Part No. 24-11443-00006, Rev. B
2
NS8000 Series
Location considerations
48 in
(1.2 m)
°C
MAX
MIN
50°C
122°F
0°C
32°F
MAX
90% RH
MIN
10% RH
85°F (29°C) MAX DP
Special tools
(only one type needed)
Johnson Controls T-4000-119 Allen-head adjustment tool
JC 5309 Allen-head flexible tool
1/16 in (1.5 mm) Allen wrench
Note:
• Locate the network sensor away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled),
or sources of electrical interference.
•
Height requirements may vary depending on the site.
•
Network sensors without CO
2
sensing are shock and vibration resistant, but not shock and vibration proof. Be careful not
to drop the unit or mount it where it could be exposed to excessive vibration. Dropping a CO
2
network sensor may result
in readings outside of the specified accuracy tolerance.