53
When "Group" is selected as the debuggi ng mode, the operation mode is group
control.
Long press the "ON/OFF" key ON the inverter panel for 3 seconds, the "RUN"
light will always be ON after flashing, the inverter will start to RUN, and the
system will work (if the load is single -phase pump running for the first time,
select "Yes" after motor parameter detection, and the inverter will start to
RUN).At this point, it is necessary to check whether the photovoltaic pump
system is working normally and whether it can reach the head and flow of the
system .After running for a period of time, press the "ON/OFF" key ON the LCD
panel of the inverter to stop the inverter and turn OFF the "RUN" light.
Disconnect the DC input of the PHOTOVOLTAIC array, connect the AC input,
and repeat the above operation.
Note
!
●
Output power of inverter drives the pump working; the pump will stop
working while the inverter stops.
●
for the first test run, if there is any abnormality, the inverter will report a fault, please
refer to "
9.1 troubleshooting
" section.
●
System commissioning, may be abnormal, such as no flow, or flow rate cannot
reach the designed value, or even the three phase water pump issued by abnormal
sound. Please kindly check below:
a) Three-phase AC pump reversal (saying three-phase pump connected wrong),
you nee
d to stop and set “M-Mode”, please refer to the Chapter “
8.3.2.3 DSP
Parameter Settings
” and “
8.3.4 Parameter Settings
”;
b) Output power of PV module is too weak;
7.3 Stop Frequency Setting
Solar pump system for the first time trial run is successful, need to set the system