Figure 7: Maximum wire length for low-voltage

(<30 V) Inputs by current and wire Size

Communications bus and supply power

wiring guidelines

Table 4 provides information about the functions,

ratings, and requirements for the expansion

module's communication bus and supply power

terminals; it additionally provides guidelines for wire

sizes, cable types, and cable lengths when wiring

the expansion module communication buses and

supply power.
In addition to the guidelines in Table 4, observe the

following guidelines when wiring an SA or FC bus

and the 24 VAC supply power:

• Run 

all

 low-voltage wiring and cables separate

from high-voltage wiring.

• All SA and FC bus cables, regardless of wire

size, should be twisted, insulated, stranded

copper wire.

• Shielded cable is strongly recommended for all

SA and FC bus cables.

• Refer to the 

MS/TP Communications Bus

Technical Bulletin (LIT-12011034)

 for detailed

information regarding wire size and cable

length requirements for the SA and FC buses.

Communications bus and supply power terminal blocks, ratings, and requirements 

Table 4: Communications bus and supply power terminal blocks, functions, ratings, requirements, and

cables

Terminal block/Port

label

Terminal labels Function, electrical ratings/Requirements

Recommended cable type

+
-

FC or SA Bus Communications

COM

Signal Reference (Common) for FC or SA Bus

communications

FC Bus

or

SA Bus

SHLD

or

SA PWR

SHLD on FC Bus:

 Isolated terminal (optional

shield drain connection)

SA PWR on SA Bus:

 15 VDC power lead

connection

Note: 

The SA PWR terminal on an IOM

expansion module does not supply 15

VDC. The SA bus supervisor supplies 15

VDC to devices on the SA bus requiring

power.

FC Bus: 0.6 mm (22 AWG) stranded, 3-wire

twisted, shielded cable recommended.
SA Bus: 0.6 mm (22 AWG) stranded, 4-

wire (2 twisted-pairs), shielded cable

recommended.

Note: 

On the SA Bus, the + and - wire

are one twisted pair, and the COM

and SA PWR are the second twisted

pair of wires.

SA/FC BUS

(Port)

RJ-12 6-Position Modular Connector provides:
FC or SA Bus Communications
FC or SA Bus Signal Reference and 15 VDC

Common
Commissioning Converter or ZFR /ZFR Pro

Wireless Router
(Maximum total current draw for SA Bus is 100

mA.)

Wireless Commissioning Converter

retractable cable or 24 AWG 3-pair CAT 3

Cable <30.5 m (100 ft)

HOT

24 VAC Power Supply - Hot
Supplies 20–30 VAC (Nominal 24 VAC)

24~

COM

24 VAC Power Supply - Common

0.8 mm to 1.0 mm
(18 AWG) 2-wire

IOM3723 Input/Output Module Installation Guide

8

Содержание 24-10143-1124

Страница 1: ...able protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and u...

Страница 2: ...Termination Switch see Setting the End of Line EOL switch 6 Binary Input BI Terminal Block see Input and Output wiring guidelines 7 LED Status Indicators see Table 7 8 Mounting Clips Mounting Observe...

Страница 3: ...ounting features and dimensions See the following figure for mounting dimensions listed in millimeters and inches Inches are listed in parenthesis The following figure also illustrates the DIN rail ch...

Страница 4: ...n avant de r aliser un branchement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des composants con...

Страница 5: ...owing figure Figure 4 FC bus terminal block wiring When connecting the IOM to an SA bus wire the bus terminal block plugs on the expansion module and other SA bus devices in a daisy chain configuratio...

Страница 6: ...idelines about the functions ratings and requirements for the expansion module input and output terminals and references guidelines for determining proper wire sizes and cable lengths In addition to t...

Страница 7: ...pe Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 f...

Страница 8: ...functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements Recommended cable type FC or SA Bus Communications COM Signal Reference Com...

Страница 9: ...Device addresses 4 through 127 are the valid addresses for these expansion modules The DIP switch block has eight switches numbered 128 64 32 16 8 4 2 and 1 Switches 64 through 1 are device address sw...

Страница 10: ...on module components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the expansion module Important Disconnect all power sources to the expansi...

Страница 11: ...firmware package files refer to the CCT Installation Instructions LIT 12011259 LED status and states Observe the Status LEDs on the front of the expansion module Table 7 provides LED status indicator...

Страница 12: ...and Y69 Transformers Product Bulletin LIT 125755 for more information AS CBLTSTAT Cable adapter for connection to 8 pin TE 6700 Series sensors AS XFR050 0 Power transformer Class 2 24 VAC 50 VA maximu...

Страница 13: ...SA FC Bus and Supply Power 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting c...

Страница 14: ...other terms set forth at www johnsoncontrols com techterms Your use of this product constitutes an agreement to such terms Patents Patents https jcipat com Single point of contact APAC Europe NA SA JO...

Отзывы: