175619-XIM-C-0109

8

Johnson Controls Unitary Products

LOCATION

Use the following guidelines to select a suitable loca-
tion for these units.

1.

Unit is designed for outdoor installation only.

2.

Condenser coils must have an unlimited supply of
air.

3.

Where a choice of location is possible, position the
unit on either north or east side of building.

4.

For ground level installation, use a level concrete
slab with a minimum thickness of 101 mm (4”). The
length and width should be at least 6 inches
greater than the unit base rails. Do not tie slab to
the building foundation.

5.

Roof structures must be able to support the weight
of the unit and its options and/or accessories. Unit
must be installed on a solid level roof curb or
appropriate angle iron frame.

6.

Maintain level tolerance to 13 mm (1/2”) maximum
across the entire length or width of the unit.

If a unit is to be installed on a roof curb or special frame
other than a YORK roof curb, gasketing must be
applied to all surfaces that come in contact with the unit
underside.

RIGGING AND HANDLING

Exercise care when moving the unit. Do not remove
any packaging until the unit is near the place of installa-
tion. Rig the unit by attaching chain or cable slings to
the lifting holes provided in the base rails. Spreader
bars, whose length exceeds the largest dimension
across the unit, MUST BE USED.

Units may also be moved or lifted with a forklift.  Slotted
openings in the base rails are provided for this pur-
pose.  Fork lengths must be a minimum of 1067 mm
(42”).

Remove the nesting brackets from the four corners on
the top of the unit.  All screws that are removed when
removing the brackets must be replaced on the unit.

Refer to Tables 4, 5 and 9 for unit weights and to Table
7  for approximate center of gravity.

CLEARANCES

All units require certain clearances for proper operation
and service. Installer must make provisions for ade-
quate ventilation air.  Refer to Dimensions and Clear-
ances shown in Figures 7 through 11 and Table 14 for
the clearances required for combustible construction,
servicing, and proper unit operation.

Before lifting a unit, make sure that all panels
are in place and that its weight is distributed
equally on all cables so it will lift evenly.

Do not permit overhanging structures or shrubs
to obstruct outdoor air discharge outlet, com-
bustion air inlet or vent outlets.

Содержание SUNLINE 2000 BQ 036

Страница 1: ...ODUCT NOMENCLATURE 6 INSTALLATION 7 OPERATION 29 START UP COOLING 33 TROUBLESHOOTING 33 MAINTENANCE 37 See the following page for a complete Table of Con tents NOTES CAUTIONS AND WARNINGS Installer sh...

Страница 2: ...BLOWERS 27 CHECKING SUPPLY AIR FLOW RATE 27 OPERATION 29 SEQUENCE OF OPERATIONS OVERVIEW 29 COOLING SEQUENCE OF OPERATION 29 CONTINUOUS BLOWER 29 INTERMITTENT BLOWER 29 NO OUTDOOR AIR OPTIONS 29 ECONO...

Страница 3: ...S Tbl Pg 1 UNIT APPLICATION DATA BQ 7 2 CONTROL WIRE SIZES 12 3 ELECTRIC HEATER SUPPLY AIRFLOW LIMITATIONS 13 4 BQ 4 POINT LOADS WEIGHT DISTRIBUTION KG LBS 17 5 BQ 6 POINT LOADS WEIGHT DISTRIBUTION KG...

Страница 4: ...hould install repair main tain or service this equipment Observe all precautions in the literature on labels and tags accompanying the equipment whenever working on air conditioning equipment Be sure...

Страница 5: ...ARNING Notes are intended to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert installer that personal injury and or equip ment damage...

Страница 6: ...ohnson Controller DFS APS Honeywell Controller DFS APS Novar Controller DFS APS Simplicity IntelliComfort Controller Simplicity IntelliComfort Controller w ModLinc 2 Pleated filters BAS Ready Economiz...

Страница 7: ...er s and or the customer s expense Size of unit for proposed installation should be based on heat loss heat gain calculation made according to the methods of the Air Conditioning Contractors of Americ...

Страница 8: ...the unit Do not remove any packaging until the unit is near the place of installa tion Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails Spreader bars wh...

Страница 9: ...should NOT be sized to match the dimensions of the duct connections on the unit Refer to Figures 7 and 10 for information concerning side and bottom supply and return air duct openings CONDENSATE DRAI...

Страница 10: ...l result in frosted coils or safety shutdown Minimum filter area and required sizes are shown in Physical Data Table 8 SERVICE ACCESS The following removable panels provide access to all serviceable c...

Страница 11: ...CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 3 1 2 4 3 1 2 4 Second stage heating not required on single stage heating units Second stage cooling not required on single stage c...

Страница 12: ...ment wire must be of the type shown on the wiring diagram and the same mini mum gauge as the replaced wire Electrical line must be sized properly to carry the load Use copper conductors only Each unit...

Страница 13: ...e Minimum Position Adjusting screw found on the damper control module fully clockwise and then set the thermostat indoor fan switch to the on position and then off or energize and de energize terminal...

Страница 14: ...the signal is below it s setpoint the actuator is allowed to modulate normally in accor dance with the enthalpy and mixed air sensor inputs When the AQ signal exceeds it s setpoint setting and there i...

Страница 15: ...175619 XIM C 0109 Johnson Controls Unitary Products 15 FIGURE 4 ENTHALPY SETPOINT ADJUSTMENT...

Страница 16: ...IAQ IAQ Min Free Cool T T1 AQ1 AQ SO SO SR SR A B C D TR TR1 24 Vac HOT 24 Vac COM EF EF1 2 3 4 5 1 Exhaust Air Adjustment Screw Exhaust Air LED Damper Min Position Screw Indoor Air Quality Max Adjust...

Страница 17: ...TRIBUTION kg Lbs UNIT TOTAL A B C D E F BQ036 252 555 37 82 37 81 36 80 46 102 47 104 48 105 BQ048 270 595 40 88 40 87 39 86 50 110 50 111 51 112 BQ060 281 620 42 92 41 91 41 90 52 114 52 116 53 117 1...

Страница 18: ...4200 4500 CONDENSER COILS Rows Deep 1 1 1 Fins Per Inch 25mm 20 20 20 Face Area m2 ft2 1 60 17 1 1 60 17 1 1 60 17 1 COMPRESSOR Qty Per Unit Type Quantity Reciprocating 1 Reciprocating 1 Scroll 1 AIR...

Страница 19: ...7 5 10 4 29 5 35 2CE045115462 10 2 14 2 34 2 40 2CE045120462 14 6 20 3 41 9 45 2CE045130462 21 5 29 9 53 9 60 Note 1 HACR Type per NEC Note 2 These electric heaters DO NOT include a fuse box If a fuse...

Страница 20: ...S 3 5 TON HEAT PUMP FRONT VIEW FIGURE 8 UNIT WITH ECONOMIZER RAINHOOD 829 325 8 1140 447 8 64 21 2 213 83 8 292 111 2 445 171 2 445 171 2 181 77 8 171 63 4 206 81 8 137 53 8 2089 821 4 165 61 2 mm inc...

Страница 21: ...ED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD FIGURE 10 UNIT DIMENSIONS REAR VIEW DETAIL B 454 177 8 184 71 4 699 271 2 485 191 8 1140 447 8 305 12 419 161 2 mm inch 260 101 4 89 31 2 210 81 4 111 43 8 mm...

Страница 22: ...FOR DICONNECT SWITCH Shipped attached to the blower housing inside the blower compartment FIELD SUPPLIED DISCONNECT SWITCH LOCATION BLOWER MOTOR ACCESS FILTER ACCESS DOT PLUGS TABLE 14 MINIMUM CLEARAN...

