I/O terminal blocks, ratings, and

requirements

Table 2: IOM3723 terminal blocks, functions, ratings, requirements, and cables

Terminal block

label

Terminal label Function, ratings, requirements

Determine wire size and

maximum cable length

Binary Input - Dry Contact Maintained Mode

0.01 second minimum pulse width Internal 16 V, 10K ohm pull

up

IN

n

Binary Input - Pulse Counter/Accumulator Mode

0.01 second minimum pulse width
(50 Hz at 50% duty cycle)
Internal 16 V, 10K ohm pull up

BINARY INPUT

ICOM 

n

Binary Input Common

 for all Binary Input (IN) terminals

Note: 

All Binary ICOM

n

 terminals share a common,

which is isolated from all other commons, except the

Configurable Output (CO) common (OCOM

n

) when the

CO is defined as an Analog Output.

Note: 

For all Binary ICOM

n

 terminals, BI is isolated from

the FC bus common.

See Guideline A in Table 3.

Cable and wire length guidelines

The following table defines cable length guidelines for the various wire sizes that may be used for wiring low-

voltage (<30 V) input and outputs.

Table 3: Cable length guidelines

Guideline

Wire size/Gauge and type

Maximum cable length

and type

Assumptions

1.0 mm (18 AWG) stranded copper

457 m (1,500 ft) twisted wire

0.8 mm (20 AWG) stranded copper

297 m (975 ft) twisted wire

0.6 mm (22 AWG) stranded copper

183 m (600 ft) twisted wire

A

0.5 mm (24 AWG) stranded copper

107 m (350 ft) twisted wire

100 mV maximum voltage drop
Depending on the cable and the connected

input device, you may have to define an offset

in the setup software for the input or output

point.

1.0 mm (18 AWG) stranded copper

229 m (750 ft) twisted wire

0.8 mm (20 AWG) stranded copper

137 m (450 ft) twisted wire

0.6 mm (22 AWG) stranded copper

91 m (300 ft) twisted wire

B

0.5 mm (24 AWG) stranded copper

61 m (200 ft) twisted wire

100 mV maximum voltage drop
Depending on the cable and the connected

input device, you may have to define an offset

in the setup software for the input or output

point.

C

See Figure 7 to select wire size/gauge. Use

stranded copper wire.

See Figure 7 to determine

cable length. Use twisted

wire cable.

N/A

Maximum cable length versus load

current

Use the following figure to estimate the maximum

cable length relative to the wire size and the load

current (in mA) when wiring inputs.

Note: 

The following information applies to low-

voltage (<30 V) inputs only.

IOM3723 Input/Output Module Installation Guide

7

Содержание 24-10143-1124

Страница 1: ...able protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and u...

Страница 2: ...Termination Switch see Setting the End of Line EOL switch 6 Binary Input BI Terminal Block see Input and Output wiring guidelines 7 LED Status Indicators see Table 7 8 Mounting Clips Mounting Observe...

Страница 3: ...ounting features and dimensions See the following figure for mounting dimensions listed in millimeters and inches Inches are listed in parenthesis The following figure also illustrates the DIN rail ch...

Страница 4: ...n avant de r aliser un branchement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des composants con...

Страница 5: ...owing figure Figure 4 FC bus terminal block wiring When connecting the IOM to an SA bus wire the bus terminal block plugs on the expansion module and other SA bus devices in a daisy chain configuratio...

Страница 6: ...idelines about the functions ratings and requirements for the expansion module input and output terminals and references guidelines for determining proper wire sizes and cable lengths In addition to t...

Страница 7: ...pe Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 f...

Страница 8: ...functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements Recommended cable type FC or SA Bus Communications COM Signal Reference Com...

Страница 9: ...Device addresses 4 through 127 are the valid addresses for these expansion modules The DIP switch block has eight switches numbered 128 64 32 16 8 4 2 and 1 Switches 64 through 1 are device address sw...

Страница 10: ...on module components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the expansion module Important Disconnect all power sources to the expansi...

Страница 11: ...firmware package files refer to the CCT Installation Instructions LIT 12011259 LED status and states Observe the Status LEDs on the front of the expansion module Table 7 provides LED status indicator...

Страница 12: ...and Y69 Transformers Product Bulletin LIT 125755 for more information AS CBLTSTAT Cable adapter for connection to 8 pin TE 6700 Series sensors AS XFR050 0 Power transformer Class 2 24 VAC 50 VA maximu...

Страница 13: ...SA FC Bus and Supply Power 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting c...

Страница 14: ...other terms set forth at www johnsoncontrols com techterms Your use of this product constitutes an agreement to such terms Patents Patents https jcipat com Single point of contact APAC Europe NA SA JO...

Отзывы: