background image

• Mount the expansion module in an area

free of corrosive vapors and observe the

Ambient Conditions requirements in 

Technical

specifications

.

• Provide for sufficient space around the

expansion module for cable and wire

connections for easy cover removal and good

ventilation through the expansion module (50

mm [2 in.] minimum on the top, bottom, and

front of the expansion module).

• Do not mount the expansion module on

surfaces prone to vibration, such as duct work.

• Do not mount the expansion module in areas

where electromagnetic emissions from other

devices or wiring can interfere with expansion

module communication.

Observe these additional guidelines when mounting

an expansion module in a panel or enclosure:

• Mount the expansion module so that the

enclosure walls do not obstruct cover removal

or ventilation through the expansion module.

• Mount the expansion module so that the power

transformer and other devices do not radiate

excessive heat to the expansion module.

• Do not install the expansion module in an

airtight enclosure.

Figure 2: Mounting positions

Mounting features and dimensions

See the following figure for mounting dimensions

listed in millimeters and inches. Inches are listed

in parenthesis. The following figure also illustrates

the DIN rail channel and the mounting clips in an

extended position.

Figure 3: Back of expansion module

DIN rail mount applications

About this task:

Mounting the expansion module horizontally on 35

mm (1.4 in.) DIN rail is the preferred method.

To mount an expansion module on a 35 mm DIN

rail, complete the following steps:

1. Securely mount a 20 cm (8 in.) or longer

section of 35 mm (1.4 in.) DIN rail, horizontally

and centered in the desired space.

2. Pull the two bottom mounting clips outward

from the expansion module to the extended

position.

3. Hang the expansion module on the DIN rail by

the hooks at the top of the (DIN rail) channel

on the back of the expansion module, and

position the expansion module snugly against

the DIN rail.

4. Push the bottom mounting clips inward (up)

to secure the expansion module on the DIN

rail.

To remove the expansion module from the

DIN rail, pull the bottom mounting clips

out to the extended position and carefully

lift the expansion module off the DIN rail.

Wall mount applications

About this task:

IOM3723 Input/Output Module Installation Guide

3

Содержание 24-10143-1124

Страница 1: ...able protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and u...

Страница 2: ...Termination Switch see Setting the End of Line EOL switch 6 Binary Input BI Terminal Block see Input and Output wiring guidelines 7 LED Status Indicators see Table 7 8 Mounting Clips Mounting Observe...

Страница 3: ...ounting features and dimensions See the following figure for mounting dimensions listed in millimeters and inches Inches are listed in parenthesis The following figure also illustrates the DIN rail ch...

Страница 4: ...n avant de r aliser un branchement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des composants con...

Страница 5: ...owing figure Figure 4 FC bus terminal block wiring When connecting the IOM to an SA bus wire the bus terminal block plugs on the expansion module and other SA bus devices in a daisy chain configuratio...

Страница 6: ...idelines about the functions ratings and requirements for the expansion module input and output terminals and references guidelines for determining proper wire sizes and cable lengths In addition to t...

Страница 7: ...pe Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 f...

Страница 8: ...functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements Recommended cable type FC or SA Bus Communications COM Signal Reference Com...

Страница 9: ...Device addresses 4 through 127 are the valid addresses for these expansion modules The DIP switch block has eight switches numbered 128 64 32 16 8 4 2 and 1 Switches 64 through 1 are device address sw...

Страница 10: ...on module components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the expansion module Important Disconnect all power sources to the expansi...

Страница 11: ...firmware package files refer to the CCT Installation Instructions LIT 12011259 LED status and states Observe the Status LEDs on the front of the expansion module Table 7 provides LED status indicator...

Страница 12: ...and Y69 Transformers Product Bulletin LIT 125755 for more information AS CBLTSTAT Cable adapter for connection to 8 pin TE 6700 Series sensors AS XFR050 0 Power transformer Class 2 24 VAC 50 VA maximu...

Страница 13: ...SA FC Bus and Supply Power 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting c...

Страница 14: ...other terms set forth at www johnsoncontrols com techterms Your use of this product constitutes an agreement to such terms Patents Patents https jcipat com Single point of contact APAC Europe NA SA JO...

Отзывы: