TABLE 16: SUPPLY AIR BLOWER PERFORMANCE (4 TON DIRECT DRIVE) - SIDE DUCT APPLICATION
M
3
/S
WATTS
M
3
/S
WATTS
M
3
/S
WATTS
M
3
/S
WATTS
M
3
/S
WATTS
HI
-
-
-
-
0.94
1010
0.92
975
0.90
945
MED
0.85
910
0.84
880
0.82
850
0.80
825
0.79
800
LOW
0.77
810
0.76
780
0.75
760
0.73
740
0.73
730
M
3
/S
WATTS
M
3
/S
WATTS
M
3
/S
WATTS
M
3
/S
WATTS
HI
0.87
910
0.93
825
0.78
825
0.72
775
MED
0.76
775
0.74
740
0.70
700
0.66
660
LOW
0.71
715
0.69
690
0.66
660
0.61
615
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
HI
-
-
-
-
2000
1010
1950
975
1905
945
MED
1810
910
1780
880
1740
850
1700
825
1665
800
LOW
1635
810
1610
780
1580
760
1555
740
1540
730
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
HI
1840
910
1770
825
1660
825
1530
775
MED
1620
775
1560
740
1480
700
1390
660
LOW
1510
715
1460
690
1400
660
1300
615
4
1
AVAILABLE EXTERNAL STATIC PRESSURE-Pa*
M
3
/S
149
50
74
99
124
UNIT
TONNAGE
MOTOR SPEED
4
1
174
UNIT
TONNAGE
MOTOR SPEED
AVAILABLE EXTERNAL STATIC PRESSURE-Pa*
223
198
248
CFM
UNIT
TONNAGE
MOTOR SPEED
AVAILABLE EXTERNAL STATIC PRESSURE-IWG*
0.20
0.30
0.40
0.50
0.60
4
1
UNIT
TONNAGE
MOTOR SPEED
4
1
AVAILABLE EXTERNAL STATIC PRESSURE-IWG*
0.70
0.80
0.90
1.00
1. Side Duct application (380/415 Volts)
* . Includes allowances for a wet evaporator coil, 25mm [1 in] filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values
on applications other than units with side duct airflows.