175619-XIM-C-0109
26
Johnson Controls Unitary Products
TABLE 18: BELT DRIVE BLOWER MOTOR AND DRIVE DATA
TABLE 19: STATIC RESISTANCES
mm
inch
mm
inch
mm
inch
mm
inch
mm
inch
5 TON
850-1180
1.5
1450
56
1.0
IVL44
69-97 2.8-3.8
22
7/8
127
5.0
25
1
922
36.3
A35
MODEL
BLOWER
RANGE
(RPM)
MOTOR
1
ADJUSTABLE MOTOR PULLY
HP
RPM
FRAME
SIZE
SERVICE
FACTOR
DESIG-
NATION
PITCH DIA.
DESIG-
NATION
BELT
FIXED BLOWER PULLY
BORE
PITCH DIA.
BORE
PITCH
LENGTH
1. All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because
they are located in the moving air, upstream of any heating device
1000
1200
1400
1600
1800
2000
2200
2400
2600
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.20
0.23
5-15KW
0.04
0.05
0.06
0.07
0.08
0.10
0.12
0.14
0.16
20-30KW
0.06
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.20
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.14
0.16
BOTTOM DUCT CONNECTIONS
1
ELECTRIC
HEATERS
1
RESISTANCE, IWG
CFM
DESCRIPTION
ECONOMIZER
1, 2
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 62.0 Pa [0.25 IWG], the unit will deliver less CFM during full economizer operation.
0.47
0.57
0.66
0.75
0.85
0.94
1.03
1.13
1.23
17.4
19.8
22.3
27.3
32.2
37.2
42.2
49.6
57.0
5-15KW
10.0
12.4
14.9
17.4
19.8
24.8
29.8
34.7
39.7
20-30KW
14.9
17.4
19.8
22.3
27.3
32.2
37.2
42.2
49.6
14.9
17.4
19.8
22.3
24.8
27.3
29.8
34.7
39.7
BOTTOM DUCT CONNECTIONS
1
ELECTRIC
HEATERS
1
RESISTANCE, Pa
M
DESCRIPTION
ECONOMIZER
1, 2
3
/S