Figure 6: 24 VAC supply power terminal block

wiring

Note: 

The supply power wire colors may

be different on transformers from other

manufacturers. Refer to the transformer

manufacturer’s instructions and the project

installation drawings for wiring details.

Important: 

Connect 24 VAC supply power to

the expansion module and all other network

devices so that transformer phasing is uniform

across the network devices. Powering network

devices with uniform 24 VAC supply power

phasing reduces noise, interference, and

ground loop problems. The expansion module

does not require an earth ground connection.

Terminal Wiring Guidelines,
Functions, Ratings, and
Requirements

Input and Output wiring guidelines

Table 2 provides information and guidelines about

the functions, ratings, and requirements for the

expansion module input and output terminals, and

references guidelines for determining proper wire

sizes and cable lengths.
In addition to the wiring guidelines in Table 2

• Run 

all

 low-voltage wiring and cables separate

from high-voltage wiring.

• All input and output cables, regardless of

wire size or number of wires, should consist

of stranded, insulated, and twisted copper

wires., observe these guidelines when wiring

controller inputs and outputs:

• Shielded cable is not required for input or

output cables.

• Shielded cable is recommended for input

and output cables that are exposed to high

electromagnetic or radio frequency noise.

• Inputs/outputs with cables less than 30 m

(100 ft) typically do not require an offset in

the software setup. Cable runs over 30 m (100

ft) may require an offset in the input/output

software setup.

IOM3723 Input/Output Module Installation Guide

6

Содержание 24-10143-1124

Страница 1: ...able protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and u...

Страница 2: ...Termination Switch see Setting the End of Line EOL switch 6 Binary Input BI Terminal Block see Input and Output wiring guidelines 7 LED Status Indicators see Table 7 8 Mounting Clips Mounting Observe...

Страница 3: ...ounting features and dimensions See the following figure for mounting dimensions listed in millimeters and inches Inches are listed in parenthesis The following figure also illustrates the DIN rail ch...

Страница 4: ...n avant de r aliser un branchement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des composants con...

Страница 5: ...owing figure Figure 4 FC bus terminal block wiring When connecting the IOM to an SA bus wire the bus terminal block plugs on the expansion module and other SA bus devices in a daisy chain configuratio...

Страница 6: ...idelines about the functions ratings and requirements for the expansion module input and output terminals and references guidelines for determining proper wire sizes and cable lengths In addition to t...

Страница 7: ...pe Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 f...

Страница 8: ...functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements Recommended cable type FC or SA Bus Communications COM Signal Reference Com...

Страница 9: ...Device addresses 4 through 127 are the valid addresses for these expansion modules The DIP switch block has eight switches numbered 128 64 32 16 8 4 2 and 1 Switches 64 through 1 are device address sw...

Страница 10: ...on module components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the expansion module Important Disconnect all power sources to the expansi...

Страница 11: ...firmware package files refer to the CCT Installation Instructions LIT 12011259 LED status and states Observe the Status LEDs on the front of the expansion module Table 7 provides LED status indicator...

Страница 12: ...and Y69 Transformers Product Bulletin LIT 125755 for more information AS CBLTSTAT Cable adapter for connection to 8 pin TE 6700 Series sensors AS XFR050 0 Power transformer Class 2 24 VAC 50 VA maximu...

Страница 13: ...SA FC Bus and Supply Power 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting c...

Страница 14: ...other terms set forth at www johnsoncontrols com techterms Your use of this product constitutes an agreement to such terms Patents Patents https jcipat com Single point of contact APAC Europe NA SA JO...

Отзывы: