Part No. 24-11443-00006, Rev. B
9
NS8000 Series
Technical specifications
Supply voltage
9.8 VDC to 16.5 VDC; 15 VDC nominal (from SA bus)
Current consumption
Base current
draw (all
models)
Screen off
18 mA maximum (non-transmitting)
Screen on
45 mA maximum
CO
2
models
13 mA maximum additional current (during measurement)
Note:
SA bus applications are limited to a power load of 210 mA. The best practice when configuring an
SA bus is to limit the total available operating power consumption to 120 mA or less. This power level
allows you to connect a BTCVT Wireless Commissioning Converter temporarily or a DIS1710 Local
Controller Display to the bus for commissioning, adjusting, and monitoring.
Terminations
Modular jack and
screw terminal block
Network sensor
addressing
LCD full color graphical models
Configurable through graphical user interface
Wire size
Modular jack models
24 AWG or 26 AWG (0.5 mm or 0.4 mm diameter); three twisted
pair (six conductors)
Screw terminal block models
18 AWG to 22 AWG (1 mm to 0.6 mm diameter); 22 AWG
(0.6 mm diameter)
Communication rate
Auto-detect: 9.6 kbps, 19.2 kbps, 38.4 kbps, or 76.8 kbps
Temperature measurement range
32.0°F/0°C to 104°F/40°C
Temperature sensor type
Digital temperature sensor
Humidity sensor type
Thin film capacitive sensor
Ambient conditions
Operating
32°F to 122°F (0°C to 50°C); 10% to 90% RH, noncondensing;
85°F (29°C) maximum dew point
Storage
-40°F to 122°F (-40°C to 50°C); 5% to 95% RH, noncondensing
Temperature resolution
±0.5°F/±0.5°C
Temperature accuracy
NS Series Network Zone Sensor
±1°F/±0.6°C
Temperature element only
±0.36°F/±0.2°C at 70°F/21°C
Humidity element
accuracy
NSB8BHxxxx-0 models
±3% RH for 20% to 80% RH at 50°F to 95°F (10°C to 35°C)
±6% RH for 10% to 20% and 80% to 90% RH at 50°F to 95°F
(10°C to 35°C)
CO
2
measurement range
0 ppm - 2000 ppm
CO
2
sensor accuracy
Accuracy
±30 ppm +3% of CO
2
reading at 77°F (25°C) and 978 hPa
(1,000 ft/300 m)
Temperature dependence
±1.4 ppm/°F (± 2.5 ppm/°C)
Pressure dependence
See Table 3 for CO
2
altitude compensation.
CO
2
sensor operation range
32°F to 122°F (0°C to 50°C)
Time constant
10 minutes nominal at 10 fpm airflow
Default temperature setpoint adjustment range
50°F/10°C to 86°F/30°C in 0.5° increments
CO
2
sensor lifespan
10 years under standard operating conditions
LCD lifespan
Screen timeout set to off
>10 years
Screen timeout set to dim
At least 6 years
Dimensions (height x width x depth)
3.4 in. x 5 in. x 1.1 in. (85.3 mm x 127.55 mm x 26.8 mm)
Shipping weight
0.4 lb/0.18 kg