background image

Note: 

See Table 3 to determine wire size and

cable lengths for cables.

Note: 

The SA Bus and FC Bus wiring

recommendations in this table are for MS/

TP bus at 38,400 baud. For more information,

refer to the 

MS/TP Communications Bus Technical

Bulletin (LIT-12011034)

.

Termination details

A set of Johnson Controls termination diagrams

provides details for wiring inputs and outputs to the

controllers. See the following table in this section for

the applicable termination diagram.

Table 5: Termination details

Type of device

Type of Input/

Output

Termination diagrams

Dry Contact (Binary Input)

BI

Setup and Adjustments

Setting the device address

About this task:

Metasys expansion modules are master devices

on MS/TP (SA or FC) buses. Before operating an

expansion module on a bus, you

 must

 set a valid

and unique device address for each expansion

module on the bus. You set an expansion module's

device address by setting the positions of the

switches on the DIP switch block at the top of the

expansion module . Device addresses 4 through

127 are the valid addresses for these expansion

modules.

The DIP switch block has eight switches numbered

128, 64, 32, 16, 8, 4, 2, and 1. Switches 64 through 1

are device address switches.Switch 128 is a mode

switch that enables a controller to operate on

ZFR/ZFR Pro Series Wireless Field Bus. Switch 128

must be set to off for all hard-wired SA and FC bus

applications.

Figure 8: Device address DIP switch block set to

address 21

Note: 

 

Metasys

 controllers ship with switch 128

ON and the remaining address switches OFF

rendering the controllers wired subordinate

devices, which do not operate on MS/TP buses,

but do not interfere with bus operation. Set

a valid and unique device address on the

expansion module before applying power to

the expansion module on the bus.

To set the device addresses on 

Metasys

expansion modules, complete the following

steps:

1. Set 

all

 of the switches on the address DIP

switch block (128 through 1) to OFF.

2. Set one or more of the seven address switches

(64 though 1) to ON, so that the sum of the

switch numbers set to ON equals the intended

device address, and ensure that switch 128

remains set to OFF.

IOM3723 Input/Output Module Installation Guide

9

Содержание 24-10143-1124

Страница 1: ...able protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and u...

Страница 2: ...Termination Switch see Setting the End of Line EOL switch 6 Binary Input BI Terminal Block see Input and Output wiring guidelines 7 LED Status Indicators see Table 7 8 Mounting Clips Mounting Observe...

Страница 3: ...ounting features and dimensions See the following figure for mounting dimensions listed in millimeters and inches Inches are listed in parenthesis The following figure also illustrates the DIN rail ch...

Страница 4: ...n avant de r aliser un branchement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des composants con...

Страница 5: ...owing figure Figure 4 FC bus terminal block wiring When connecting the IOM to an SA bus wire the bus terminal block plugs on the expansion module and other SA bus devices in a daisy chain configuratio...

Страница 6: ...idelines about the functions ratings and requirements for the expansion module input and output terminals and references guidelines for determining proper wire sizes and cable lengths In addition to t...

Страница 7: ...pe Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 f...

Страница 8: ...functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements Recommended cable type FC or SA Bus Communications COM Signal Reference Com...

Страница 9: ...Device addresses 4 through 127 are the valid addresses for these expansion modules The DIP switch block has eight switches numbered 128 64 32 16 8 4 2 and 1 Switches 64 through 1 are device address sw...

Страница 10: ...on module components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the expansion module Important Disconnect all power sources to the expansi...

Страница 11: ...firmware package files refer to the CCT Installation Instructions LIT 12011259 LED status and states Observe the Status LEDs on the front of the expansion module Table 7 provides LED status indicator...

Страница 12: ...and Y69 Transformers Product Bulletin LIT 125755 for more information AS CBLTSTAT Cable adapter for connection to 8 pin TE 6700 Series sensors AS XFR050 0 Power transformer Class 2 24 VAC 50 VA maximu...

Страница 13: ...SA FC Bus and Supply Power 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting c...

Страница 14: ...other terms set forth at www johnsoncontrols com techterms Your use of this product constitutes an agreement to such terms Patents Patents https jcipat com Single point of contact APAC Europe NA SA JO...

Отзывы: