is white Error Title 24 error indicator Page indicator Settings screen page indicator Scroll arro...

Страница 6: ... temperature relative humidity RH or CO2 show below the relevant icon Any interaction with a display screen activates temporary occupancy mode for 2 minutes See Figure 1 to 3 for individual graphical display screens Main screens overview Viewing the settings screens 1 Tap the Settings icon to access the settings screens 2 Tap the left and right arrows at the top of the screen to scroll through the...

Страница 7: ...s icon and use the scroll arrow to navigate to the second page 2 To change the temperature unit tap the Toggle icon to switch between Fahrenheit and Celsius Title 24 error indicators In the event of a Title 24 related error the graphical screen displays the Error icon in the upper left of the display screen with the corresponding error code number for all the required state of California Title 24 ...

Страница 8: ...curacy of the CO2 concentration measurement is essential modify the offset property of the NS Series CO2 Network Sensors Zone Quality ZN Q Analog Input AI The offset represents the local atmospheric pressure in hectopascals hPa Set the offset to the known local pressure or use the local altitude value listed in Table 3 The factory default value is 978 hPa As of Release 5 3 of the Controller Config...

Страница 9: ...e measurement range 32 0 F 0 C to 104 F 40 C Temperature sensor type Digital temperature sensor Humidity sensor type Thin film capacitive sensor Ambient conditions Operating 32 F to 122 F 0 C to 50 C 10 to 90 RH noncondensing 85 F 29 C maximum dew point Storage 40 F to 122 F 40 C to 50 C 5 to 95 RH noncondensing Temperature resolution 0 5 F 0 5 C Temperature accuracy NS Series Network Zone Sensor ...

Страница 10: ...ontact Johnson Controls www johnsoncontrols com contact us APAC JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA Europe JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY NA SA JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA Single point of contact The performance specifications are nominal and conform to acceptable indu...