Toucan 1210
Toucan 1310
ELECTRICAL SYSTEM
4
4
Calibrator use as operating control instrument (test
mode) :
- Position the control panel selector either to
"platform controls" or "ground controls".
- Ensure the lower emergency stop switch is not
activated.
- Connect the calibrator to the controller and
depress the "select" button until "TEST" is
displayed.
NOTE
When "TEST" is selected, the work platform
can operate normally.
The value displayed on the screen corresponds to the
value of the acceleration input received by the motor
speed controller.
- When the joystick controller is activated at
platform controls, the acceleration input varies
from 0 to 100%.
- When controlling a superstructure function and
using the rotary potentiometer, the acceleration
input varies from 40/45% to 100%.
- The or buttons step through the other tests.
-
CL
: (closed) means that the selected speed is active.
-
OP
: (open) means that the speed is not selected or is
not active.
Diagnostic Led :
The controller is equipped with a diagnostic system
using a green LED located near the calibrator socket.
At connection the LED must light up and stay lit.
If the green LED is off :
- The controller is out of order.
- The controller circuit is faulty.
- Controller supply fault (fuses faulty in the
control circuit).
The green led may also flash a certain number of times
at connection :
-
2
flashes : "Pump inhibit" function active
(parameter Test 10 of controller = CL - see § 4.3)
-
3
flashes : Short circuit across mosfets or motor
open circuit.
-
7
flashes : Battery discharged. (Voltage below
13V).
-
8
flashes : Activation of thermal cutback (overheat).
Connections on 17 pin connector "SEVCON - MOS"
90 - "PUMP" controller :
To avoid any corrosion, the connections must be kept
well greased.
A 3,5 V voltage on pin 14 of the controller connector
corresponds to a 0% input (speed null).
A 0 V voltage on pin 14 of the controller connector
corresponds to a 100% input (max. speed).
Test
sequence
Function
Display
-
Accelerator
0 to 100%
1
Speed n°1
CL or OP
2
Speed n°2
CL or OP
3
Speed n°3
CL or OP
4
Speed n°4
CL or OP
5
Speed n°5
CL or OP
6
Speed n°6
CL or OP
7
Speed n°7
CL or OP
8
Speed n°8
CL or OP
9
Not used
10
Pump inhibit CL or OP
Содержание TOUCAN 1210
Страница 2: ......
Страница 10: ...Models Revision 03 2012 10 Toucan 1210 Toucan 1310 Thispageintentionallyleft blank CORRECTIVE ACTION REQUEST...
Страница 14: ...Models Revision 03 2012 14 Toucan 1210 Toucan 1310 Thispageintentionallyleft blank...
Страница 52: ...Models Revision 03 2012 52 Toucan 1210 Toucan 1310 Thispageintentionallyleft blank...
Страница 54: ...Models Revision 03 2012 54 Toucan 1210 Toucan 1310 ELECTRICAL SYSTEM 4 4 4 1 2 Power circuit wiring PC0338...
Страница 128: ...Models Revision 03 2012 128 Toucan 1210 Toucan 1310 NOTES...