Страница 23: ...70 750 1440 725 1410 700 1370 675 1330 650 CFM WATTS CFM WATTS CFM WATTS CFM WATTS HI 1600 765 1540 735 1490 700 1380 670 MED 1450 690 1400 665 1360 650 1270 610 LOW 1290 625 1250 610 1220 600 1130 56...

Страница 24: ...800 LOW 1635 810 1610 780 1580 760 1555 740 1540 730 CFM WATTS CFM WATTS CFM WATTS CFM WATTS HI 1840 910 1770 825 1660 825 1530 775 MED 1620 775 1560 740 1480 700 1390 660 LOW 1510 715 1460 690 1400 6...

Страница 25: ...1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640 2300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 1535 2200 980 1160 1002 1170 1022 1190 1044 1250 1066 1350 1090 1...

Страница 26: ...15KW 0 04 0 05 0 06 0 07 0 08 0 10 0 12 0 14 0 16 20 30KW 0 06 0 07 0 08 0 09 0 11 0 13 0 15 0 17 0 20 0 06 0 07 0 08 0 09 0 10 0 11 0 12 0 14 0 16 BOTTOM DUCT CONNECTIONS1 ELECTRIC HEATERS1 RESISTAN...

Страница 27: ...st be within the limitations shown in the Unit Application Data Table 1 2 Pulleys can be adjusted in half turn increments 3 The tension on the belt should be adjusted as shown in the Belt Adjustment F...

Страница 28: ...atly measuring the pressure drop across a wet coil under field conditions would be inaccurate To assure a dry coil the compressors should be deac tivated while the test is being run 4 Knowing the pres...

Страница 29: ...the system switch set to either the AUTO or HEAT settings the blower is energized whenever a cooling or heating operation is requested The blower is ener gized after any specified delay associated wit...

Страница 30: ...ion provides minimum position but does not provide power exhaust operation MOTORIZED OUTDOOR AIR DAMPERS This system operation is the same as the units with no outdoor air options with one exception W...

Страница 31: ...low pressure switch to protect against loss of refrigerant charge opens at 48 kPa gauge 7 psig and resets at 154 kPa gauge 22 psig The above pressure switches are hard soldered to the unit The refrige...

Страница 32: ...umper across the test pin terminals on the board Depending on the selected defrost minimum run time of 30 60 or 90 minutes the board will go into defrost in 7 5 15 or 22 5 seconds The DC will remain i...

Страница 33: ...essures 2 Measure the temperature drop across the evapora tor coil 3 Measure the system Amperage draw across all legs of 3 phase power wires 4 Measure the condenser fan amp draw SHUT DOWN 1 Set the th...

Страница 34: ...room thermostat and the UCB c Loose wiring from the room thermostat to the UCB 9 If 24 volts is present at the room thermostat but not at the UCB check for proper wiring between the thermostat and th...

Страница 35: ...4 volts is pres ent at the Y1 OUT terminal check for 24 volts at the Y1 ECON terminal If 24 volts is not present check for loose wiring from the Y1 OUT terminal to the Mate N Lock plug the jumper in t...

Страница 36: ...second span the fault history is cleared TEST RESET When this button is pressed and released one time within five seconds any anti short cycle delays ASCD is by passed for one cycle When this button i...

Страница 37: ...cation of the motor and bearings can extend the life of components but is optional TABLE 8 UNIT CONTROL BOARD FLASH CODES Flash Code Description On Steady Control Failure Replace Control Heart Beat No...

Страница 38: ...otor for ten minutes until excess grease is purged from the cavity Replace the plugs 5 ton units are supplied with blower shaft bearings that do not require maintenance but may be lubricated if desire...

Страница 39: ...175619 XIM C 0109 Johnson Controls Unitary Products 39...

Страница 40: ...hange without notice Printed in U S A 175619 XIM C 0109 Copyright 2009 by Unitary Products Group All rights reserved Supersedes 175619 YIM B 0507 Johnson Controls Unitary Products 5005 York Drive Norm...